| Date |
Text |
| 2009-03-02 16:45:32 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS WITH BUCK ENGINEERING INC. THE ENGINEERS |
| | LICENSE NUMBER IS REQUIRED IN THE TITLE BLOCK OF EACH |
| | SHEET. FAC 61G15-23.002(2) & FS 471.025. |
| | |
| | 2. SHT 1.1 EXISTING PLAN VIEW. THE APPLICATION FOR |
| | PERMIT DESCRIPTION OF PROJECT STATES, "RELOCATING |
| | EXISTING OLD BATHROOMS". EXISTING BATHROOMS ARE NOT |
| | SHOWN ON THE EXISTING PLAN VIEW. PLEASE INDICATE THE |
| | LOCATION OF THE EXISTING BATHROOMS. SECTIONS 106.1.2, |
| | 106.1.3, 106.1.1, 701.1 & 704.5. |
| | |
| | 3. SHT 2.1 CODES FOR THIS PROJECT SHALL INCLUDE THE |
| | 2007 REVISIONS TO THE FLORIDA BUILDING CODE. SECTION |
| | 106.1.1. |
| | |
| | 4. SHT 5.1 PER SECTION 1107.2 SEPARATE SECONDARY ROOF |
| | DRAINS ARE REQUIRED AND PER SECTION 1503.4.3 OF THE |
| | BUILDING CODE THE OVERFLOW SCUPPER SHALL BE A MINIMUM |
| | OF 2" AND A MAXIMUM OF 4" OFF THE ROOF TO THE FLOW |
| | LINE. PLEASE SUBMIT A DETAIL/ELEVATION SHOWING THE |
| | SEPARATE OVERFLOW SCUPPERS AND COMPLIANCE WITH |
| | 1503.4.3. |
| | |
| | 5. SHTS 2.1 & 6.1 THE CLEAR FLOOR SPACE FOR THE |
| | DRINKING FOUNTAIN IS REQUIRED TO BE FORWARD APPROACH. |
| | SECTION 11-4.15.5. SHT 2.1 SHOWS PARALLEL APPROACH. |
| | PLEASE CHANGE THE CLEAR FLOOR SPACE TO REFLECT THE |
| | REQUIRED APPROACH. |
| | |
| | 6. SHT 8.1 THE SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN. THE FLOOR DRAIN BY THE SERVICE SINK AND |
| | THE FLOOR DRAIN BY THE WATER HEATER AS WELL AS THE 3" |
| | STUB UP FOR FUTUREUSE ARE NOT SHOWN ON THE RISER. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 7. SHT 8.1 PLUMBING PLAN SHOWS NO SANITARY PIPING TO |
| | THE SERVICE SINK, NO VENT FOR THE FLOOR DRAIN BY THE |
| | WATER HEATER, NO VENT FOR THE FUTURE STUB UP IN PHASE |
| | II, NOR DOES IT SHOW THE BUILDING DRAIN EXITING THE |
| | BUILDING AND CONNECTING TO THE BUILDING SEWER AS WELL |
| | AS THE CLEANOUTS REQUIRED BY SECTIONS 708.3.1 & |
| | 708.3.5. SECTIONS 106.1.1, 701.1, 901.1. |
| | |
| | 8. SHT 8.1 THERMAL EXPANSION CONTROL IS REQUIRED PER |
| | SECTION 607.3.2. PLEASE INDICATE METHOD. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |