| 2009-02-18 13:55:37 | ***DENIED*** |
| | |
| | 1) LIFE SAFETY TO COMPLY WITH THE FLORIDA FIRE |
| | PREVENTION CODE, 2007 WHICH INCLUDES NFPA 101, 2006 AND |
| | NFPA 1, 2006 SINCE DECEMBER 31, 2008. F.A.C. 69A-60.004 |
| | |
| | 2) PROVIDE OCCUPANCY CLASSIFICATION PER 101, CHAPTER-6. |
| | |
| | 3) CLARIFY THE OCCUPANT LOAD FOR ALL AREAS BASED ON |
| | ACTUAL USE IN A CLEAR MANNER. PLEASE EXPLAIN THE FACTOR |
| | OF 100 FOR STORAGE OCCUPANCIES. 101, TABLE 7.3.1.2. |
| | |
| | 4) THE BUILDING ADDRESS THAT IS SHOWN ON SHEET 6.1 |
| | SHALL COMPLY WITH THE CITY OF WEST PALM BEACH |
| | REQUIREMENTS FOR COMMERCIAL BUILDINGS AND SHALL BE |
| | MINIMUM 6" HEIGHT, 1" WIDTH AND CONTRASTING WITH THE |
| | BACKGROUND. THE NUMERICAL SHOWN DOES NOT MATCH THE |
| | TITLE BLOCK AND PERMIT APPLICATION. |
| | |
| | 5) PLEASE ILLUSTRATE THE MAXIMUM TRAVEL DISTANCE |
| | INFORMATION ON THE LIFE SAFETY PLAN THAT INDICATES THE |
| | ACTUAL DISTANCES. |
| | |
| | 6) THE REQUIRED FIRE EXTINGUISHERS TO BE MOUNTED AT |
| | LOCATIONS NOT TO EXCEED THE 75' TRAVEL DISTANCE |
| | REQUIREMENT. |
| | |
| | 7) ADVISE IF THIS PROJECT MEETS THE DEFINITION OF |
| | MULTIPLE OCCUPANCY, 6.1.14.2.1 A BUILDING OR STRUCTURE |
| | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXISTS OR |
| | MIXED OCCUPANCY, 6.1.14.2.2 A MULTIPLE OCCUPANCY WHERE |
| | THE OCCUPANCIES ARE INTERMINGLED. |
| | |
| | 8) PLEASE LIST TYPE AND QUANTITY OF STORAGE THAT WILL |
| | BE MAINTAINED ON A DAILY BASIS. |
| | |
| | |
| | MIKE WENNERGREN, ASST. FIRE MARSHAL |
| | FIRE PLAN REVIEW |