| 2009-02-18 16:12:22 | |
| | |
| | |
| | *** DENIED *** |
| | |
| | 1) NOTE: PLANS NEED TO CONTAIN ALL OF THE FOLLOWING |
| | RELEVANT CODES ON THE ELECTRICAL SHEETS. |
| | 2004 FBC W/2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | |
| | FAC 69A-60.004, AND .003 WAS REVISED ON DECEMBER 31ST, |
| | 2008 TO ADOPT THE NEW LIFE SAFETY CODE AND FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS DO NOT |
| | CONTAIN ANY SIGNATURE, DATE OR SEAL FOR PERSON |
| | RESPONSIBLE. THEY DO CONTAIN A PRINTED NAME OF A |
| | STRUCTURAL ENGINEER. |
| | PLEASE BE SURE TO SEE FS 471.025 FOR ENGINEER AS |
| | RESPONSIBLE DESIGNER. |
| | PLEASE ALSO SEE FBC 13-103.1 FOR CERTIFICATION OF |
| | COMPLIANCE REQUIRED. |
| | PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1, .1.2 AND |
| | .1.3 FOR ALL INFORMATION ON PLANS REGARDING LIGHTING |
| | WHICH IS REQUIRED TO COORDINATE WITH SPECIFIC LIGHTING |
| | ON PLANS. |
| | BASED ON THE SUBMITTED INPUT DATA REPORT WHICH |
| | ACCOMPANIES THE SUBMITTED ENERGY CALCULATIONS SUMMARY, |
| | THE IDR DOES NOT MATCH THE PLANS. THE PLANS ACTUALLY DO |
| | CONTAIN A GREATER NUMBER OF FIXTURES ALONG WITH HIGHER |
| | WATTAGES. |
| | PLEASE SEE THE INTERIOR LIGHTING ON THE IDR WHICH ONLY |
| | INDICATES 32W YET BASED ON THE FIXTURE LEGEND FIXTURE |
| | *A* FOR EXAMPLE ARE 2-32W BULBS. |
| | *B* FIXTURES ARE 3-32W. |
| | IN EITHER CASE THE VA RATING TO BE PART OF THE IDR IS |
| | BASED ON THE EFFICIENCY RATING OF THE FIXTURE/BALLAST |
| | VA. |
| | THIS IS VERY IMPORT AS POWER FACTORS ON BALLAST FOR |
| | EXAMPLE INCLUDING BUT NO LIMITED TO1.15 OR LOWER .86 |
| | WHICH WILL GREATLY AFFECT CALCULATIONS. ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |