| Date |
Text |
| 2009-02-04 11:18:37 | BUILDING CHANGE OF USE/ALTERATION, BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FBC WITH 2007 REVISIONS. |
| | |
| | 1- DESCRIPTION OF WORK SHOWN ON PERMIT APPLICATION |
| | DOESN'T MATCH INFORMATION SHOWN ON PLANS SUBMITTED. |
| | PLANS SHOW CHANGE OF USE FROM PARKING TO MERCANTILE. |
| | REVISE DESCRIPTION ON PERMIT APPLICATION AS REQUIRED TO |
| | MATCH PLANS. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT |
| | FEES FOR CHANGE OF USE ARE REQUIRED. BRING BACK PALM |
| | BEACH COUNTY STAMPED PLANS AND COPY OF THE PAID RECEIPT |
| | IF FEES ARE DUE. IF THIS WAS DONE BEFORE, PLEASE GET |
| | THE PLANS RE-STAMPED AND BRING COPY OF PAID RECEIPT. WE |
| | NEED THIS INFORMATION FOR RECORD KEEPING. |
| | |
| | 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | 4- ACCORDING TO PROPERTY APPRAISAL WEBSITE AERIAL VIEW |
| | OF THE BUILDING (SEE ATTACHED COPY) AND DEFINITION FOR |
| | BUILDING AREA ON CHAPTER SEC. 502 OF 2004 FBC THE |
| | BUILDING IS TO BE CONSIDERED AS ONE BUILDING. NEED TO |
| | PROVIDE COMPLETE INFORMATION FOR ENTIRE BUILDING TO |
| | VERIFY COMPLIANCE WITH: |
| | A) TOTAL BUILDING AREA ALLOWED ACCORDING TO THE |
| | BUILDING CONSTRUCTION TYPE. PROVIDE CALCULATIONS TO |
| | VERIFY COMPLIANCE WITH TABLE 503 FBC 2004. |
| | |
| | B) PERCENTAGE OF OPENINGS ALLOWED, INCLUDING PROTECTED |
| | AND UNPROTECTED OPENINGS AS REQUIRED BY TABLE 704.8 FBC |
| | 2004. |
| | |
| | C) SEPARATION BETWEEN OCCUPANCIES. TABLE 302.3.2 FBC |
| | 2004. |
| | NOTE: TAKE INTO CONSIDERATION FIRE RATING OF DOORS AND |
| | WINDOWS ON WALKWAY BETWEEN THRIFT SHOP AND STORAGE. |
| | TABLE 704.8 FBC 2004. |
| | |
| | 5- ENGINEER NEEDS TO WRITE DOWN HIS LICENSE NUMBER AS |
| | REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE. PLANS ONLY SHOW THE ENGINEERING FIRM CERTIFICATE |
| | OF AUTHORIZATION NUMBER, NOT THE ENGINEER'S LICENSE |
| | NUMBER. THIS APPLIES TO TITLE BLOCK ON ALL SHEETS. |
| | |
| | 6- SHEET 2.1: |
| | A) GENERAL NOTES ON THE BOTTOM LEFT OF SHEET DON'T |
| | CORRESPOND TO THIS PROJECT. THEY CORRESPOND TO AN |
| | EATING PLACE LIKE SUBWAY. REVISE NOTES AS REQUIRED TO |
| | INCLUDE ONLY THE ONES THAT PERTAIN TO THIS JOB. |
| | |
| | B) UPDATE CODES FOR THIS PROJECT. REFER TO FBC 2004 |
| | WITH 2007 REVISIONS, NOT 2006. ALSO, THE SCOPE OF WORK |
| | INCLUDES CHANGE OF OCCUPANCY. SEE CHAPTER 8 OF 2004 |
| | FLORIDA EXISTING BUILDING CODE. |
| | |
| | C) PROJECT DATA AT THIS TENANT INFORMATION: COORDINATE |
| | ALL INFORMATION WITH ITEM #4 ABOVE. |
| | IN ADDITION CLARIFY THE FOLLOWING: |
| | * WHERE WAS GROUP M "ORDINARY HAZARD" TERM AND STORAGE |
| | S-1 "ORDINARY HAZARD" TERM TAKEN FROM. WHAT DOES |
| | "ORDINARY HAZARD" MEANS. SPECIFY CODE SECTION OR TABLE |
| | WHERE THIS WAS TAKEN FROM. |
| | |
| | ** GENERAL HEIGHT AND AREA INFORMATION IS INCORRECT |
| | BASED ON THE TYPE OF CONSNTRUCTION IIIB. REVISE AS |
| | REQUIRED. |
| | |
| | *** REVISE FIRE RATED CORRIDORS INFORMATION. SEE TABLE |
| | 1016.1 FBC 2004. |
| | |
| | **** REVISE MAXIMUM TRAVEL DISTANCE. ACCORDING TO |
| | CONSTRUCTION TYPE SHOWN THIS IS TYPE III UNSPRINKLERED. |
| | |
| | ***** REVISE INFORMATION GIVEN ON CONSTRUCTION |
| | CLASIFICATION PER TABLE 602 FBC 2004. INFORMATION IS |
| | NOT CLEAR, FIRE RATING IS NOT SPECIFIED AND NEED TO |
| | COORDINATE THIS INFORMATION WITH ITEM #4 ABOVE. |
| | |
| | ****** CLARIFY WHERE IS THE NUMBER OF PEOPLE CONSIDERED |
| | FOR THE STORAGE AREA TAKEN FROM. THIS NUMBER DOESN'T |
| | WORK WITH TABLE 1004.1.2 FBC 2004. IT CAN'T HAVE MORE |
| | PEOPLE THAN THAT ALLOWED BY THE TABLE. |
| | |
| | D) REVISE DESIGN PARAMETERS INFORMATION: WHERE IS |
| | SECTION 1609.6A-D TAKEN FROM. SEE CODE FOR CORRECT CODE |
| | SECTIONS TO BE REFERENCED. |
| | |
| | E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR RAMP |
| | HANDRAILS IN CORRIDOR BETWEEN THRIFT STORE AND STORAGE |
| | TO VERIFY COMPLIANCE WITH SEC. 11-4.8.5 FBC 2004. |
| | |
| | F) PROVIDE COMPLETE INFORMATION TO VERIFY IF HANDRAILS |
| | ARE REQUIRED OR NOT ON RAMP GOING TO THE THRIFT STORE |
| | BY EAST WALL SINGLE DOOR. |
| | |
| | G) LANDING ON EAST RAMP BY SINGLE ENTRY DOOR DOESN'T |
| | COMPLY WITH SEC. 11-4.8.4 FBC 2004. REVISE AS REQUIRED. |
| | |
| | H) MANEUVERING CLEARANCES AT DOOR LEADING TO THE WOMEN |
| | TOILET ROOM DOESN'T COMPLY WITH FIGURE 25 OF CHAPTER 11 |
| | FBC 2004. PROVIDE DIMENSIONS SHOWING COMPLIANCE. |
| | |
| | I) INFORMATION ON INTERIOR WALL DETAIL AND GENERAL WALL |
| | LEGEND DOESN'T MATCH. REVISE STUD SPACING TO MATCH. |
| | |
| | J) PROVIDE COMPLETE CALCULATIONS SHOWING HOW THE |
| | DIMENSIONS FOR ALLOWED WALL OPENINGS WHERE TAKEN FROM. |
| | IN ADDITION. NEED TO COORDINATE THIS INFORMATION WITH |
| | ITEM #4 ABOVE. PROVIDE SKETCH SHOWING CONSIDERED WALL |
| | AREAS AND CORRESPONDING DISTANCES. |
| | |
| | K) SHOW OVERALL BUILDING FOOTPRINT. COORDINATE WITH |
| | ITEM #4 ABOVE. |
| | |
| | 7- SHEET 5.1: |
| | A) PARAPET WALL DETAIL: PARAPET WALL TO HAVE THE SAME |
| | FIRE-RESISTANCE RATING AS THE WALL SUPPORTING IT AS |
| | REQUIRED BY SEC. 704.11.1 FBC 2004. REVISE AS REQUIRED. |
| | |
| | B) SHEET 2.1 SPECIFIES TYPE IIIB CONSTRUCTION TYPE. |
| | REVISE PARAPET CONSTRUCTION AS REQUIRED TO MATCH TYPE |
| | OF CONSTRUCTION SPECIFIED FOR THE BUILDING. |
| | |
| | C) PROVIDE COMPLETE TRUSS ENGINEERING PACKAGE. TRUSS |
| | PACKAGE NEED TO BE REVIEWED AND APPROVED IN WRITING BY |
| | THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS |
| | OFFICE. |
| | |
| | D) COMPONENTS AND CLADDING PRESSURES ZONES FOR ROOF |
| | SCHEDULE: CLARIFY WHY SPACING FOR NAILS AT INTERMEDIATE |
| | SUPPORTS IS NOT GIVEN FOR ROOF ZONE #3. |
| | |
| | E) PLYWOOD ROOF SHEATHING SPECIFICATIONS SHOWN ON |
| | PARAPET WALL DETAIL DON'T MATCH SPECIFICATIONS SHOWN ON |
| | COMPONENTS AND CLADDING SCHEDULE AND ON PLYWOOD |
| | SHEATHING NAILING SCHEDULE NOTE AT BOTTOM RIGHT CORNER |
| | OF SHEET. REVISE AS REQUIRED. |
| | |
| | F) ROOF DESIGN LOADS TO MATCH LOADS SPECIFIED ON SHEET |
| | 2.1. |
| | |
| | G) ROOF FRAMING PLAN: CLARIFY WHY NEW GUTTER BY OTHERS |
| | ON EXISTING HIGHER ROOF. THERE IS NOT BUILDING SECTION |
| | ON SHEET 7 AS SPECIFIED ON NOTE. PROVIDE ALL PERTINENT |
| | INFORMATION AS REQUIRED. CLARIFY IF A SEPARATE PERMIT |
| | WILL BE APPLIED FOR THE GUTTER. |
| | |
| | 8- SHEET 6.1: |
| | A) COMPONENTS AND CLADDING PRESSURES ZONES FOR WALLS |
| | SCHEDULE: CLARIFY WHY THE NAIL SPACING IS MORE CLOSER |
| | TOGETHER FOR ZONE 4 THAN FOR ZONE 5. |
| | |
| | B) CLARIFY WHY THERE IS NOT NAILING SPECIFICATIONS FOR |
| | INTERMEDIATE SUPPORTS ON ZONE 4 OF COMPONENTS AND |
| | CLADDING SCHEDULE. |
| | |
| | C) STRUCTURAL DOOR BUCK DETAIL: SEE SUBMITTED PRODUCT |
| | APPROVAL AND REVISE DOOR BUCK DETAIL AS REQUIRED. |
| | |
| | D) SOME SIZE OF WINDOWS SHOWN ON ELEVATIONS DON'T MATCH |
| | SIZE OF WINDOWS SPECIFIED ON FLOOR PLAN ON SHEET 2.1. |
| | REVISE AS REQUIRED TO MATCH. |
| | NOTE: CHECK PRODUCT APPROVAL SUBMITTED FOR MAXIMUM SIZE |
| | OF WINDOW. |
| | |
| | E) TYPICAL WALL SECTION 3/6.1: SPECIFY HOW PROVIDING |
| | THE REQUIRED FIRE RATING ON BOTH SIDES OF WALL. |
| | CORRIDOR SIDE AND INTERIOR SIDE. INCLUDING THE CEILING |
| | AREA. |
| | |
| | F) SHOW ON TYPICAL WALL SECTION 3/6.1 HOW COMPLYING |
| | WITH THE FIRE BARRIER AS REQUIRED BY SEC. 706 FBC 2004. |
| | |
| | G) TYPICAL WALL SECTION 3/6.1 TO SHOW COMPLIANCE WITH |
| | FIRE PARTITION CONTINUITY SEC. 708.4 FBC 2004. |
| | |
| | H) TYPICAL SECTION 3/6.1 SHOWS UL DESIGN U914. THESE IS |
| | FOR A 3 HOUR FIRE RATED WALL. SPECIFICATIONS SHOWN ON |
| | THIS WALL SECTION DON'T MATCH THE SPECIFICATIONS SHOWN |
| | ON UL914. REVISE AS REQUIRED TO MATCH. |
| | |
| | I) REVISE SPOUT HEIGHT AND KNEE DETAIL. SPOUT IS 36" |
| | MAX. NO MIN. |
| | |
| | J) INFORMATION FOR DETAIL 2/6.1 IS NOT CLEAR. |
| | INFORMATION IS OVERLAPPING ON THE SHEET MARGIN LINE. |
| | REVISE AS REQUIRED. |
| | |
| | K) TOILET ELEVATIONS: CLARIFY DIMENSION OF 33" AND 7" |
| | SHOWN BY THE MIRROR AND SINK SIDE. WHERE ARE THIS |
| | DIMENSIONS TAKEN FROM?. THEY DON'T WORK WITH SINK RIM |
| | HEIGHT EITHER. SEE COMMENTS ON PLANS. REVISE AS |
| | REQUIRED. |
| | |
| | 9- SHEET 7.1: |
| | A) REVISE PARAPET CONSTRUCTION ON ALL WALL SECTIONS. |
| | COORDINATE WITH ITEM #7A AND #7B ABOVE. |
| | |
| | B) REVISE ROOF SHEATHING NAILING AND SPACING ON WALL |
| | SECTIONS. COORDINATE WITH ITEM #7E ABOVE. |
| | |
| | C) INFORMATION FOR DETAILS 10/7.1 AND DETAIL 9/7.1 IS |
| | OVERLAPPING. REVISE AS REQUIRED. |
| | |
| | D) TYPICAL WALL SECTION 4/7.1 SPECIFIES UL ASSEMBLY |
| | U914, WHICH IS FOR A 3 HOUR FIRE RATED WALL. |
| | SPECIFICATIONS SHOWN ON THIS DETAIL DON'T MATCH UL 914. |
| | REVISE AS REQUIRED. |
| | |
| | 10- SHEET SEP-1: |
| | A) PROVIDE COMPLETE ENGINEERING FOR LIGHT POLES TO |
| | WITHSTAND 140MPH "SUSTAINED" WIND SPEED AS REQUIRED BY |
| | EXTERIOR LIGHT POLES NOTES #2 AND #5. |
| | |
| | B) PROVIDE SHOP DRAWINGS AND SPECIFICATIONS FOR LIGHT |
| | POLES THAT MEET THE DESIGN CRITERIA. THIS INFORMATION |
| | NEED TO BE REVIEWED AND APPROVED BY THE ENGINEER OF |
| | RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | C) SEPARATE PERMIT MAY BE REQUIRED FOR NEW PARKING |
| | WORK. COORDINATE WITH ZONING AND ENGINEERING. |
| | |
| | 11- PROVIDE COMPLETE SPECIFICATIONS FROM MANUFACTURER |
| | FOR TWO HOUR FIRE RATED CONCRETE BLOCK AS REQUIRED BY |
| | TYPE IIIB TYPE OF CONSTRUCTION SPECIFIED ON PLANS. |
| | |
| | 12- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED |
| | BY DCA RULE 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS |
| | SPECIFIED ON PLANS AND DETAILS. |
| | NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND PAGE WHERE CONNECTORS ARE SHOWN. NO NEED TO |
| | SUBMIT COMPLETE REPORT. THIS APPLIES TO STRUCTURAL |
| | CONNECTORS ONLY. |
| | |
| | 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 14- FLAT ROOF PRODUCT APPROVAL NOA 06-0626.04 |
| | SUBMITTED: SELECTED ASSEMBLY ON PAGE 11 OF 24 IS FOR AN |
| | INSULATED DECK. ALSO, IT'S LIMITED BY GENERAL |
| | LIMITATION #7. NEED TO PROVIDE SIGNED AND SEALED RAS |
| | 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND |
| | CORNER AREAS. SEE GENERAL LIMITATION #7 ON PAGE 24 OF |
| | 24. |
| | |
| | 15- PLANS AND SECTIONS DON'T SPECIFY AN INSULATED ROOF |
| | ASSEMBLY. COORDINATE AND REVISE AS REQUIRED TO MATCH |
| | FLAT ROOF PRODUCT APPROVAL. |
| | |
| | 16- ENERGY CALCULATIONS: |
| | A) NEED TO BE SIGNED AND SEALED BY THE DESIGN |
| | PROFESSIONAL WHO PREPARED THEM. MAKE SURE NAME AND |
| | LICENSE NUMBER OF ENGINEER IS PROVIDED. |
| | |
| | B) AREA DOESN'T MATCH AREA SPECIFY ON PLANS. REVISE AS |
| | REQUIRED TO MATCH |
| | |
| | 17- ASBESTOS REPORT SUBMITTED: |
| | A) REPORT NEED TO BE SIGNED AND SEALED BY THE DESIGN |
| | PROFESSIONAL WHO PREPARED IT AS REQUIRED BY CHAPTER 471 |
| | AND 481 OF FLORIDA STATUTE. PLEASE, MAKE SURE NAME OF |
| | PROFESSIONAL AND LICENSE NUMBER IS PROVIDED AND |
| | ORIGINAL SEAL AN SIGNATURE IS PROVIDED AS WELL. REPORT |
| | SUBMITTED WAS NO SIGNED AND SEALED. |
| | |
| | B) FIRM NEEDS TO PROVIDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER IN ALL SHEETS AS REQUIRED BY SEC. |
| | 61G15-23.002 AND/OR 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 18- PLEASE RETURN REVIEWED SET AFTER CORRECTIONS ARE |
| | DONE TO ORIGINAL DRAWINGS TO EXPEDITE REVIEW PROCESS. |
| | |
| | JULIO GOMEZ |