| Plan Review Notes For Permit 09010325 |
| Permit Number |
09010325 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-03-30 23:09:56 | *****UNSAT***** | | | | | | ** THE FOLLOWING THREE OF FOUR COMMENTS FROM THE | | | PREVIOUS PLAN REVIEW (2/6/09)STILL NEED TO BE ADDRESSED | | | AND/OR ACKNOWLEDGED: | | | | | | 2. THE ACTUAL PROJECT SITE ADDRESS SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 3. THE FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED FOR | | | CENTRAL STATION SERVICE. | | | | | | 4. ON SHEET FA/07, A LETTER IS ATTACHED IN REFERENCE TO | | | THE SMOKE DETECTORS WITH SOUNDER BASES HAVING BEEN | | | DESIGNED/PROGRAMMED TO GIVE A A LOCAL ALARM TO COMPLY | | | WITH NFPA 2006. HOWEVER THIS LETTER SHALL CONTAIN THE | | | PROJECT SITE ADDRESS AND BE SIGNED AND SEALED BY THE | | | ENGINEER OF RECORD AS ITS INTENDED USE. BETTER YET, | | | INCLUDE IN THE FIRE ALARM SYSTEM'S SEQUENCE OF | | | OPERATION. | | | | | | **NEW COMMENT | | | | | | A. WHERE IS THE SEQUENCE OF OPERATIONS FOR THIS FIRE | | | ALARM SYSTEM? | | | | | | B. PROVIDE SPECIFICATIONS FOR THE DEVICES/EQUIPMENT | | | THAT ARE PERTINENT AND/OR SPECIFIC FOR THE FIRE ALARM | | | SYSTEM AT THIS PROJECT SITE ONLY. | | | | | | C. PLANS ARE TO BE SIGNED AND SEALED BY THE ENGINEER OF | | | RECORD. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|