| Notes |
| Date |
Text |
| 2009-02-06 14:24:36 | ***DENIED*** | | | | | | 1) A COMPLETE FIRE PLAN REVIEW CAN NOT BE CONDUCTED AT | | | THIS TIME. IT IS DIFFICULT TO DETERMINE THE ACTUAL | | | LOCATION OF THE DEVICES AS THEY RELATE TO THE BUILDING. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS. FBC 106.1.1 | | | | | | 2) THE ADDRESS IN THE TITLE BLOCK INDICATES PALM BEACH, | | | FL. THE CORRECT JURISDICTION IS WEST PALM BEACH, FL. | | | PLEASE CORRECT THE INFORMATION AND ADD THE BUILDING | | | NUMERICAL TO EACH SHEET OF THE DRAWINGS. | | | | | | 3) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL | | | STATION SERVICE. | | | | | | 4) THE PLANS SUGGEST THAT THE APPLIANCES INSIDE THE | | | GUEST ROOMS ARE DETECTORS ACCORDING TO THE SYMBOL | | | LEGEND. PLEASE CLARIFY AS NFPA 101, 2006 SEC. 28.3.4.5 | | | REQUIRES APPROVED SINGLE STATION SMOKE ALARMS THAT WILL | | | NOT INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH | | | 9.6.2.9.4, 101. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|