Plan Review Notes
Plan Review Notes For Permit 09010325
Permit Number 09010325
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-02-06 14:24:36***DENIED***
  
 1) A COMPLETE FIRE PLAN REVIEW CAN NOT BE CONDUCTED AT
 THIS TIME. IT IS DIFFICULT TO DETERMINE THE ACTUAL
 LOCATION OF THE DEVICES AS THEY RELATE TO THE BUILDING.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS. FBC 106.1.1
  
 2) THE ADDRESS IN THE TITLE BLOCK INDICATES PALM BEACH,
 FL. THE CORRECT JURISDICTION IS WEST PALM BEACH, FL.
 PLEASE CORRECT THE INFORMATION AND ADD THE BUILDING
 NUMERICAL TO EACH SHEET OF THE DRAWINGS.
  
 3) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE.
  
 4) THE PLANS SUGGEST THAT THE APPLIANCES INSIDE THE
 GUEST ROOMS ARE DETECTORS ACCORDING TO THE SYMBOL
 LEGEND. PLEASE CLARIFY AS NFPA 101, 2006 SEC. 28.3.4.5
 REQUIRES APPROVED SINGLE STATION SMOKE ALARMS THAT WILL
 NOT INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 9.6.2.9.4, 101.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756