| Notes |
| Date |
Text |
| 2009-02-20 16:12:58 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | | | | 1. SHTS P-3 & P-4 PLUMBING 2ND FLOOR & SANITARY RISER | | | DIAGRAM SHOWS A HORIZONTAL DRY VENT UPSTREAM OF THE TUB | | | & SHOWER. THIS IS PROHIBITED BY SECTIONS 905.3 & 905.4. | | | (SEE RED LINE EXAMPLE TO CORRECT VENT). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|