| Plan Review Notes For Permit 09010315 |
| Permit Number |
09010315 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-02 16:13:26 | 2004 FBC W/2007 REVISIONS | | | INSTALL PHOTOVOLTAIC SYSTEM | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. FS 713 | | | | | | 2) SUBMIT TWO COPIES OF SIGNED, SEALED AND DATED | | | WINDLOAD CALCULATIONS USING THE 2004 FBC / ASCE7-02. | | | SEE FS 471 AND FAC 61G15.23.002 | | | | | | 3) PROVIDE A ROOF MOUNTING DETAIL SPECIFING THE | | | LOCATION, SIZE, CONFIGURATION, ETC. OF THE UNIT. | | | SPECIFY THE SIZE, LOCATION AND TYPE OF FASTENERS THAT | | | WILL BE USED TO ANCHOR THE UNIT/EQUIPMENT TO THE ROOF. | | | FBC R301.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|