| 2009-05-29 10:03:20 | MOTOR VEHICLE SHOWROOM (B), BUILDING REVIEW THIRD |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FBC WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | 2- ORIGINAL COMMENT: MEN TOILET ROOM NEEDS TO COMPLY |
| | WITH CHAPTER 11 FBC 2004 SEC. 11-4.1.3(11). IF TOILETS |
| | ARE PROVIDED THEN BOTH MEN AND WOMEN NEED TO COMPLY. |
| | RESPONSE SAYING THAT HANDICAPPED TOILET ROOM FOR MEN IS |
| | ON ANOTHER AREA DOESN'T PROVIDE EQUALITY FOR EVERYBODY. |
| | CODE SECTION REQUIRES EACH TOILET ROOM TO COMPLY. |
| | |
| | *** ARCHITECT'S RESPONSE TO THIS COMMENT: "MEN'S TOILET |
| | HAS BEEN REMOVED AS PER BUILDING DEPARTMENT |
| | REQUIREMENT". |
| | |
| | CLARIFICATION: IT IS NOT THE BUILDING DEPARTMENT |
| | REQUIREMENT TO REMOVE THE MEN'S TOILET. IF TOILETS ARE |
| | PROVIDED, THEN BOTH NEED TO COMPLY WITH SEC. |
| | 11-4.1.3(11) OF 2004 FBC. PLANS NOW SHOW ONLY TOILET |
| | ROOM FOR WOMEN. NEED TO PROVIDE TOILET ROOM FOR MEN |
| | ALSO AND BOTH NEED TO BE ADA COMPLIANT. ANOTHER |
| | SOLUTION MAY BE TO PROVIDE UNISEX TOILET. CHECK WITH |
| | THE PLUMBING CODE FOR REQUIRED NUMBER OF FIXTURES. |
| | REVISE PLANS AS REQUIRED. |
| | |
| | 3- NEED TO PROVIDE TURNING AREA AT THE KITCHENETTE AREA |
| | TO COMPLY WITH SEC. 11-4.2.3 FBC 2004. T-SHAPED SPACE |
| | SHOWN IS OUTSIDE THE KITCHENETTE AREA. NEED TO PROVIDE |
| | TURNING AREA INSIDE THE KITCHENETTE AREA. OTHERWISE A |
| | PERSON USING A WHEELCHAIR NEEDS TO REVERSE TO GET OUT. |
| | |
| | REVISED PLAN STILL DOESN'T PROVIDE TURNING AREA. |
| | HANDICAPPED PERSON USING THE REFRIGERATOR STILL HAS TO |
| | BACK UP ALL THE WAY BACK. THERE IS NO TURNING AREA |
| | PROVIDED IN THIS AREA. TURNING AREA IS STILL PROVIDED |
| | OUTSIDE THE KITCHENETTE AREA, NOT INSIDE. REVISE PLANS |
| | AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |