| Date |
Text |
| 2009-02-04 14:43:50 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A-101 REFERENCES DETAILED FIXTURE & ACCESSORIES |
| | ON SHEET A-104, BUT NO FIXTURES AND ACCESSORIES WERE |
| | FOUND. PLEASE CLARIFY & CORRELATE. SECTION 106.1.1 & |
| | CHAPTER 11. |
| | |
| | 2. SHT A-101 SUBMIT DETAILS/ELEVATIONS SHOWING |
| | COMPLIANCE WITH THE FOLLOWING: |
| | |
| | A. DRINKING FOUNTAIN |
| | 1. 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. |
| | |
| | B. W/C'S |
| | 1. 11-4.16.4 GRAB BARS (NOT SHOWN IN MEN'S TOILET |
| | ROOM). |
| | |
| | C. STALLS |
| | 1. 11-4.17.3 SIZE & ARRANGEMENT EXCEPTION (1)(2) LAV |
| | REQUIRED IN STALL. (SEE FIGURE 30(E)). |
| | |
| | D. LAV'S |
| | 1. 11-4.19.2 CLEARANCE (29"). |
| | |
| | F. TOILET ROOMS |
| | 1. 11-4.22.3 UNOBSTRUCTED TURNING AREA REQUIRED. (NOT |
| | SHOWN IN MEN'S TOILET ROOM). |
| | |
| | 3. MEN'S TOILET ROOM SHALL BE ACCESSIBLE. SECTION |
| | 11-4.1.6(1)(B). |
| | |
| | 4. A TURNING AREA IS REQUIRED AT THE KITCHENETTE. |
| | SECTION 11-4.2.3. |
| | |
| | 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM REQUIRED BY |
| | SECTION 106.3.5.1.3(3)(5)(8)(10)(13). SHOW ALL PIPE |
| | SIZES, VALVES, WATER HEATER, THERMAL EXPANSION CONTROL, |
| | WATER HAMMER ARRESTORS & RPZV BACKFLOW PREVENTOR. |
| | SECTIONS 604.1, 604.9, 606.1, 606.2, 607.13.2 & |
| | 608.13.2. |
| | |
| | 6. SHT P-102 PLUMBING SPECIFICATIONS 2(A) CODES TO |
| | INCLUDE THE 2007 AMENDMENTS TO THE FBC-2004 PLUMBING |
| | CODE. THE STANDARD CODE IS NOT ADOPTED. PLEASE DELETE |
| | REFERENCE TO STANDARD CODE. SECTION 106.1.2 |
| | |
| | 7. SHT P-102 PLUMBING SPECIFICATIONS 5(F) AIR CHAMBERS |
| | ARE NOT APPROVED. PLEASE DELETE REFERENCE. SECTION |
| | 604.9 AND PDI-WH 201. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |