| 2009-01-27 11:00:07 | MOTOR VEHICLE SHOWROOM (B), BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FBC WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. SEE ITEM #10 BELOW FOR |
| | CORRECT ADDRESS AND PARCEL ID NUMBER INFORMATION. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | 2- CLEAR FLOOR SPACE OF WOMEN HANDICAPPED RESTROOM |
| | DOESN'T COMPLY WITH SEC. 11-4.22.3 FBC 2004. THERE IS |
| | NOT AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH SEC. |
| | 11-4.2.3. |
| | |
| | 3- SPECIFY ALL DIMENSIONS ON WOMEN HANDICAPPED TOILET |
| | RESTROOM TO VERIFY COMPLIANCE WITH ALL MINIMUM |
| | CLEARANCES REQUIRED BY CHAPTER 11 FBC 2004. |
| | |
| | 4- CLARIFY WHY THE MEN'S TOILET ROOM IS NOT DESIGNED TO |
| | COMPLY WITH CHAPTER 11 FBC 2004 SEC. 11-4.1.3(11). |
| | |
| | 5- SPECIFY ALL DIMENSIONS FOR OFFICE NEXT TO THE |
| | KITCHENETTE TO VERIFY CLEARANCES BETWEEN COUNTERS. SEC. |
| | 11-4.3 FBC 2004. |
| | |
| | 6- SPECIFY ALL DIMENSIONS NEXT TO THE DOORS TO VERIFY |
| | COMPLIANCE WITH MANEUVERING CLEARANCES AT DOORS AS |
| | REQUIRED BY SEC. 11-4.13.6 FBC 2004. CHECK DOOR THAT |
| | PROVIDES ACCESS TO THE WOMENS TOILET ROOM. THERE IS NO |
| | ENOUGH ROOM. ALSO, CHECK DOOR IN OFFICE NEXT TO THE |
| | KITCHENETTE AREA. |
| | |
| | 7- UPPER CABINETS SHOWN ON OFFICE NEXT TO THE |
| | KITCHENETTE AREA AND IN THE KITCHENETTE AREA NEED TO |
| | COMPLY WITH SEC. 11-4.25.3. FBC 2004. |
| | |
| | 8- SHEET A-103: PROPOSED OPENING DETAIL SPECIFIES THAT |
| | MAXIMUM OPENING TO BE 50", WHILE SHEET A-101 SPECIFIES |
| | OPENING TO BE 4'-6" X 7'-2". REVISE AS REQUIRED TO |
| | MATCH. |
| | ***NOTE: COORDINATE OPENING DIMENSIONS WITH REQUIRED |
| | CLEARANCE FOR DOOR MANEUVERING. SEE ITEM #5 ABOVE. |
| | |
| | 9- SHEET A-105: KITCHENETTE SINK DIMENSIONS TO COMPLY |
| | WITH SEC. 11-4.24.3 (KNEE CLEARANCE), 11-4.24.4 (SINK |
| | DEPTH) AND SEC. 11-4.24.5 (CLEAR FLOOR SPACE UNDERNEATH |
| | THE SINK). REVISE AS REQUIRED. |
| | |
| | 10- CLARIFY TYPE OF HARDWARE FOR ALL ACCESSIBLE DOORS |
| | TO REVIEW COMPLIANCE WITH SEC. 11-4.13.9 FBC 2004. DOOR |
| | TYPES SHOWN ON DOOR SCHEDULE ON SHEET A-106 DON'T SHOW |
| | APPROVED TYPE OF HARDWARE. THEY SHOW TWISTING HANDLES. |
| | REVISE/CLARIFY SPECIFICATIONS AND DRAWINGS AS REQUIRED. |
| | |
| | 11- CLARIFY ADDRESS OF BUILDING. ACCORDING TO THE |
| | PROPERTY APPRAISAL WEBSITE, THERE ARE THREE DIFFERENT |
| | BUILDING WITH THREE DIFFERENT ADDRESSES THAT ARE OWNED |
| | BY THE SAME OWNER. BUILDING WHERE WORK IS TAKEN PLACE |
| | IS THE 901 S. DIXIE HWY, NOT 915 S. DIXIE HWY. SEE |
| | ATTACHED COPY OF PROPERTY APPRAISAL AERIAL VIEW. REVISE |
| | ADDRESS ON PLANS AND PERMIT APPLICATION AS REQUIRED. |
| | ***NOTE: PLEASE MAKE SURE CORRECT PARCEL ID NUMBER IS |
| | USED ON PERMIT APPLICATION TO AVOID ANY CONFLICTS OR |
| | DELAYS. ALSO, INFORMATION ON NOTICE OF COMMENCEMENT |
| | NEED TO MATCH ACCORDINGLY. |
| | |