| Plan Review Notes For Permit 09010301 |
| Permit Number |
09010301 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-30 14:11:03 | ***PROVISO*** | | | | | | 1) FIRE ALARM PANEL ENCLOSURE SHALL MEET THE | | | REQUIREMENT OF NFPA 72, 2002 FOR VOLTAGE, TEMPERATURE | | | AND HUMIDITY VARIATION. | | | | | | 2) LOCAL FIRE ALARM SYSTEMS FOR EXISTING APARTMENT | | | BUILDINGS SHALL MEET THE REQUIREMENTS OF NFPA 101, | | | 2006, SEC. 31.3.4.3.5.1 FOR FIRE DEPARTMENT | | | NOTIFICATION. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|