| 2009-02-05 10:32:16 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT 1 OF 3 EXISTING SANITARY RISER DIAGRAM FOR THE |
| | LAVS SHOW DOES NOT MEET CODE REQUIREMENTS NOR DOES IT |
| | REFLECT THE FLOOR PLAN. THE LAV IS NOT VENTED AND THE |
| | RISER SHOWS A 3RD WATER CLOSET, NOT TWO LAVS. (SEE RED |
| | LINE CORRECTION). |
| | |
| | 2. SUBMIT A SANITARY RISER DIAGRAM FOR THE NEW LAV |
| | SHOWING THE CONNECTION TO THE EXISTING SANITARY, SHOW |
| | ALL PIPE SIZES, TRAPS AND VENTS. SECTIONS |
| | 106.3.5.1.3(4)(6)(13), 701.1, 901.2.1 & 1002.1. |
| | |
| | 3. MORE INFORMATION IS REQUIRED FOR THE KITCHEN. THE |
| | EXISTING FLOOR PLAN DOES NOT INDICATE THE LOCATION OF |
| | THE KITCHEN SINK. PLEASE INDICATE THE LOCATION AS |
| | EXISTING, AND IF THE KITCHEN SINK IS MOVED TO A NEW |
| | LOCATION, THEN A SANITARY RISER DIAGRAM FOR THE KITCHEN |
| | SINK SHALL BE SUBMITTED SHOWING THE POINT OF |
| | CONNECTION, THE PIPE SIZE, TRAP & VENT. SECTIONS |
| | 106.3.5.1.3(4)(6)(13), 701.1, 901.2.1 & 1002.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |