Plan Review Notes
Plan Review Notes For Permit 09010286
Permit Number 09010286
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-05 10:32:16DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT 1 OF 3 EXISTING SANITARY RISER DIAGRAM FOR THE
 LAVS SHOW DOES NOT MEET CODE REQUIREMENTS NOR DOES IT
 REFLECT THE FLOOR PLAN. THE LAV IS NOT VENTED AND THE
 RISER SHOWS A 3RD WATER CLOSET, NOT TWO LAVS. (SEE RED
 LINE CORRECTION).
  
 2. SUBMIT A SANITARY RISER DIAGRAM FOR THE NEW LAV
 SHOWING THE CONNECTION TO THE EXISTING SANITARY, SHOW
 ALL PIPE SIZES, TRAPS AND VENTS. SECTIONS
 106.3.5.1.3(4)(6)(13), 701.1, 901.2.1 & 1002.1.
  
 3. MORE INFORMATION IS REQUIRED FOR THE KITCHEN. THE
 EXISTING FLOOR PLAN DOES NOT INDICATE THE LOCATION OF
 THE KITCHEN SINK. PLEASE INDICATE THE LOCATION AS
 EXISTING, AND IF THE KITCHEN SINK IS MOVED TO A NEW
 LOCATION, THEN A SANITARY RISER DIAGRAM FOR THE KITCHEN
 SINK SHALL BE SUBMITTED SHOWING THE POINT OF
 CONNECTION, THE PIPE SIZE, TRAP & VENT. SECTIONS
 106.3.5.1.3(4)(6)(13), 701.1, 901.2.1 & 1002.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  