Plan Review Notes
Plan Review Notes For Permit 09010286
Permit Number 09010286
Review Stop M
Sequence Number 1
Notes
Date Text
2009-02-15 10:18:49REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE SCOPE OF A/C WORK AS SHOWN ON PLANS IS NOT
 CLEAR. ONLY AN "EXISTING HVAC" PLAN IS PROVIDED WITH NO
 CHANGES SHOWN ON PLANS. PLEASE SHOW ON PLANS WHICH
 PARTS OF THE A/C SYSTEM ARE BEING REMOVED AS WELL AS
 WHICH WORK IS TO BE NEW IN ACCORDANCE WITH FBCB
 106.1.1.
  
 2. PLEASE CLARIFY ALL DUCT SIZES SHOWN ON PLANS. ONE
 DUCT IS MARKED WITH A SIZE OF "MX6." IT IS NOT CLEAR
 WHAT THE SIZE OF THIS DUCT IS. ALSO, PLEASE INDICATE
 SIZES AT ALL DUCT TRANSITIONS TO CLARIFY THE DUCT SIZE
 ON BOTH SIDES OF THE TRANSITIONS IN ACCORDANCE WITH
 FBCM 603.1.
  