| Plan Review Notes For Permit 09010286 |
| Permit Number |
09010286 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-15 10:18:49 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. THE SCOPE OF A/C WORK AS SHOWN ON PLANS IS NOT | | | CLEAR. ONLY AN "EXISTING HVAC" PLAN IS PROVIDED WITH NO | | | CHANGES SHOWN ON PLANS. PLEASE SHOW ON PLANS WHICH | | | PARTS OF THE A/C SYSTEM ARE BEING REMOVED AS WELL AS | | | WHICH WORK IS TO BE NEW IN ACCORDANCE WITH FBCB | | | 106.1.1. | | | | | | 2. PLEASE CLARIFY ALL DUCT SIZES SHOWN ON PLANS. ONE | | | DUCT IS MARKED WITH A SIZE OF "MX6." IT IS NOT CLEAR | | | WHAT THE SIZE OF THIS DUCT IS. ALSO, PLEASE INDICATE | | | SIZES AT ALL DUCT TRANSITIONS TO CLARIFY THE DUCT SIZE | | | ON BOTH SIDES OF THE TRANSITIONS IN ACCORDANCE WITH | | | FBCM 603.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|