| Plan Review Notes For Permit 09010286 |
| Permit Number |
09010286 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-10 13:19:10 | ***DENIED*** | | | | | | 1) PLANS SUBMITTED AFTER DEC.31, 2008 SHALL COMPLY WITH | | | NFPA 101, 2006 EDITION. | | | | | | 2) PLEASE SHOW THE LOCATIONS OF THE EXISTING AND OR NEW | | | HARD WIRED SMOKE ALARMS THAT SHALL BE INTERCONNECTED TO | | | CAUSE THE ACTIVATION OF (1) SMOKE ALARM TO ACTIVATE ALL | | | THE SMOKE ALARMS. 101, SEC. 9.6.2.9. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|