| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET #3, UNLESS OTHERWISE |
| | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1).THE NEW BATHROOM DOES NOT |
| | COMPLY. LIST THIS CIRCUIT IN THE PANEL SCHEDULE. |
| | |
| | 2} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. INDICATE GFI |
| | ON THE PLANS AND CORRECT THE SPACING. |
| | |
| | 3} THE REFRIGERATOR CIRCUIT WAS NOT MOVED TO THE NEW |
| | REFRIGERATOR LOCATION ACCORDING TO THE RECEPTACLE |
| | NUMBER. 408.4. |
| | |
| | 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE |
| | INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |