Plan Review Notes
Plan Review Notes For Permit 09010273
Permit Number 09010273
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-29 06:39:422004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. 561-233-5025
  
 3) THE DESCRIPTION OF WORK THAT IS LISTED ON THE
 APPLICATION STATES ENCLOSING SCREEN PORCH. THERE IS NO
 RECORD OF AN EXISTING SCREEN PORCH INDICATED ON THE
 SURVEY OR WITH THE PROPERTY APPRAISER'S OFFICE. THE
 PLANS ALSO DO NOT INDICATE AN EXISTING SCREEN PORCH AT
 THE LOCATION OF THIS WORK. THEREFORE, BASED ON THE
 INFORMATION THAT WAS SUBMITTED, IT IS ASSUMED THAT THIS
 IS AN ADDITION.
  
 4) THE PLANS SPECIFY THIS AS A LEVEL 2 ALTERATION.
 HOWEVER, IT APPEARS TO BE AN ADDITION. PLEASE CLARIFY.
 SEE 2004 FBC EXISTING BUILDING CHAPTER 3.
  
 4) THE VALUE THAT WAS SPECIFIED FOR THE SCOPE OF WORK
 SHOWN ON THE PLANS IS LOW. PER FBC 108.3 CITY
 AMENDMENTS THE VALUE HAS BEEN ADJUSTED TO $ 29141.00
 BASED ON THE ICC BUILDING VALUATION DATA. ADDITIONAL
 FEES OF $ 625.09 ARE DUE.
  
 5) PROVIDE A TYPICAL FRAMING DETAIL FOR EXTERIOR WALL
 OPENINGS. SPECIFY HEADERS, STRAPPING ETC. FBC R602.
  
 6) SPECIFY THE REQUIRED SPECIES AND GRADE OF WOOD FOR
 RAFTERS AND WALLS. FBC R602 AND R802
  
 7) SPECIFY THE SPACING OF THE 2 X 6 WALL STUDS ON THE
 PLANS. FBC R602
  
 8) SHOW COMPLIANCE WITH R703.6.3 WHERE CEMENT PLASTER
 (STUCCO) IS TO BE APPLIED TO LATH OVER FRAME
 CONSTRUCTION, MEASURES SHALL BE TAKEN TO PREVENT
 BONDING BETWEEN THE CEMENT PLASTER AND THE
 WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED
 BETWEEN THE WATER-RESISTIVE BARRIER AND THE CEMENT
 PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 MATERIAL; OR
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP; OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 9) SHOW COMPLIANCE WITH R320.1 TERMITE PROTECTION SHALL
 BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION (SEE SECTION 202, REGISTERED
 TERMITICIDE). UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.
  
 10) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1/8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS. A CONTINUOUS EAVE VENT WILL BE REQUIRED.
  
 11) SPECIFY THE LENGTH/EMBED DEPTH OF THE 3/4" ANCHOR
 BOLTS FOR THE BOTTOM PLATE. R403.1.6 REQUIRES A MINIMUM
 OF 7" INTO CONCRETE.
  
 12) SUBMIT TWO COPIES OF THE SURVEY. FBC 106.1* CITY
 AMENDMENTS
  
 13) SUBMIT TWO COPIES OF ENERGY CALCULATION FORMS AS
 REQUIRED BY FBC 13-6.
  
 14) SUBMIT TWO COPIES OF PRODUCT APPROVALS. DCA RULE
 9B-72 AND FBC 106.1* CITY AMENDMENTS
  
 15) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 16) SUBMIT PRODUCT APPROVALS FOR THE BUILT-UP ROOF
 SYSTEM SPECIFIED ON THE PLANS. THE ROOFING PRODUCT
 APPROVAL THAT WAS SUBMITTED IS FOR ASPHALT SHINGLES
 WHICH CAN NOT BE USED ON A FLAT ROOF.
  
 17) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 OUTSWING DOORS IS FOR AN IMPACT RATED GLAZED DOOR.
 SUBMIT THE PRODUCT APPROVALS FOR THE STORAGE ROOM DOOR,
 UNLESS THIS IS THE TYPE OF DOOR THAT WILL BE INSTALLED
 ON THE STORAGE ROOM. DCA RULE 9B-72
  
 NOTE: THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 WINDOWS AND GLASS DOOR ARE LARGE MISSILE IMPACT RATED
 AND DO NOT REQUIRE STORM PANELS. HOWEVER, IF IMPACT
 WINDOWS AND DOORS WILL NOT BE USED, PRODUCT APPROVALS
 FOR STORM PANELS WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]