| Plan Review Notes For Permit 09010259 |
| Permit Number |
09010259 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-02-23 15:37:18 | 2004 FBC W/2007 REVISIONS | | | ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) ON SHEET A-6 UNDER ROOF NOTES AND TRUSS LOADING THE | | | EXPOSURE CATEGORY HAS NOT BEEN CHANGED FROM 'B' TO 'C'. | | | PLEASE CORRECT. FBC R301.2.1.4 | | | | | | 2) FACED BATT INSULATION CAN NOT BE INSTALLED AS SHOWN | | | ON SHEET A-3. THE EXPOSED VAPOR BARRIER FACING IS | | | FLAMMABLE. ALSO THE TOP CORD OF THE TRUSSES ARE 2 X 4S | | | AND THE R-19 BATTS ARE 6'. PLEASE CORRECT. IF THE | | | INSULATION IS INSTALLED AT THE CEILING, ATTIC | | | VENTILATION WILL BE REQUIRED IN COMPLIANCE WITH FBC | | | R806.1. | | | | | | 3) THE CEILING TYPE IS SPECIFIED AS UNDER ATTIC ON THE | | | ENERGY CALCULATION FORMS AND PLANS SHOW IT INSTALLED AS | | | A SINGLE ASSEMBLY WITH NO ATTIC. PLEASE CORRECT. SEE | | | FBC 13-604 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|