| Plan Review Notes For Permit 09010258 |
| Permit Number |
09010258 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-24 12:10:44 | 1. STRUCTURAL DETAIL FOR CONDENSER WALL MOUNTING STANDS | | | NOTE THAT THEY ARE ONLY VALID WITH RAISED SEAL AND FOR | | | ONE JOB ONLY. PROVIDE RAISED SEAL DRAWINGS FROM | | | DESIGNER OF RECORD AND MARK DRAWING WITH JOBSITE | | | ADDRESS. SHOP DRAWINGS SHALL ALSO BE REVIEWED AND | | | APPROVED IN WRITING BY THE PROJECT DESIGNER OF RECORD. | | | FBCB 105.3.1.2, FBCB 106.1. IF THESE ARE PRE-ENGINEERED | | | STANDS, PROVIDE PRODUCT APPROVAL WHICH HAS BEEN | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD IN | | | ACCORDANCE WIH FBCB 106.3.3. | | | | | | 2. DETAIL DRAWINGS FOR WALK-IN COOLER CONSTRUCTION | | | CONTAIN A NOTE STATING "NOT FR CONSTRUCTION." IF THEY | | | ARE NOT FOR CONSTRUCTION, WHY ARE THEY BEING SUBMITTED | | | FOR PERMIT? PROVIDE DOCUMENTATION WHICH IS INTENDED TO | | | BE CONSTRUCTED IN ACCORDANCE WITH FBCB 106.1.1. | | | | | | 3. THE PROPOSED COOLER ENCLOSURES ARE TO BE INSTALLED | | | OUTDOORS. PROVIDE SUPPORTING DOCUMENTATION SHOWING | | | THESE COOLERS ARE DESIGNED FOR WIND RESISTANCE IN | | | ACCORDANCE WITH FBCM 301.13. SUPPORTING DOCUMENTATION | | | SHALL BE APPROVED IN WRITING BY THE PROJECT DESIGNER OF | | | RECORD. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|