| 2009-01-28 14:10:41 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. DOCUMENTS PREPARED BY AN ENGINEER OR ARCHITECT AND |
| | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, |
| | DATED ORIGINALS FS471, FS481 (SHEET A2.1, SHEET E1.3, |
| | ENGINEERING BY FRANK BENNARDO, PE). |
| | |
| | 2. GOVERNING CODE SHOULD INCLUDE 2007 |
| | REVISIONS/SUPPLMENTS, BRACKET ENGINEERING. |
| | |
| | 3. COOLER SPEC SHEETS; THERE IS INFORMATION HAND |
| | WRITTEN ON THE SPEC SHEETS, BUT THE NOTES ARE |
| | ILLEGIBLE. THE PLAN REFERS TO "STANDARD BUILDING CODE". |
| | THIS CODE HAS NOT BEEN IN EFFECT FOR MANY YEARS; PLEASE |
| | REVISE TO DECLARE GOVERNING CODE. WIND DESIGN DOES NOT |
| | REFER TO EXPOSURE CLASSIFICATION FBC1609, AND THE |
| | PERSON TAKING RESPONSIBILITY FOR THE DESIGN IS TO SIGN |
| | THE PLAN FBC*106. AS IT IS NOT CLEAR WHICH UNITS WILL |
| | BE WALL MOUNTED AND WHICH WILL BE FLOOR MOUNTED, IT IS |
| | NOT CLEAR WHETHER OR NOT WIND DESIGN CRITERIA APPLY. |
| | |
| | 4. SHOP DRAWINGS ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD, FBC*106, FBC16. |
| | |
| | 5. DELEGATED ENGINEERING IS TO BE REVIEWED BY DESIGNER |
| | OF RECORD, FAC61G15, FAC61G1. |
| | |
| | 6. PROVIDE A PLAN WHICH SHOWS LOCATION OF WHERE THE |
| | WALL MOUNT BRACKETS WILL BE USED. THE PLANS ARE NOT |
| | CLEAR; WILL THESE BRACKETS BE USED FOR ALL FOUR? |
| | NOTHING ON THE PLAN INDICATES SUCH. FBC*106. |
| | |
| | 7. PLEASE PROVIDE TOTAL VALUE FOR THIS JOB; LABOR AND |
| | MATERIALS. |
| | |
| | |
| | |
| | |