| Plan Review Notes For Permit 09010216 |
| Permit Number |
09010216 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-06 14:42:44 | \ | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PROJECT DESCRIPTION ON THE APPLICATION INDICATES | | | AN ILLUMINATED SIGN BUT NO ELECTRICAL PLANS OR | | | SPECIFICATION WERE SUBMITTED FOR REVIEW. | | | | | | 2} THE DESCRIPTION ALSO INDICATES REMOVING THE | | | "EXISTING" WALL SIGNS. THIS IS A NEW BUILDING WITH NO | | | SIGN PERMITS, WHICH SIGNS ARE "EXISTING"? | | | | | | 3} A DISCONNECTING MEANS PER 600.6 FOR THE CIRCUITS | | | REQUIRED BY 600.5. LOCATED ON THE PLANS | | | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|