Plan Review Notes
Plan Review Notes For Permit 09010216
Permit Number 09010216
Review Stop E
Sequence Number 1
Notes
Date Text
2009-02-06 14:42:44\
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PROJECT DESCRIPTION ON THE APPLICATION INDICATES
 AN ILLUMINATED SIGN BUT NO ELECTRICAL PLANS OR
 SPECIFICATION WERE SUBMITTED FOR REVIEW.
  
 2} THE DESCRIPTION ALSO INDICATES REMOVING THE
 "EXISTING" WALL SIGNS. THIS IS A NEW BUILDING WITH NO
 SIGN PERMITS, WHICH SIGNS ARE "EXISTING"?
  
 3} A DISCONNECTING MEANS PER 600.6 FOR THE CIRCUITS
 REQUIRED BY 600.5. LOCATED ON THE PLANS
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  