| Plan Review Notes For Permit 09010187 |
| Permit Number |
09010187 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-17 13:36:07 | PLEASE NOTE THAT PLANS WILL REMAIN IN FAILED STATUS | | | UNTIL REVIEWED AND APPROVED FOR PERMIT APPLICATION. | | | PLEASE SEE THE FOLLOWING: | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE | | | PREVENTION CODE, 2007 EDITION TO INCLUDE NFPA 101, 2006 | | | AND NFPA 1, 2006. THIS CURRENT ADOPTED CODE HAS BEEN IN | | | EFFECT SINCE DECEMBER 31, 2008. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM REMODEL PRIOR TO | | | EQUIPMENT INSTALLATION. | | | | | | 3) FIRE SPRINKLER SYSTEM TO COMPLY WITH NFPA 13, 2002 | | | EDITION. SHEET F001, NOTE #1 | | | | | | 4) DUCT SMOKE DETECTORS TO BE WIRED INTO FIRE ALARM | | | SYSTEM THAT UPON ACTIVATION WILL CAUSE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|