Plan Review Notes
Plan Review Notes For Permit 09010187
Permit Number 09010187
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-02-17 13:36:07PLEASE NOTE THAT PLANS WILL REMAIN IN FAILED STATUS
 UNTIL REVIEWED AND APPROVED FOR PERMIT APPLICATION.
 PLEASE SEE THE FOLLOWING:
  
 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2007 EDITION TO INCLUDE NFPA 101, 2006
 AND NFPA 1, 2006. THIS CURRENT ADOPTED CODE HAS BEEN IN
 EFFECT SINCE DECEMBER 31, 2008.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL PRIOR TO
 EQUIPMENT INSTALLATION.
  
 3) FIRE SPRINKLER SYSTEM TO COMPLY WITH NFPA 13, 2002
 EDITION. SHEET F001, NOTE #1
  
 4) DUCT SMOKE DETECTORS TO BE WIRED INTO FIRE ALARM
 SYSTEM THAT UPON ACTIVATION WILL CAUSE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756