2009-02-05 09:40:31** DENIED **
  
  
 1) NOTE: ** IMPORTANT***
 THE PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW.
 UNDER PLAN REVIEW THIS DOES NOT LOCK ANY PROJECT UNDER
 THIS CURRENT SET OF CODES. IT SHOULD BE KNOWN THAT AS
 OF MARCH 1ST, 2009 THE STATE OF FLORIDA WILL BE
 ADOPTING THE NEW SET OF CODES. THIS WILL INCLUDE THE
 2007 FBC ALONG WITH SEVERAL NEW ADOPTED CODES. ONLY
 PLANS SUBMITTED UNDER **PERMIT APPLICATION* WITH
 LICENSED CONTRACTOR AND APPLICABLE FEES PAID BEFORE
 MARCH 1ST, 2009 WILL LOCK IN PROJECT UNDER THE CURRENT
 CODES.
 IT IS ALSO IMPORTANT TO KNOW THAT PER THE STATE FIRE
 MARSHAL. THE 2007 FLORIDA FIRE PREVENTION CODE AS OF
 DECEMBER 31ST, 2008 HAS BEEN ADOPTED. THE 2006 NFPA-101
 IS NOW IN EFFECT. PLEASE ADJUST CODE DESIGN AND CODE ON
 PLANS.
  
 2) NOTE: PLEASE PROVIDE MORE IDENTIFICATION ON RISER.
 IS ALL OF THIS EXISTING TO REMAIN? SOME ITEMS ARE
 SPECIFIC ON RISER AS BEING EXISTING HOWEVER NOT ALL.
 IF THE ENTIRE RISER IS EXISTING NOT EACH AN EVERY ITEM
 NEEDS TO BE NOTED IF THE MAIN DESCRIPTION WHICH STATES
 *ELECTRICAL ONE-LINE DIAGRAM* STATES IT IS EXISTING.
 IF SOME OF THESE ITEMS ARE NEW THEN RISER NEEDS MORE
 INFORMATION FOR REVIEW OF CONDUCTORS ETC.
 215.5,230,220,310.16 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1,
 13-415.1.ABC.1.1,.1.2, .1.3. ALL NEW DEVICES BEING
 INSTALLED NEED TO MEET THE SECTIONS NOTED. ** THIS IS
 FOR NEW BEING INSTALLED ONLY.
  
 4) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2
 FOR LIGHTING PERFORMANCE CALCULATIONS NEEDED. NO NEW
 LIGHTING MAY BE ADDED UNLESS EXISTING IS BELOW
 ALLOWANCE LEVELS AND NEW LIGHTING BEING DESIGNED DOES
 NOT EXCEED THE LEVELS IN TABLES SET FORTH IN THE FBC.
 *** IF THERE ARE QUESTIONS, PLEASE CALL TO GO OVER.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  