Plan Review Notes
Plan Review Notes For Permit 09010157
Permit Number 09010157
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-13 14:36:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SHUTTER CONNECTION TYPES A AND H REQUIRE CONCRETE
 SUBSTRATE WHICH HAS A MINIMUM STRENGTH OF 3KSI (AS PER
 NOTES ON SHEET 14), SEE ANCHOR CHART ON SHEET 13. IF
 CONTRACTOR SPECIFIES CONCRETE, CONTRACTOR IS TO PROVIDE
 EVIDENCE THAT THE EXISTING CONCRETE MEETS THE MINIMUM
 STRENGTH REQUIREMENTS; OTHERWISE, MUST USE
 SPECIFICATIONS FOR HOLLOW BLOCK.
  
 2. SEE SHEET 14, AN EDGE DISTANCE OF 3" REQUIRES A
 FACTOR OF .83 APPLIED TO THE ANCHOR SPACING.