| Plan Review Notes For Permit 09010116 |
| Permit Number |
09010116 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-04-30 09:01:18 | | | | | | | | | | | | | PROVISO | | | | | | THE "MAIN BONDING JUMPER" SHOWN INSTALLED IN THE | | | GENERATOR, SHEET "E-4" MUST NOT BE INSTALLED AS IT | | | CREATES A PARALLEL PATH BETWEEN THE GENERATOR NEUTRAL | | | AND THE SYSTEM EQUIPMENT GROUND. THE EQUIPMENT GROUND | | | AND NEUTRAL MUST REMAIN ISOLATED, 250.6 NEC, UNLESS THE | | | GENERATOR WAS A SEPARATELY DERIVED SYSTEM, WHICH WOULD | | | REQUIRE A 4 POLE ATS. | | | | | | SUBMIT MANUFACTURERS SPECIFICATIONS FOR THE NEW 60KW | | | EMERGENCY GENERATOR SHOWN ON SHEET E-1. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|