2009-04-30 09:01:18 
  
  
  
 PROVISO
  
 THE "MAIN BONDING JUMPER" SHOWN INSTALLED IN THE
 GENERATOR, SHEET "E-4" MUST NOT BE INSTALLED AS IT
 CREATES A PARALLEL PATH BETWEEN THE GENERATOR NEUTRAL
 AND THE SYSTEM EQUIPMENT GROUND. THE EQUIPMENT GROUND
 AND NEUTRAL MUST REMAIN ISOLATED, 250.6 NEC, UNLESS THE
 GENERATOR WAS A SEPARATELY DERIVED SYSTEM, WHICH WOULD
 REQUIRE A 4 POLE ATS.
  
 SUBMIT MANUFACTURERS SPECIFICATIONS FOR THE NEW 60KW
 EMERGENCY GENERATOR SHOWN ON SHEET E-1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  