Plan Review Notes
Plan Review Notes For Permit 09010116
Permit Number 09010116
Review Stop B
Sequence Number 2
Notes
Date Text
2009-04-08 16:02:07BUILDING PLAN REVIEW
 PERMIT:09010116
 ADD: 7915 S. DIXIE HWY
 CONT: CHINCHOR ELECTRIC INC.
 TEL: (386)774-1020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-8-09
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NO RESPONSE NOT ADDRESSED: SHEET S-1 SHOWS TWO
 DIFFERENT TYPES OF BEAMS. DETAIL #1 SHOW A "BOND
 BEAM"WITH 2 #5 REINFORCING BARS AND THE TYPICAL MASONRY
 WALL CONSTRUCTION DETAIL SHOW A CAST IN PLACE
 REINFORCED CONCRETE TIE BEAM WITH NO DIMENSIONS.
 CLEARLY STATE WHICH BEAM DETAIL WILL BE USED? THE
 FOUNDATION PLAN DETAIL FAIL TO SHOW THE LOCATION OF THE
 VERTICAL REINFORCING BARS AS STATED IN THE NOTE BELOW.
 ON SHEET S-1, PLEASE INDICATE THE TYPE AND SIZE OF THE
 MATERIALS FOR EACH DETAIL. SHOW THE BRACING DETAIL FOR
 THE MASONRY CONSTRUCTION PER FBC 2104.1.9
  
 3) NO RESPONSE NOT ADDRESSED: SHEET E-3 SHOWS
 ADDITIONAL STRUCTURAL INFORMATION THAT IS NOT SHOWN ON
 THE SHEET (S-1), EXAMPLE THE DOORS AND BOLLARDS WITH
 THE DOT GUARDRAIL. THE NEW MASONRY WALL NEEDS TO SHOW A
 HEADER DETAIL FOR THE TWO DOORS. WILL THE DOOR HEADER
 BE CONSTRUCTED WITH A REINFORCED CONCRETE OR WILL A
 LINTEL BE USED? IF THE LINTEL WILL BE USED, PROVIDE THE
 PRODUCT APPROVAL INDICATING THE SIZE OF THE LENTIL.
 PROVIDE PRODUCT APPROVAL FOR THE TWO DOORS AND INDICATE
 OR HI-LIGHT ALL INFORMATION PERTAINING TO THE
 INSTALLATION OF THE DOORS FROM THE INSTALLATION
 INSTRUCTIONS ON EACH PAGE OF THE PRODUCT APPROVAL.
  
 4) NO RESPONSE NOT ADDRESSED: SHEET E-3 AND S-1 HAVE
 DIFFERENT ENGINEERS, THEREFORE THE WIND DESIGN
 INFORMATION SHALL BE SHOWN BY EACH ENGINEER IN
 ACCORDANCE WITH 1603.1.4 AND 1609.1.3. IS THE GUARDRAIL
 ATTACHED TO THE BOLLARDS? IF SO, PROVIDE A DETAIL FOR
 THE ATTACHMENT. THERE IS A NOTE AT THE TOP LEFT SECTION
 OF SHEET E-3 STATING "8" HIGH BLOCK WALL PAINT TO
 MATCH", ISN'T THIS A 14' HIGH WALL? CLARIFY.
  
 5) OK
  
 6) SUBMIT THE SOIL REPORT PER FBC 1802.6
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  