| 2009-04-08 16:02:07 | BUILDING PLAN REVIEW |
| | PERMIT:09010116 |
| | ADD: 7915 S. DIXIE HWY |
| | CONT: CHINCHOR ELECTRIC INC. |
| | TEL: (386)774-1020 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4-8-09 |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NO RESPONSE NOT ADDRESSED: SHEET S-1 SHOWS TWO |
| | DIFFERENT TYPES OF BEAMS. DETAIL #1 SHOW A "BOND |
| | BEAM"WITH 2 #5 REINFORCING BARS AND THE TYPICAL MASONRY |
| | WALL CONSTRUCTION DETAIL SHOW A CAST IN PLACE |
| | REINFORCED CONCRETE TIE BEAM WITH NO DIMENSIONS. |
| | CLEARLY STATE WHICH BEAM DETAIL WILL BE USED? THE |
| | FOUNDATION PLAN DETAIL FAIL TO SHOW THE LOCATION OF THE |
| | VERTICAL REINFORCING BARS AS STATED IN THE NOTE BELOW. |
| | ON SHEET S-1, PLEASE INDICATE THE TYPE AND SIZE OF THE |
| | MATERIALS FOR EACH DETAIL. SHOW THE BRACING DETAIL FOR |
| | THE MASONRY CONSTRUCTION PER FBC 2104.1.9 |
| | |
| | 3) NO RESPONSE NOT ADDRESSED: SHEET E-3 SHOWS |
| | ADDITIONAL STRUCTURAL INFORMATION THAT IS NOT SHOWN ON |
| | THE SHEET (S-1), EXAMPLE THE DOORS AND BOLLARDS WITH |
| | THE DOT GUARDRAIL. THE NEW MASONRY WALL NEEDS TO SHOW A |
| | HEADER DETAIL FOR THE TWO DOORS. WILL THE DOOR HEADER |
| | BE CONSTRUCTED WITH A REINFORCED CONCRETE OR WILL A |
| | LINTEL BE USED? IF THE LINTEL WILL BE USED, PROVIDE THE |
| | PRODUCT APPROVAL INDICATING THE SIZE OF THE LENTIL. |
| | PROVIDE PRODUCT APPROVAL FOR THE TWO DOORS AND INDICATE |
| | OR HI-LIGHT ALL INFORMATION PERTAINING TO THE |
| | INSTALLATION OF THE DOORS FROM THE INSTALLATION |
| | INSTRUCTIONS ON EACH PAGE OF THE PRODUCT APPROVAL. |
| | |
| | 4) NO RESPONSE NOT ADDRESSED: SHEET E-3 AND S-1 HAVE |
| | DIFFERENT ENGINEERS, THEREFORE THE WIND DESIGN |
| | INFORMATION SHALL BE SHOWN BY EACH ENGINEER IN |
| | ACCORDANCE WITH 1603.1.4 AND 1609.1.3. IS THE GUARDRAIL |
| | ATTACHED TO THE BOLLARDS? IF SO, PROVIDE A DETAIL FOR |
| | THE ATTACHMENT. THERE IS A NOTE AT THE TOP LEFT SECTION |
| | OF SHEET E-3 STATING "8" HIGH BLOCK WALL PAINT TO |
| | MATCH", ISN'T THIS A 14' HIGH WALL? CLARIFY. |
| | |
| | 5) OK |
| | |
| | 6) SUBMIT THE SOIL REPORT PER FBC 1802.6 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561)805-6726 |
| | FAX (561) 805-6676 |
| | [email protected] |
| | |