 APPLICATION #09010116 ELECTRICAL PLAN REVIEW
 7915 S. DIXIE HIGHWAY 1/28/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE EMERGENCY GENERATOR AS IT CURRENTLY EXISTS IS IN
 VIOLATION OF THE FOLLOWING CODES:
  
 A) 700.12(B)(3) DUAL SUPPLIES- PRIME MOVERS SHALL NOT
 BE SOLELY DEPENDENT ON A PUBLIC UTILITY GAS SYSTEM FOR
 THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY FOR THEIR
 COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR
 AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO
 ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED.
 B) NFPA-110 7.2 LOCATION. 7.2.1.1 THE ROOM SHALL HAVE A
 MINIMUM 2-HOUR FIRE RATING OR BE LOCATED IN AN ADEQUATE
 ENCLOSURE LOCATED OUTSIDE THE BUILDING CAPABLE OF
 RESISTING THE ENTRANCE OF SNOW OR RAIN AT A MAXIMUM
 WIND VELOCITY REQUIRED BY LOCAL BUILDING CODES.
 C) 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 D) 7.2.2 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE
 SAME ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT
 IS INSTALLED.
  
 NOTE: IF THERE ARE NO LEGALLY REQUIRED SYSTEMS IN THE
 BUILDING BEING FED FROM THE EXISTING GENERATOR THEN IT
 ALSO BECOMES AN "OPTIONAL STANDBY SYSTEM" AND NONE OF
 THE ABOVE COMMENTS APPLY. AS I DISCUSSED WITH MR.
 VARGAS WHEN I REVIEWED THE PLANS PREVIOUSLY, IF THE
 REQUIRED EMERGENCY LIGHTING WHERE BATTERY BACK UP ALL
 ISSUES ARE SOLVED.
  
 2} THE "EXISTING SINGLE LINE DIAGRAM" ON SHEET E-1 DOES
 NOT CORRELATE WITH THE ELECTRICAL
 RISER DIAGRAM SUBMITTED FOR PERMIT NUMBER 08040571,
 WHICH SHOWS PANEL "CP" FED FROM THE "EM" PANEL.
  
 3} IT IS NOT CLEAR IN THE SPECIFICATIONS IF THE ATS IS
 CAPABLE OF DISCONNECTING UTILITY POWER AND GENERATOR
 POWER. THAT APPEARS FUNCTION TO BE AN OPTION, PLEASE
 CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  