Plan Review Notes
Plan Review Notes For Permit 09010050
Permit Number 09010050
Review Stop M
Sequence Number 1
Notes
Date Text
2009-02-01 15:53:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE ADDITION OF A DUST COLLECTOR TO THIS PROPERTY
 WOULD CONSTITUTE A CHANGE OF OCCUPANCY. DECLARE THE
 PREVIOUS AND NEW OCCUPANCY CLASSIFICATIONS BASED ON
 FBCB CHAPTER 3 ON PLANS. DEMONSTRATE COMPLIANCE WITH
 FBC, EXISTING BUILDING CHAPTER 8 FOR CHANGE OF
 OCCUPANCY. INDICATE CHANGE OF OCCUPANCY ON PERMIT
 APPLICATION AT THE DESCRIPTION OF WORK SECTION.
  
 2. DEMONSTRATE COMPLIANCE WITH NFPA 664-02 FOR
 WOODWORKING FACILITIES. DUST COLLECTORS SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 8.2.2.5.
 DEMONSTRATE COMPLIANCE WITH THESE AND OTHER RELATED
 REQUIREMENTS ON PLANS.
  
 3. DETAIL IS PROVIDED REGARDING WIND RESISTANCE FOR THE
 DUCT COLLECTOR STAND. PLEASE PROVIDE SUPPORTING
 DOCUMENTATION SHOWING THE DUST COLLECTOR EQUIPMENT
 ITSELF AND RELATED DUCTWORK ARE DESIGNED AND INSTALLED
 FOR WIND RESISTANCE IN ACCORDANCE WITH FBCM 301.13.
  
 MUCH INFORMATION IS MISSING FORM PLANS. ADDITIONAL
 COMMENTS ARE LIKELY IN SUBSEQUENT REVIEW.
  