Plan Review Notes
Plan Review Notes For Permit 09010050
Permit Number 09010050
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-01-22 11:05:42***DENIED***
  
 1) PLEASE PROVIDE ADDITIONAL INFORMATION ILLUSTRATING
 THE EQUIPMENT LOCATION AS IT RELATES TO REQUIRED MEANS
 OF EGRESS.
  
 2) WORK SHALL COMPLY WITH APPLICABLE BUILDING CODES AND
 FLORIDA FIRE PREVENTION CODE, 2007 EDITION.
  
 3) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING ANY
 EXISTING BUILDING FIRE PROTECTION SYSTEMS IF
 APPLICABLE. FIRE SPRINKLER, FIRE ALARM ETC)
  
 4) WORK TO COMPLY WITH NFPA 664, STANDARD FOR THE
 PREVENTION OF FIRE AND EXPLOSIONS IN WOOD PROCESSING
 FACILITIES, 2007 EDITION.
  
 5) PLEASE MAKE NOTE OF OTHER REVIEW COMMENTS REGARDING
 FAC REQUIREMENTS FOR TITLE BLOCK.
  
 6) PLEASE PROVIDE INFORMATION DESCRIBING DAILY
 MAINTENANCE /HOUSEKEEPING IMPLEMENTATION TO LIMIT DUST
 BUILD-UP AND REDUCE THE HIGH COMBUSTIBILITY HAZARD.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756