Plan Review Notes
Plan Review Notes For Permit 09010050
Permit Number 09010050
Review Stop E
Sequence Number 1
Notes
Date Text
2009-01-13 11:36:00 
  
 APPLICATION #09010050 ELECTRICAL PLAN REVIEW
 435 SOUTHERN BLVD.
 WEST PALM BEACH, FL. 1/13/09
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE 40 HP 3 PHASE, 208 VOLT MOTOR SHOWN ON SHEET M-1
 IS LISTED AS 104 AMPS. PER TABLE 430.250 THE CORRECT
 AMPERAGE WOULD BE 114 AMPS.
  
 2} THE #1 THHN CONDUCTORS FEEDING THE DISCONNECT ?A?,
 AND THE 40 HP MOTOR, ARE NONCOMPLIANT WITH 430.250,
 430.22(E), 310.16.
  
 3} SHEET 4/4 OF THE ENGINEERED PLANS LIST THE MATERIAL
 HANDLING FAN AS 20 HP. CORRELATE WITH M-1, PROVIDE
 MANUFACTURERS SPECIFICATIONS FOR THE MOTOR STARTER AND
 THE EXHAUST/MATERIAL HANDLING FAN.
  
 4} THE AIR LOCK FAN ON SHEET M-1 IS LISTED AS 1 HP
 THREE PHASE 208 VOLTS @201 AMPS.PER 430.250 THE
 AMPERAGE SHOULD BE 4.6. SEE 430.22(E)
  
 5} SAME COMMENT FOR THE REGENERATION FAN LISTED AT 6.3
 AMPS, 7.5 AMPS PER 430.250.
  
 6} ALL ENGINEERED SHEETS REFERENCE THE 2006
 SUPPLEMENTS, SHOULD REFERENCE 2007
  
 7} THE DUST COLLECTOR EXHAUST FAN IS LISTED AT 230
 VOLTS. THE SERVICE IS 208 VOLTS. 408.4 NEC.
  
 8} INICATE WHAT THE COLLECTOR IS BEING USED FOR.
 DECLARE LOCATION PER ARTICLE 500, SHOW COMPLIANCE WITH
 THE WIRING METHODS DECLARED.
  
 9} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
  