Plan Review Notes
Plan Review Notes For Permit 09010050
Permit Number 09010050
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-15 12:07:32 
 BUILDING PLAN REVIEW
 PERMIT: 09010050
 ADD: 435 SOUTHERN BLVD
 CONT: ALTMAN BROTHERS, LLC
 TEL: (561)694-1651
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-15-09
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 106.1.2 ADDITIONAL INFORMATION IS REQUIRED TO DO AN
 ADEQUATE REVIEW. THE PLANS NEED TO STATE A) THE TYPE OF
 CONSTRUCTION AS DEFINED IN CHAPTER 6 /TABLE 601 AND
 TABLE 503.
 B) THE USE AND OCCUPANCY IN ACCORDANCE WITH CHAPTER 3
 C) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED,
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 5) OUR SYSTEM SHOWS THE TYPE OF LICENSE FOR THIS
 ADDRESS IS FOR THE ?SALE OF CABINETRY? NOT
 MANUFACTURING. IF ANY MANUFACTURING IS CARRIED OUT AT
 THIS LOCATION, THE APPROPRIATE LICENSE WILL BE REQUIRED
 AND CAN BE OBTAIN FROM THIS OFFICE.
  
 NOTE: THIS REVIEW WILL BE COMPLETED WITH THE FOLLOWING
 ASSUMPTION, THE WOOD WORKING SHOP WILL BE CONSIDERED
 FACTORY-INDUSTRIAL F1 SINCE SECTION 306 OF THE BUILDING
 CODE DOES LIST MILLWORK (SASH & DOOR) AS A F1
 OCCUPANCY.
  
 THE NEXT ISSUE WILL BE HOW TO CLASSIFY THE SAWDUST THAT
 IS CREATED WHEN WORK IS BEING COMPLETED. THE WOOD
 BEFORE IT IS CUT IS A MINOR HAZARD BUT WHEN SAWDUST IS
 CREATED, THE SAWDUST IS VERY COMBUSTIBLE AND CREATES A
 HIGH HAZARD OR H-2 OCCUPANCY. TABLE 307.7(1) IS FOR THE
 MAXIMUM ALLOWABLE QUANTITIES OF MATERIAL ALLOWED PER
 CONTROL AREA THAT POSES A PHYSICAL HAZARD. WHEN YOU
 SCAN THE TABLE THERE IS NO CATEGORY FOR COMBUSTIBLE
 DUST, THERE IS FOR COMBUSTIBLE DUST INTO AN H-2
 CATEGORY. SEE 415.7 GROUP H-2.
  
 415.7.1 COMBUSTIBLE DUSTS, GRAIN PROCESSING AND
 STORAGE.
 THE PROVISIONS OF SECTIONS 415.7.1.1 THROUGH 415.7.1.5
 SHALL APPLY TO BUILDINGS IN WHICH MATERIALS THAT
 PRODUCE COMBUSTIBLE DUSTS ARE STORED OR HANDLED.
 BUILDINGS THAT STORE OR HANDLE COMBUSTIBLE DUSTS SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF NFPA 61, NFPA
 120, NFPA 651, NFPA 654, NFPA 655, NFPA 664 AND NFPA
 85, AND THE FLORIDA FIRE PREVENTION CODE.
  
 NFPA 664 IS THE STANDARD FOR THE PREVENTION OF FIRE AND
 EXPLOSIONS IN WOOD PROCESSING FACILITIES 2007 EDITION.
 THE DUST COLLECTION SYSTEM SHALL BE DESIGN AND
 CONSTRUCTED IN ACCORDANCE WITH NFPA 664. THE DESIGNER
 AND INSTALLER QUALIFICATIONS SHALL BE IN ACCORDANCE
 WITH SECTION 4.4.
  
 PLEASE PROVIDE INFORMATION ON THE BULK STORAGE TANK
 SIZE IN WIDTH DEPTH AND HEIGHT AS WELL AS CUBIC FEET.
 PROVIDE DOCUMENTATION ON THE HOUSE KEEPING AND
 INSPECTION PROGRAMS AND MAINTENANCE OF THE UNIT. 11.1
 GENERAL REQUIREMENTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (805) 805-6676
 [email protected]
  