| 2009-05-07 12:56:50 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} SHEET E-1 INCORRECTLY REFERENCES THE 2008 NEC IN THE |
| | ELECTRICAL NOTES |
| | |
| | 2} R313.1 SMOKE ALARMS. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS.***ONE DETECTOR NEEDS TO BE |
| | ADDED OUTSIDE THE BACK BEDROOMS TO SATISFY THIS |
| | REQUIREMENT. SEE 210.12 FOR AFCI CIRCUITING. |
| | |
| | 2} SEE 210.12 FOR AFCI CIRCUITING.THERE IS NO NOTES |
| | INDICATING THIS REQUIREMENT FOR THE BEDROOM OUTLETS. |
| | |
| | 3} THE RISER DIAGRAM ON SHEET E-2 LISTS 4/0 COPPER |
| | CONDUCTORS IN THE 2 1/2" RISER CONDUIT. THE #4 |
| | GROUNDING ELECTRODE CONDUCTOR IS NOT LARGE ENOUGH FOR |
| | THOSE CONDUCTORS, SEE 250.66. THERE ALSO A NOTE |
| | MENTIONING ALUMINUM CONDUCTORS PANEL FEEDERS, CORRELATE |
| | ALL THE FEEDERS AND REMOVE THE NOTES THAT AREN'T |
| | RELEVANT TO SHOW THE INTENT OF THE DESIGNER. |
| | |
| | 4} FROM THE METER THERE ARE 1/0 CONDUCTORS RUNNING TO |
| | THE 225 AMP DISCONNECTING VIOLATION OF 310.15(B)(6) |
| | |
| | 5} THE RECEPTACLES ON CIRCUIT A-23 IN THE GREAT AND |
| | MASTER BEDROOMS ARE LABELED WATER PROOF EXTERIOR |
| | RECEPTACLES ON THE PANEL SCHEDULE. 408.4 NEC. |
| | |
| | 6} THE DINING ROOM RECEPTACLES ARE REQUIRED TO BE ON A |
| | SMALL APPLIANCE CIRCUIT PER 210.52 (B) (1) RECEPTACLE |
| | OUTLETS SERVED IN THE KITCHEN, PANTRY, BREAKFAST ROOM, |
| | DINING ROOM, OR SIMILAR AREA OF A DWELLING UNIT, THE |
| | TWO OR MORE 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS |
| | REQUIRED BY 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR |
| | RECEPTACLE OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP |
| | OUTLETS COVERED BY 210.52(C), AND RECEPTACLE OUTLETS |
| | FOR REFRIGERATION EQUIPMENT. |
| | |
| | 7} PER 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT EACH WALL COUNTER SPACE |
| | THAT IS 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS |
| | SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| | IS MORE THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM |
| | A RECEPTACLE OUTLET IN THAT SPACE***THE COUNTERTOP |
| | RECEPTACLES ON THE REFRIGERATOR SIDE OF THE KITCHEN DO |
| | NOT COMPLY WITH THAT ARTICLE AS NO RECEPTACLES ARE |
| | SHOWN. |
| | |
| | 8} THE RECEPTACLE SPACING IN THE SUN ROOM MUST COMPLY |
| | WITH 210.52(A)(1) & (2). |
| | |
| | 9} A RECEPTACLE MUST BE ADDED OUTSIDE AT THE FRONT OF |
| | THE HOUSE PER 210.52(E). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |
| | |
| | 8} RECEPTACLES IN THE SUN ROOM MUST COMPLY WITH. |
| | |
| | |