Plan Review Notes
Plan Review Notes For Permit 09010047
Permit Number 09010047
Review Stop E
Sequence Number 2
Notes
Date Text
2009-05-07 12:56:50 
  
 THIS REVIEW WAS DONE UNDER THESE CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-1 INCORRECTLY REFERENCES THE 2008 NEC IN THE
 ELECTRICAL NOTES
  
 2} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.***ONE DETECTOR NEEDS TO BE
 ADDED OUTSIDE THE BACK BEDROOMS TO SATISFY THIS
 REQUIREMENT. SEE 210.12 FOR AFCI CIRCUITING.
  
 2} SEE 210.12 FOR AFCI CIRCUITING.THERE IS NO NOTES
 INDICATING THIS REQUIREMENT FOR THE BEDROOM OUTLETS.
  
 3} THE RISER DIAGRAM ON SHEET E-2 LISTS 4/0 COPPER
 CONDUCTORS IN THE 2 1/2" RISER CONDUIT. THE #4
 GROUNDING ELECTRODE CONDUCTOR IS NOT LARGE ENOUGH FOR
 THOSE CONDUCTORS, SEE 250.66. THERE ALSO A NOTE
 MENTIONING ALUMINUM CONDUCTORS PANEL FEEDERS, CORRELATE
 ALL THE FEEDERS AND REMOVE THE NOTES THAT AREN'T
 RELEVANT TO SHOW THE INTENT OF THE DESIGNER.
  
 4} FROM THE METER THERE ARE 1/0 CONDUCTORS RUNNING TO
 THE 225 AMP DISCONNECTING VIOLATION OF 310.15(B)(6)
  
 5} THE RECEPTACLES ON CIRCUIT A-23 IN THE GREAT AND
 MASTER BEDROOMS ARE LABELED WATER PROOF EXTERIOR
 RECEPTACLES ON THE PANEL SCHEDULE. 408.4 NEC.
  
 6} THE DINING ROOM RECEPTACLES ARE REQUIRED TO BE ON A
 SMALL APPLIANCE CIRCUIT PER 210.52 (B) (1) RECEPTACLE
 OUTLETS SERVED IN THE KITCHEN, PANTRY, BREAKFAST ROOM,
 DINING ROOM, OR SIMILAR AREA OF A DWELLING UNIT, THE
 TWO OR MORE 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS
 REQUIRED BY 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP
 OUTLETS COVERED BY 210.52(C), AND RECEPTACLE OUTLETS
 FOR REFRIGERATION EQUIPMENT.
  
 7} PER 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTER SPACE
 THAT IS 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM
 A RECEPTACLE OUTLET IN THAT SPACE***THE COUNTERTOP
 RECEPTACLES ON THE REFRIGERATOR SIDE OF THE KITCHEN DO
 NOT COMPLY WITH THAT ARTICLE AS NO RECEPTACLES ARE
 SHOWN.
  
 8} THE RECEPTACLE SPACING IN THE SUN ROOM MUST COMPLY
 WITH 210.52(A)(1) & (2).
  
 9} A RECEPTACLE MUST BE ADDED OUTSIDE AT THE FRONT OF
 THE HOUSE PER 210.52(E).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
 8} RECEPTACLES IN THE SUN ROOM MUST COMPLY WITH.
  
  