Date Text
2009-01-12 09:04:48 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} PROVIDE A PANEL SCHEDULE WITH OCP AND WIRE SIZES PER
 408.4, 310.16 NEC.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 4} THE KITCHEN LAYOUT IS INCOMPLETE AND THEREFORE
 COMPLIANCE WITH 210.52(B) FOR SPACING CANNOT BE
 PROPERLY REVIEWED
  
 5} PER 210.8(A)(6), KITCHEN COUNTERTOP RECEPTACLE MUST
 BE GFI PROTECTED.INDICATE SAME ON THE PLAN.
  
 6} PER 210.8(A)(1)ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN BATHROOMS SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL. NOT SHOWN ON THE PLAN.
  
 7} 210.52 (E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. THESE ARE REQUIRED TO BE GFI PROTECTED PER
 210.8(A)(3).
  
 8} PROVIDE A LEGEND FOR THE DEVICES AND FIXTURES ON THE
 PLAN.IT IS HARD TO DETERMINE LIGHTS , SPEAKERS AND
 PHONE SYMBOLS.106.1.3 FBC
  
 9} 106.1.3 RESERVED. QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.***THE SCALE
 GIVEN IS INCORRECT AS THE COPIED PLANS SEEM TO HAVE
 BEEN REDUCED.
  
 PER 713 FLORIDA STATUTES A NOTICE OF COMMENCEMENT MUST
 BE FILED PRIOR TO THE FIRST INSPECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  