| 2009-01-13 09:08:54 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 EXISTING BUILDING |
| | |
| | 1. SHT C1 PRESENT CODE CYCLE IS THE FBC-2004 WITH 2007 |
| | AMENDMENTS. SECTION 106.1.1. PLANS INDICATE 2006 |
| | AMENDMENTS. PLEASE UPDATE CODE CRITERIA. |
| | |
| | 2. INDICATE LEVEL OF ALTERATION PER CHAPTER 3 OF THE |
| | FBC-2004 EXISTING BUILDING CODE. |
| | |
| | 2. SHTS D2 & A3. MORE INFORMATION IS REQUIRED. SECTION |
| | 106.1.2. THE DEMO SHEET DOES NOT SHOW A KITCHEN SINK |
| | NOR DOES IT SHOW A WASHING MACHINE WHICH ARE BOTH |
| | INDICATED ON THE PROPOSED SHEET. ARE THESE FIXTURES |
| | EXISTING OR NEW? PLEASE CLARIFY. |
| | |
| | 3. WITH NEW INFORMATION, THERE MAY BE MORE COMMENTS. IF |
| | NEW FIXTURES, A SANITARY RISER DIAGRAM WILL BE REQUIRED |
| | FOR THE NEW FIXTURES SHOWING ALL PIPE SIZES, TRAPS, |
| | VENTS ETC. SECTION 106.3.5.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |