| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION |
| | ON THE APPLICATION, PROVIDE AN AIC RATING PER 110.9 & |
| | 10. |
| | |
| | 2} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE |
| | CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED |
| | LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS |
| | USED, THE CALCULATED LOAD AFTER APPLYING DEMAND |
| | FACTORS, ARTICLE 215.5 NEC 2005.*** FOR THE ENTIRE |
| | SERVICE. |
| | |
| | 3} THERE IS NO "GROUND" PROVIDED BY FPL (SEE RISER |
| | OVERHEAD) REMOVE THE #6. |
| | |
| | 4} 250.24(C) GROUNDED CONDUCTOR BROUGHT TO SERVICE |
| | EQUIPMENT WHERE AN AC SYSTEM OPERATING AT LESS THAN |
| | 1000 VOLTS IS GROUNDED AT ANY POINT, THE GROUNDED |
| | CONDUCTOR(S) SHALL BE RUN TO EACH SERVICE DISCONNECTING |
| | MEANS AND SHALL BE BONDED TO EACH DISCONNECTING MEANS |
| | ENCLOSURE. THE GROUNDED CONDUCTOR(S) SHALL BE INSTALLED |
| | IN ACCORDANCE WITH 250.24(C)(1) THROUGH (C)(3). |
| | EXCEPTION: WHERE MORE THAN ONE SERVICE DISCONNECTING |
| | MEANS ARE LOCATED IN AN ASSEMBLY LISTED FOR USE AS |
| | SERVICE EQUIPMENT, IT SHALL BE PERMITTED TO RUN THE |
| | GROUNDED CONDUCTOR(S) TO THE ASSEMBLY, AND THE |
| | CONDUCTOR(S) SHALL BE BONDED TO THE ASSEMBLY |
| | ENCLOSURE.*** THE RISER HAS MULTIPLE GROUND RODS. THE |
| | NEUTRAL SHOULD BE GROUNDED IN THE GUTTER, A MAIN |
| | BONDING JUMPER INSTALLED IN THE DISCONNECTS, AND |
| | ADDITIONAL ELECTRODES ONLY AT SEPARATE STRUCTURES PER |
| | 250.32 |
| | |
| | 5 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE |
| | FEEDERS TO THE CABANA PANELS ON THE RISER DIAGRAM.215.5 |
| | NEC. |
| | |
| | 6} INDICATE CONDUCTOR SIZES ON THE PANEL SCHEDULE SO |
| | THAT COMPLIANCE WITH 310.16 CAN BE REVIEWED. |
| | |
| | 7} 210.25 COMMON AREA BRANCH CIRCUITS |
| | BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY |
| | LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED |
| | ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED |
| | FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL, |
| | COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON |
| | AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT |
| | BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL |
| | DWELLING UNIT.THERE ARE TWO PANELS AND THREE UNITS. THE |
| | 2ND FLOOR UNIT APPEARS HAS NO ACCESS TO THE PANEL FOR |
| | THAT UNIT. PLEASE CLARIFY. |
| | |
| | 8} LABEL THE WATER HEATERS ON THE PLAN. 106.1 FBC |
| | |
| | 9} R313.1.1 RESIDENTIAL BUILDING CODE, SMOKE ALARMS |
| | SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN |
| | REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE |
| | ARTICLE FOR COMPLETE TEXT.***LOCATE THE ALARMS ON THE |
| | PLANS. |
| | |
| | FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE |
| | FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE |
| | THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED.(2005 NEC) ON THE ELECTRICAL OR COVER SHEET. |
| | ALSO NOTE THE 2007 REVISIONS TO THE 2004 FBC ARE IN |
| | EFFECT. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| | REVIEW COMMENTS IN WRITING. |
| | |