| 2009-02-18 16:54:26 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE WEST PALM BEACH |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS LS-1, LS-2 & LS-3. THE BUILDING CODE ANALYSIS |
| | SHALL INCLUDE THE 2007 AMENDMENTS. ALSO IF THE PERMIT |
| | IS NOT APPLIED FOR PRIOR TO MARCH 1, 2009 THE NEW |
| | FBC-2007 CODE WILL BE ADOPTED AND THE BUILDING PLANS |
| | SHALL BE DESIGNED TO THE FBC- 2007. SECTION 106.1.1. |
| | |
| | 2. SHT A-1.0 MEN'S AND WOMEN'S TOILET ROOM 116 & 116 |
| | AND DRINKING FOUNTAINS. SHOW COMPLIANCE WITH THE |
| | FOLLOWING SECTIONS: 11-4.15, 11-4.16, 11-4.17, 11-4.18, |
| | 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS & FIGURES. |
| | |
| | 3. SHT A-1.0 MEZZENINE PLAN MEN'S & WOMEN'S LOCKERS. |
| | SHOW COMPLIANCE WITH THE FOLLOWING SECTIONS: 11-4.16, |
| | 11-4.19, 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS AS WELL |
| | AS SECTION 11-4.24 WITH ALL SUBSECTIONS FOR THE BREAK |
| | SINK. |
| | |
| | 4. SHT A-2.0 SUBMIT CALCULATIONS FOR ALL ROOF/DECK |
| | DRAINS ON THE EAST & WEST SIDES OF THE BUILDING. SHOW |
| | THE SQUARE FOOTAGE AREA FOR EACH DRAIN & 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH |
| | AREA. SHOW THE LOCATION OF THE REQUIRED SECONDARY |
| | DRAINAGE SHOWING THE SIZE OF THE DRAINS PER SECTIONS |
| | 1106 & 1107 WITH ALL SUBSECTIONS & TABLES. |
| | |
| | 5. SHT A-2.0 TOILET ROOM H.C. (202) SHOW COMPLIANCE |
| | WITH THE FOLLOWING: SECTIONS 11-4.16, 11-4.19 & 11-4.22 |
| | WITH ALL SUBSECTIONS. |
| | |
| | 6. SHTS A-2.0, A-3.0, A-4.0, A-5.0, A-6.0, A-7.0 A-8.0, |
| | A-9.0 & A-10.0. PLEASE SHOW COMPLIANCE WITH SECTIONS |
| | 11-9.1.2, 11-9.1.3, 11-9.1.4 & 11-9.2.3. INDICATE THE |
| | NUMBER OF GUEST ROOMS AVAILABLE. INDICATE THE LOCATION |
| | OF SLEEPING ACCOMODATIONS FOR PERSONS WITH HEARING |
| | IMPAIRMENTS, INDICATE ALL AVAILABLE CLASSES OF SLEEPING |
| | ACCOMMODATIONS & SHOW HOW THEY ARE DISPERSED AMONG |
| | VARIOUS CLASSES. INDICATE GUESTROOMS THAT COMPLY WITH |
| | SPECIAL ACCESSIBILITY FEATURES. SECTION 106.1.2. |
| | |
| | 7. SHT A-3.0 INDICATE HOW THE ROOF TERRACES WILL DRAIN |
| | THE STORM WATER. SECTIONS 106.1.2, 1106 & 1107. |
| | |
| | 8. SHT A-11.0 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. INDICATE THE AREA OF EACH DRAIN |
| | AND SHOW 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS ADDED TO EACH DRAIN. SECTIONS 1106 & 1107 WITH |
| | ALL SUBSECTIONS & TABLES. SHOW HOW THE UPPER ROOFS WILL |
| | BE DRAINED. (SEE MACHINE ROOM, STAIRWAY, ELECTRICAL |
| | ROOM, TOILET ROOMS, STORAGE ROOM ETC.). SHOW PRIMARY |
| | AND SECONDARY LOCATIONS. |
| | |
| | 9. SHT A-11.1 3RD LEVEL ROOF PLAN. INDICATE HOW THE |
| | AREAS BETWEEN COL. G & COL. H DRAIN. SECTIONS 106.1.1, |
| | 1106 & 1107. |
| | |
| | 10. SHTS A-12.0 & A-13.0 SHOW THE SIZE OF THE GUTTERS |
| | AND DOWNSPOUTS & INDICATE THE TOTAL SQUARE FOOTAGE |
| | DRAINING INTO THE GUTTERS & DOWNSPOUTS. TABLES 1106.3 & |
| | 1106.6. |
| | |
| | 11. SHT A-21.1 DETAIL 3 SHOWS A SECOND W/C & LAV NOT |
| | SHOWN ON SHT A-2.0 ROOM 205. PLEASE CORRELATE. SECTIONS |
| | 106.1.1, 601.1 & 701.1. |
| | |
| | 12. SHT A-21.1 DETAILS 1 & 3 REFERENCE |
| | ELEVATIONS/DETAILS 9 THRU 17 ON SHT A-21.1. THESE |
| | DETAILS WERE NOT SUBMITTED. ALSO DOTTED LINE |
| | PARTITIONS, DOORS ETC. SHOWN ON THE FLOOR PLAN. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 13. SHT A-21.2 DETAILS 1 & 3. PLEASE SHOW COMPLIANCE |
| | WITH THE FOLLOWING: SECTIONS 11-4.16, 11-4.19 & 11-4.23 |
| | WITH ALL SUBSECTIONS. |
| | |
| | 14. SHT A-21.2 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 15. SHT A-21.3 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 3 THRU 10 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 16. SHT A-21.4 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 17. SHT A-21.5 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 18. SHT A-21.6 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 19. SHT A-22.1 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 3 THRU 18 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 20. SHT A-22.2 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 3 THRU 26 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 21. SHTS A-22.4, A-22.5, A-22.6, A-22.7, A-22.8, |
| | A-22.9, A-22.10, A-22.11, A-22.12, A-22.13, A-22.14, |
| | A-22.15 & A-23.1 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 22. SHT A-23.2 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 5 THRU 16 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 23. SHT A-24.1 DETAILS 1 & 3 REFERENCES |
| | DETAILS/ELEVATIONS 3 THRU 18 ON THE FLOOR PLAN, BUT THE |
| | DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT |
| | REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 24. SHT P-0.0 RISERS S/6-0, 5/8-0, S/9-0, S/14-0, |
| | S/15-0, S/20.0 & S/21-0 ARE NOT INDICATED ON THE FLOOR |
| | PLAN. PLEASE INDICATE WHERE EACH RISER STARTS FROM THE |
| | BUILDING THRU TO THE VENT THRU ROOF. SECTIONS 106.1.1, |
| | 106.1.2 & 701.1 AS WELL AS TABLES 710.1(1) & 710.1(2). |
| | |
| | 25. SHT P-0.0 RISERS S/6-2 & S/24-0 SHOW NO PIPING FROM |
| | THE BUILDING DRAIN. PLEASE SHOW ALL PIPING THAT |
| | REFLECTS THE RISER DIAGRAMS. SECTIONS 106.1.1 & 701.1 |
| | AS WELL AS TABLES 710.1(1) & 710.0(2). -- ALSO THERE |
| | ARE TWO S/24 RISERS AND ONE S/24-1 RISER. PLEASE |
| | CLARIFY. SECTIONS 106.1.1 & 701.1. |
| | |
| | 26. SHT P-0.0 NO RISER DESIGNATION NUMBER FOR THE RISER |
| | BY COL. AT COL. LINE C/2 NOR ON THE RISER NEXT TO |
| | S/23-0. PLEASE INDICATE RISER NUMBER. SECTION 106.1.1 & |
| | TABLES 710.1(1) & 710.0(2). |
| | |
| | 27. SHT P-0.0 HAS NOTES "SEE LEVEL 1 FOR CONTINUATION" |
| | & "BOILER ROOM SEE LEVEL 1 DRAWING". PLEASE CLARIFY. |
| | WHAT SHEET IS LEVEL 1 ON? SECTIONS 106.1.1 & 701.1. |
| | |
| | 28. SHT P-0.0 WHERE DO CONDENSATE RISERS CONNECT TO THE |
| | BUILDING CONDENSATE DRAIN? INDICATE THE TERMINATION |
| | POINT FOR THE CONDENSATE. INDICATE THE MATERIAL , PIPE |
| | SIZES ETC. SECTIONS 314.2 & 314.2.2. |
| | |
| | 29. SHT P-1.0 IDENTIFY WHAT WILL DRAIN INTO THE TRENCH |
| | DRAIN BY THE SERVICE DUMPSTER (108). STORM WATER SHALL |
| | NOT DRAIN INTO THE SANITARY PER ARTICLE III SECTION |
| | 90-125(5). DEPENDING ON THE COMMENT RESPONSE, A |
| | OIL/SAND INTERCEPTOR OR GREASE INTERCEPTOR MAY BE |
| | REQUIRED. SECTION 90-124(7). |
| | |
| | 30. SHT P1.0 A GREASE INTERCEPTOR MAY BE REQUIRED, OR |
| | IF THERE IS A GREASE INTERCEPTOR IT SHALL BE CHECKED |
| | FOR SIZE AND/OR TO SEE IF THE INTERCEPTOR IS WORKING |
| | PROPERLY. PLEASE CONTACT THE UTILITY DEPT. INDUSTRIAL |
| | PRETREATMENT, ENVIRONMENTAL COMPLIANCE. CONTACT HOLLY |
| | MCGRATH LABORATORY SUPERVISOR BY PHONE (561) 822-2271, |
| | OR BY FAX (561) 822-2279 OR BY E-MAIL [email protected]. |
| | A WRITTEN DETERMINATION SHALL BE SUBMITTED WITH PLANS |
| | INDICATING INTERCEPTOR SIZE ECT. ARTICLE III SECTION |
| | 90-124(7). |
| | |
| | 31. SHT P-1.0 RISERS S/6-1 & S/20-1 ARE NOT SHOWN ON |
| | THE FLOOR PLAN. ALSO SHOW THE VENTS FOR THE FUTURE |
| | RESTAURANT & RETAIL SPACES. SECTIONS 106.1.1 & 901.2. |
| | |
| | 32. SHT P-1.0 RISERS DESIGNATED AS S/10-2, S/11-2, |
| | S/12-2 & S/14-2. ALL OTHER RISERS ON THIS SHEET HAVE A |
| | -1 DESIGNATION. PLEASE CORRELATE. SECTION 106.1.1 AND |
| | TABLE 710.1(1). |
| | |
| | 33. SHT P-1.0 INDICATE THE SHEET NUMBER FOR THE |
| | CONTINUATION OF S/24-1, (SHOWN AS 2/24 ON SHT P-0.0 BUT |
| | AS S/24-1 ON SHTS P-1.0 & P-1.1). TABLE 710.0(1). |
| | |
| | 34. SHT P-2.0 OFFSETS & PIPING FOR JANITOR MOP SINK |
| | ROOM 201, VENDING ROOM 206 & TOILET ROOM CONNECTING TO |
| | RISER S/1-2 ARE NOT INDICATED ON THE RISER DIAGRAM. |
| | PLEASE CORRELATE. SECTION 106.1.1 & TABLES 710.1(1) & |
| | 710.1(2). |
| | |
| | 35. SHT P-2.0 OFFSETS SHOWN ON THE FLOOR PLAN FOR |
| | RISERS S/4-2, S/5-2, S/10-2, S/11-2 & S/12-2 ARE NOT |
| | SHOWN ON THE RISERS. PLEASE CORRELATE. SECTIONS 106.1.1 |
| | & 701.1. |
| | |
| | 36. SHT P-2.0 THE PIPING FOR KING ADA (219) & KING |
| | (217) ARE NOT SHOWN ON THE RISER DIAGRAM S/13-2. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 37. SHT P-2.0 RISER 2/20-2 IS NOT SHOWN ON THE FLOOR |
| | PLAN. PLEASE CLARIFY. SECTIONS 106.1.1 & 701.1. |
| | |
| | 38. SHT P-3.0 INDICATE THE RISER NUMBERS WHERE RISERS |
| | OFFSET DOWN. SEE RISERS S/1-3, S/3-3 & S/10-3. SECTIONS |
| | 106.1.1 & 701.1. |
| | |
| | 39. SHT P-3.0 THE OFFSET FOR RISER S/13-3 SHOWN ON THE |
| | FLOOR PLAN IS NOT SHOWN ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 40. SHT P-8.0 RISER S/9.8 IS INDICATED AS S/9-10. |
| | PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 41. SHT P-9.0 THE PIPING TO KING (B16)(921) IS NOT |
| | SHOWN ON RISER S/13-9. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 701.1. |
| | |
| | 42. SHT P-10.0 THE PIPING TO THE BATHROOM BY COL. LINE |
| | 4/F-G IS NOT SHOWN ON RISER DIAGRAM S/13-10. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 43. SUBMIT AN EXISTING ROOF PLAN SHOWING ALL EXISTING |
| | ROOF DRAINS, PRIMARY AND SECONDARY, WITH THE DRAIN |
| | SIZES. TABLES 1106.3 & 1106.7. |
| | |
| | 44. SHT P-11.0 RISER S/20-11 SHOWS NO SANITARY |
| | CONNECTION TO RISER. PLEASE CLARIFY. SECTIONS 106.1.1 & |
| | 701.1. |
| | |
| | 45. SHT P-11.0 IT APPEARS THAT THE SQUARE FOOTAGE |
| | INDICATED FOR SOME ROOF AREAS ALONG WITH THE VERTICAL |
| | CONTRIBUTION ARE INCORRECT. (EXAMPLES: THE N.E. CORNER |
| | AREA BETWEEN COL. LINES A & B BY COL. LINE 3, (24' X |
| | 16.5' = 396 SF BUT 317 SF IS INDICATED WITH 66 SF OF |
| | VERTICAL CONTRIBUTION) TOTAL EQUALS 462 SF. THE SAME |
| | SQUARE FOOT AREA FOR COL. LINES A & B BY COL. LINE 4 ON |
| | THE N.W. CORNER IS INDICATED AS 195 SF WITH 106 SF OF |
| | VERTICAL CONTRIBUTION.). PLEASE RECHECK AS SQUARE |
| | FOOTAGE AREA FOR ROOFS THAT DRAIN ONTO THE ROOF FROM |
| | ABOVE SHALL ALSO BE ADDED TO THE SQUARE FOOT AREA OF |
| | EACH DRAIN. SECTIONS 1106.2 & 1106.3. |
| | |
| | 46. SHT P-12.0 DOMESTIC RISERS SHOW 3" RPZV BACKFLOWS. |
| | PER TABLE 603.1 WATER SERVICE SIZE, FOOTNOTE D, ALL |
| | BACKFLOW ASSEMBLIES SHALL BE AT LEAST THE SAME SIZE AS |
| | THE LINE IN WHICH THEY ARE INSTALLED. SINCE THE WATER |
| | SERVICE LINE IS 4" THEN THE BACKFLOWS SHALL BE 4". |
| | |
| | 47. SHT P-12.0 ALL WATER RISER DIAGRAMS SHALL BE |
| | SUBMITTED IN ISOMETRIC FORM SHOWING ALL PIPE SIZES. |
| | SECTION 106.1.3. THE RISERS SHALL REFLECT THE PIPING |
| | SHOWN ON THE FLOOR PLAN. PIPING INDICATED ON THE 9TH & |
| | 10TH FLOORS DO NOT REFLECT THE FLOOR PLANS AND THE |
| | RISERS NO NOT REFLECT THE FLOOR PLANS. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 601.1. |
| | |
| | 48. SHT P-12.1 THE DOMESTIC RISER W/2 AT THE 9TH FLOOR |
| | DOES NOT REFLECT TWR-1. RISERS W/2 THRU W/6 DO NOT |
| | REFLECT THE FLOOR PLANS AT THE LAVS. FLOOR PLAN SHOWS |
| | THE WATER TO THE LEFT SIDE OF THE RISERS WHERE AS THE |
| | RISERS SHOW THE LAVS TO THE RIGHT SIDE OF THE RISERS. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1. |
| | |
| | 49. RISER W/7 HAS NOT BEEN SUBMITTED. SECTIONS |
| | 106.3.5.1.3 & 601.1. |
| | |
| | 50. SHT P-12.3 RISER W/15 DOES NOT REFLECT THE FLOOR |
| | PLAN, NOR DOES IT REFLECT TWR/15 AT THE BASE OF THE |
| | RISER, AT THE OFFSET ON THE 9TH FLOOR, NOR AT THE TOP |
| | OF THE RISER. PLEASE CORRELATE. SECTIONS 106.1.1 & |
| | 601.1. |
| | |
| | 51. SHT P-12.3 RISER W/9. WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT EACH ICE MAKER. SECTION 604.9. |
| | |
| | 52. SHT P-12.3 RISER W/18. SHOW THE PIPING AND VALVES |
| | TO REFLECT THE 11TH FLOOR. SECTIONS 106.1.2 & 601.1. |
| | |
| | 53. SHT P-12.3 THE RISER TO THE LEFT OF THE GANG BATHS |
| | HAS NO DESIGNATION NUMBER. PLEASE INDICATE NUMBER FOR |
| | RISER. SECTIONS 106.1.2 & 601.1. |
| | |
| | 54. SHT P-12.4 RISER W/7 DOES NOT REFLECT THE FLOOR |
| | PLAN OR RISER TWR/11 AT THE LAVS. ALSO NO TWR NUMBER IS |
| | INDICATED FOR THE 7TH & 9TH FLOORS, NO TWR NUMBER OR |
| | PIPING TO THE LAV AT THE 10TH FLOOR AND NO FLOOR |
| | DESIGNATIONS FOR THE 9TH & 10TH FLOORS. PLEASE CLARIFY. |
| | SECTIONS 106.1.1 & 601.1. |
| | |
| | 55. SHT P-12.4 RISER W/14 DOES NOT REFLECT TWR/13 AT |
| | THE HOT RETURN FOR THE LAVS, NOR FOR THE COLD WATER TO |
| | THE W/C'S & LAVS, THE OFFSETS AT THE 9TH FLOOR DO NOT |
| | REFLECT THE FLOOR PLAN FOR THE HOT RETURN AS WELL AS |
| | THE RISER SHOWS FIXTURES ON THE 9TH & 10TH FLOORS NOT |
| | SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 601.1. |
| | |
| | 56. SHT P-12.4 RISER W/14 DOES NOT REFLECT THE FLOOR |
| | PLAN AS THE LAVS & W/C'S ARE ON THE OPPOSITE SIDE OF |
| | THE SHOWER ON THE FLOOR PLAN ON THE 3RD THRU 8TH |
| | FLOORS, NOR DO THE OFFSETS REFLECT THE FLOOR PLAN AT |
| | THE TOP OF THE RISER. SECTIONS 106.1.1 & 601.1. |
| | |
| | 57. SHTS P-12.1 THRU P-12.4 ALL RISERS HAVE A NOTE THAT |
| | STATES "SEE DETAIL" AT THE TOP OF THE RISERS. PLEASE |
| | INDICATE WHICH DETAIL, AND ALSO INDICATE WHERE THE |
| | DETAIL CAN BE LOCATED. SECTIONS 106.1.2 & 601.1. |
| | |
| | 58. SHT P-12.5 ALL TYPICAL RISERS HAVE A NOTE THAT |
| | STATES "SEE BACK TO BACK DETAIL". PLEASE INDICATE WHERE |
| | THE DETAIL CAN BE LOCATED. SECTIONS 106.1.2 & 601.1. |
| | |
| | 59. SHT P-12.5 TWR/8 SHOWS NO HOT WATER TO THE LAV, & |
| | THE FLOOR PLAN SHOWS AN OFFSET TO THE W/C FOR ALL |
| | FLOORS EXCEPT THE 9TH FLOOR. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 601.1. |
| | |
| | 60. SHT P-12.5 TWR/13 DOES NOT REFLECT THE FLOOR PLAN. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1. |
| | |
| | 61. SHT P-12.6 THE PUMP SCHEDULE SP-2 ELEVATOR PIT |
| | SUMP. PLEASE SUBMIT A DETAIL. SHOW ALL PIPE SIZES, |
| | VALVES & VENTS AS WELL AS THE TERMINIATION POINT. |
| | SECTION 106.1.2.. ALSO PLEASE NOTE THE ELEVATOR SUMP |
| | SHALL BE INDIRECTLY CONNECTED TO THE SANITARY AND WILL |
| | BE REQUIRED TO BE DRAINED THRU AN INTERCEPTOR IF |
| | DRAINING TO THE SANITARY. SECTIONS 301.6, 712 & 1003.1. |
| | |
| | 62. SHT P-12.6 GAS WATER HEATER SCHEDULE. A SEPARATE |
| | GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE FOLLOWING |
| | INFORMATION REQUIRED FOR GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | L. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | 63. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM FOR THE |
| | PIPING AT THE HORIZONTAL CONDENSATE BUILDING DRAIN. |
| | SHOW ALL PIPE SIZES AND INDICATE WHERE ALL RISERS |
| | CONNECT TO THE BUILDING DRAIN. INDICATE THE TERMINATION |
| | POINT OF THE CONDENSATE. SECTIONS 106.1.2, 314.2.1 & |
| | 314.2.2. |
| | |
| | 64. ALL SANITARY, CONDENSATE & WATER RISER DESIGNATION |
| | NUMBERS SHALL BE INDICATED FROM THE START OF THE RISER |
| | THRU THE TOP. (EXAMPLE CONDENSATE RISERS C-1 & C-2 ARE |
| | NOT SHOWN UNTILL THE 3RD FLOOR). SHOW THE RISER AS |
| | RISER C-1, C-2 & C-3 ON SHEETS P-1.0 & P-2.0 SO THE |
| | RISERS CAN BE TRACKED FROM THE BUILDING DRAIN THRU THE |
| | TOP OF EACH RISER. SECTIONS 106.1.3, 314.2, 601.1, & |
| | 701.1. |
| | |
| | 65. SHTS P-13.0 & P-13.1 PER SECTION 917.3.2 A RELIEF |
| | VENT IS REQUIRED FOR ALL AIR ADMITTENCE VALVES FROM THE |
| | 6TH FLOOR DOWN. (SEE RISERS S/1 THRU S/8 & S/10 THRU |
| | S/13). |
| | |
| | 66. SHTS P-13.0 & P-13.1 RISERS S/1 THRU S/8 & S/10 |
| | THRU S/13 A VENT STACK IS REQUIRED PER SECTION 903.2 |
| | AND SHALL TERMINATE OUTDOORS IN OPEN AIR PER SECTION |
| | 903.3. ALL VENTS SHALL CONNECT AT THE BASE OF THE |
| | DRAINAGE STACK. SECTION 903.4. |
| | |
| | 67. SHT P-13.1 RISER S/9 IS INDICATED AS A 3" STACK. |
| | PER TABLE 912.3 A 4" STACK IS REQUIRED AND PER SECTION |
| | 903.3 THE STACK VENT SHALL TERMINATE OUTDORRS IN OPEN |
| | AIR. |
| | |
| | 68. SHTS P-13.0 & P-13.1 RISERS S/1 THRU S/13 AIR |
| | ADMITTENCE VALVES ARE NOT PERMITTED ON THE TOP OF THE |
| | STACKS PER SECTIONS 917.2 & 917.3 BUT ARE REQUIRED TO |
| | EXTEND TO OPEN AIR PER SECTION 903.3. |
| | |
| | 69. SHTS P-13.0 & P-13.1 SUBMIT A DETAIL FOR THE STUDOR |
| | P.A.P.A. SHOWN ON RISERS S/1 THRU S/13. SECTION |
| | 106.2.1. (MORE INFORMATION REQUIRED). |
| | |
| | 70. SHT P-13.0 RISER S/2 9TH FLOOR P7 SINK SHALL |
| | DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP. SECTION |
| | 909.1.1. (WET VENT). |
| | |
| | 71. SHT P-13.0 RISER S/4 DOES NOT REFLECT THE FLOOR |
| | PLAN AT THE OFFSETS TO THE W/C'S & LAVS. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 72. SHT P-13.0 RISER S/5 DOES NOT REFLECT THE FLOOR |
| | PLAN FOR THE OFFSETS FOR THE SHOWER AT THE 3RD FLOOR, |
| | AND FOR THE LAV OFFSETS ON THE 4TH THRU 10TH FLOORS. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 73. SHT P-13.0 RISER S/6 9TH DOES NOT REFLECT THE FLOOR |
| | PLAN. THE FLOOR SHOWS 2 LAVS, BUT THERE IS ONLY ONE |
| | SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 701.1. |
| | |
| | 74. SHT P-13.0 RISER S/7 DOES NOT REFLECT THE FLOOR |
| | PLAN. THERE ARE NO 2ND FLOOR FIXTURES SHOWN ON THE |
| | RISER AND SHOW ALL PIPING ON THE 9TH FLOOR AND THE P7 |
| | SINK SHALL DISCHARGE DOWNSTREAM OF THE BATHROOM |
| | FIXTURES PER SECTION 909.1.1. |
| | |
| | 75. SHT P-13.2 RISER S/7 DOES NOT REFLECT THE FLOOR |
| | PLAN AT ROOM 214 FOR FIXTURE P6. PLEASE INDICATE WHERE |
| | RISER S/7 CONTINUES ON THE RISER DIAGRAM. ALSO INDICATE |
| | WHAT FLOOR THE RISER REPRESENTS. PLEASE CORRELATE. |
| | SECTIONS 106.1.1 & 701.1. |
| | |
| | 76. SHT P-13.2 ALL RISERS FROM THE 6TH FLOOR DOWN SHALL |
| | HAVE A RELIEF VENT FOR THE AIR ADMITTENCE VALVES. |
| | SECTION 917.3.2. |
| | |
| | 77. SHT P-13.2 RISER S/18 WET VENT TO P6 & P2B FIXTURES |
| | TO BE 3" PER SECTION 909.3. PLEASE SHOW THE SECTION OF |
| | PIPE UPSTREAM OF THE W/C'S TO BE 3". |
| | |
| | 78. SHT P-13.2 RISERS S/7 & S/13 THRU S/19 PLEASE |
| | INDICATE WHICH FLOOR THESE RISER REPRESENT. SECTION |
| | 106.1.2 |
| | |
| | 79. SHT SHT P-13.3 RISERS S/22, S/23, S/24 & SND S/24. |
| | INDICATE THE RISERS REPRESENT AND CLAIRFY WHY 2 RISERS |
| | WITH THE S/24 DESIGNATION. SECTIONS 106.1.1 & 701.1. |
| | |
| | 80. SHT P-13.3 RISER S/24 ON THE LEFT SIDE OF THE SHEET |
| | SHOWS NO VENT TERMINATION. SECTION 903.3. PLEASE |
| | INDICATE VENT TERMINATION. |
| | |
| | 81. SHT P-13.3 SHOWS ISOMETRIC RISER DIAGRAM BELOW |
| | RISER S/24 ON THE RIGHT SIDE OF THE SHEET WITH NO RISER |
| | DESIGNATION. NO FIXTURE DESIGNATIONS, PIPE SIZES NOR |
| | FLOOR INDICATED. PLEASE CLARIFY. SECTIONS 106.1.1, |
| | 106.2, 701.1, 709,1 & 710.1(2). |
| | |
| | 82. SHT P-14.1 INDICATE THE RISER NUMBER FOR THE 1ST |
| | RISER ON THE LEFT SIDE OF THE SHEET. SECTIONS 106.1.2 & |
| | 701.1. |
| | |
| | 83. SHT P-14.1 RISERS DO NOT REFLECT THE FLOOR PLANS. |
| | RISERS C/2, C/7, C/8, C/10 THRU C/16, & C/18 ARE NOT |
| | SUBMITTED. PLEASE SUBMIT ALL RISERS FOR THE CONDENSATE |
| | SYSTEM THAT REFLECT THE FLOOR PLANS. SECTION |
| | 106.3.5.1.3. |
| | |
| | 84. ALL SHEETS SHALL BE SIGNED, SEALED AND DATED WHEN |
| | APPLYING FOR PERMIT. SECTION 106.1, FAC 61G1-16, |
| | 61G15-23 & FS 471, 481. |
| | |
| | 85. PLANS/DRAWING DO NOT APPEAR TO BE 100% THIS |
| | SUBMITTAL. MORE COMMENTS MAY BE FORTHCOMING WHEN |
| | RESPONSES TO THE ABOVE COMMENTS ARE SUBMITTED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |