Plan Review Notes
Plan Review Notes For Permit 09010006
Permit Number 09010006
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-18 16:54:26DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE WEST PALM BEACH
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS LS-1, LS-2 & LS-3. THE BUILDING CODE ANALYSIS
 SHALL INCLUDE THE 2007 AMENDMENTS. ALSO IF THE PERMIT
 IS NOT APPLIED FOR PRIOR TO MARCH 1, 2009 THE NEW
 FBC-2007 CODE WILL BE ADOPTED AND THE BUILDING PLANS
 SHALL BE DESIGNED TO THE FBC- 2007. SECTION 106.1.1.
  
 2. SHT A-1.0 MEN'S AND WOMEN'S TOILET ROOM 116 & 116
 AND DRINKING FOUNTAINS. SHOW COMPLIANCE WITH THE
 FOLLOWING SECTIONS: 11-4.15, 11-4.16, 11-4.17, 11-4.18,
 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS & FIGURES.
  
 3. SHT A-1.0 MEZZENINE PLAN MEN'S & WOMEN'S LOCKERS.
 SHOW COMPLIANCE WITH THE FOLLOWING SECTIONS: 11-4.16,
 11-4.19, 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS AS WELL
 AS SECTION 11-4.24 WITH ALL SUBSECTIONS FOR THE BREAK
 SINK.
  
 4. SHT A-2.0 SUBMIT CALCULATIONS FOR ALL ROOF/DECK
 DRAINS ON THE EAST & WEST SIDES OF THE BUILDING. SHOW
 THE SQUARE FOOTAGE AREA FOR EACH DRAIN & 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. SHOW THE LOCATION OF THE REQUIRED SECONDARY
 DRAINAGE SHOWING THE SIZE OF THE DRAINS PER SECTIONS
 1106 & 1107 WITH ALL SUBSECTIONS & TABLES.
  
 5. SHT A-2.0 TOILET ROOM H.C. (202) SHOW COMPLIANCE
 WITH THE FOLLOWING: SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS.
  
 6. SHTS A-2.0, A-3.0, A-4.0, A-5.0, A-6.0, A-7.0 A-8.0,
 A-9.0 & A-10.0. PLEASE SHOW COMPLIANCE WITH SECTIONS
 11-9.1.2, 11-9.1.3, 11-9.1.4 & 11-9.2.3. INDICATE THE
 NUMBER OF GUEST ROOMS AVAILABLE. INDICATE THE LOCATION
 OF SLEEPING ACCOMODATIONS FOR PERSONS WITH HEARING
 IMPAIRMENTS, INDICATE ALL AVAILABLE CLASSES OF SLEEPING
 ACCOMMODATIONS & SHOW HOW THEY ARE DISPERSED AMONG
 VARIOUS CLASSES. INDICATE GUESTROOMS THAT COMPLY WITH
 SPECIAL ACCESSIBILITY FEATURES. SECTION 106.1.2.
  
 7. SHT A-3.0 INDICATE HOW THE ROOF TERRACES WILL DRAIN
 THE STORM WATER. SECTIONS 106.1.2, 1106 & 1107.
  
 8. SHT A-11.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. INDICATE THE AREA OF EACH DRAIN
 AND SHOW 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO EACH DRAIN. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS & TABLES. SHOW HOW THE UPPER ROOFS WILL
 BE DRAINED. (SEE MACHINE ROOM, STAIRWAY, ELECTRICAL
 ROOM, TOILET ROOMS, STORAGE ROOM ETC.). SHOW PRIMARY
 AND SECONDARY LOCATIONS.
  
 9. SHT A-11.1 3RD LEVEL ROOF PLAN. INDICATE HOW THE
 AREAS BETWEEN COL. G & COL. H DRAIN. SECTIONS 106.1.1,
 1106 & 1107.
  
 10. SHTS A-12.0 & A-13.0 SHOW THE SIZE OF THE GUTTERS
 AND DOWNSPOUTS & INDICATE THE TOTAL SQUARE FOOTAGE
 DRAINING INTO THE GUTTERS & DOWNSPOUTS. TABLES 1106.3 &
 1106.6.
  
 11. SHT A-21.1 DETAIL 3 SHOWS A SECOND W/C & LAV NOT
 SHOWN ON SHT A-2.0 ROOM 205. PLEASE CORRELATE. SECTIONS
 106.1.1, 601.1 & 701.1.
  
 12. SHT A-21.1 DETAILS 1 & 3 REFERENCE
 ELEVATIONS/DETAILS 9 THRU 17 ON SHT A-21.1. THESE
 DETAILS WERE NOT SUBMITTED. ALSO DOTTED LINE
 PARTITIONS, DOORS ETC. SHOWN ON THE FLOOR PLAN. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 13. SHT A-21.2 DETAILS 1 & 3. PLEASE SHOW COMPLIANCE
 WITH THE FOLLOWING: SECTIONS 11-4.16, 11-4.19 & 11-4.23
 WITH ALL SUBSECTIONS.
  
 14. SHT A-21.2 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 15. SHT A-21.3 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 3 THRU 10 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 16. SHT A-21.4 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 17. SHT A-21.5 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 18. SHT A-21.6 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 19. SHT A-22.1 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 3 THRU 18 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 20. SHT A-22.2 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 3 THRU 26 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 21. SHTS A-22.4, A-22.5, A-22.6, A-22.7, A-22.8,
 A-22.9, A-22.10, A-22.11, A-22.12, A-22.13, A-22.14,
 A-22.15 & A-23.1 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 5 THRU 12 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 22. SHT A-23.2 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 5 THRU 16 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 23. SHT A-24.1 DETAILS 1 & 3 REFERENCES
 DETAILS/ELEVATIONS 3 THRU 18 ON THE FLOOR PLAN, BUT THE
 DETAILS/ELEVATIONS WERE NOT SUBMITTED. PLEASE SUBMIT
 REFERENCED DETAILS/ELEVATIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 24. SHT P-0.0 RISERS S/6-0, 5/8-0, S/9-0, S/14-0,
 S/15-0, S/20.0 & S/21-0 ARE NOT INDICATED ON THE FLOOR
 PLAN. PLEASE INDICATE WHERE EACH RISER STARTS FROM THE
 BUILDING THRU TO THE VENT THRU ROOF. SECTIONS 106.1.1,
 106.1.2 & 701.1 AS WELL AS TABLES 710.1(1) & 710.1(2).
  
 25. SHT P-0.0 RISERS S/6-2 & S/24-0 SHOW NO PIPING FROM
 THE BUILDING DRAIN. PLEASE SHOW ALL PIPING THAT
 REFLECTS THE RISER DIAGRAMS. SECTIONS 106.1.1 & 701.1
 AS WELL AS TABLES 710.1(1) & 710.0(2). -- ALSO THERE
 ARE TWO S/24 RISERS AND ONE S/24-1 RISER. PLEASE
 CLARIFY. SECTIONS 106.1.1 & 701.1.
  
 26. SHT P-0.0 NO RISER DESIGNATION NUMBER FOR THE RISER
 BY COL. AT COL. LINE C/2 NOR ON THE RISER NEXT TO
 S/23-0. PLEASE INDICATE RISER NUMBER. SECTION 106.1.1 &
 TABLES 710.1(1) & 710.0(2).
  
 27. SHT P-0.0 HAS NOTES "SEE LEVEL 1 FOR CONTINUATION"
 & "BOILER ROOM SEE LEVEL 1 DRAWING". PLEASE CLARIFY.
 WHAT SHEET IS LEVEL 1 ON? SECTIONS 106.1.1 & 701.1.
  
 28. SHT P-0.0 WHERE DO CONDENSATE RISERS CONNECT TO THE
 BUILDING CONDENSATE DRAIN? INDICATE THE TERMINATION
 POINT FOR THE CONDENSATE. INDICATE THE MATERIAL , PIPE
 SIZES ETC. SECTIONS 314.2 & 314.2.2.
  
 29. SHT P-1.0 IDENTIFY WHAT WILL DRAIN INTO THE TRENCH
 DRAIN BY THE SERVICE DUMPSTER (108). STORM WATER SHALL
 NOT DRAIN INTO THE SANITARY PER ARTICLE III SECTION
 90-125(5). DEPENDING ON THE COMMENT RESPONSE, A
 OIL/SAND INTERCEPTOR OR GREASE INTERCEPTOR MAY BE
 REQUIRED. SECTION 90-124(7).
  
 30. SHT P1.0 A GREASE INTERCEPTOR MAY BE REQUIRED, OR
 IF THERE IS A GREASE INTERCEPTOR IT SHALL BE CHECKED
 FOR SIZE AND/OR TO SEE IF THE INTERCEPTOR IS WORKING
 PROPERLY. PLEASE CONTACT THE UTILITY DEPT. INDUSTRIAL
 PRETREATMENT, ENVIRONMENTAL COMPLIANCE. CONTACT HOLLY
 MCGRATH LABORATORY SUPERVISOR BY PHONE (561) 822-2271,
 OR BY FAX (561) 822-2279 OR BY E-MAIL [email protected].
 A WRITTEN DETERMINATION SHALL BE SUBMITTED WITH PLANS
 INDICATING INTERCEPTOR SIZE ECT. ARTICLE III SECTION
 90-124(7).
  
 31. SHT P-1.0 RISERS S/6-1 & S/20-1 ARE NOT SHOWN ON
 THE FLOOR PLAN. ALSO SHOW THE VENTS FOR THE FUTURE
 RESTAURANT & RETAIL SPACES. SECTIONS 106.1.1 & 901.2.
  
 32. SHT P-1.0 RISERS DESIGNATED AS S/10-2, S/11-2,
 S/12-2 & S/14-2. ALL OTHER RISERS ON THIS SHEET HAVE A
 -1 DESIGNATION. PLEASE CORRELATE. SECTION 106.1.1 AND
 TABLE 710.1(1).
  
 33. SHT P-1.0 INDICATE THE SHEET NUMBER FOR THE
 CONTINUATION OF S/24-1, (SHOWN AS 2/24 ON SHT P-0.0 BUT
 AS S/24-1 ON SHTS P-1.0 & P-1.1). TABLE 710.0(1).
  
 34. SHT P-2.0 OFFSETS & PIPING FOR JANITOR MOP SINK
 ROOM 201, VENDING ROOM 206 & TOILET ROOM CONNECTING TO
 RISER S/1-2 ARE NOT INDICATED ON THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 106.1.1 & TABLES 710.1(1) &
 710.1(2).
  
 35. SHT P-2.0 OFFSETS SHOWN ON THE FLOOR PLAN FOR
 RISERS S/4-2, S/5-2, S/10-2, S/11-2 & S/12-2 ARE NOT
 SHOWN ON THE RISERS. PLEASE CORRELATE. SECTIONS 106.1.1
 & 701.1.
  
 36. SHT P-2.0 THE PIPING FOR KING ADA (219) & KING
 (217) ARE NOT SHOWN ON THE RISER DIAGRAM S/13-2. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 37. SHT P-2.0 RISER 2/20-2 IS NOT SHOWN ON THE FLOOR
 PLAN. PLEASE CLARIFY. SECTIONS 106.1.1 & 701.1.
  
 38. SHT P-3.0 INDICATE THE RISER NUMBERS WHERE RISERS
 OFFSET DOWN. SEE RISERS S/1-3, S/3-3 & S/10-3. SECTIONS
 106.1.1 & 701.1.
  
 39. SHT P-3.0 THE OFFSET FOR RISER S/13-3 SHOWN ON THE
 FLOOR PLAN IS NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 40. SHT P-8.0 RISER S/9.8 IS INDICATED AS S/9-10.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 41. SHT P-9.0 THE PIPING TO KING (B16)(921) IS NOT
 SHOWN ON RISER S/13-9. PLEASE CORRELATE. SECTIONS
 106.1.1 & 701.1.
  
 42. SHT P-10.0 THE PIPING TO THE BATHROOM BY COL. LINE
 4/F-G IS NOT SHOWN ON RISER DIAGRAM S/13-10. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 43. SUBMIT AN EXISTING ROOF PLAN SHOWING ALL EXISTING
 ROOF DRAINS, PRIMARY AND SECONDARY, WITH THE DRAIN
 SIZES. TABLES 1106.3 & 1106.7.
  
 44. SHT P-11.0 RISER S/20-11 SHOWS NO SANITARY
 CONNECTION TO RISER. PLEASE CLARIFY. SECTIONS 106.1.1 &
 701.1.
  
 45. SHT P-11.0 IT APPEARS THAT THE SQUARE FOOTAGE
 INDICATED FOR SOME ROOF AREAS ALONG WITH THE VERTICAL
 CONTRIBUTION ARE INCORRECT. (EXAMPLES: THE N.E. CORNER
 AREA BETWEEN COL. LINES A & B BY COL. LINE 3, (24' X
 16.5' = 396 SF BUT 317 SF IS INDICATED WITH 66 SF OF
 VERTICAL CONTRIBUTION) TOTAL EQUALS 462 SF. THE SAME
 SQUARE FOOT AREA FOR COL. LINES A & B BY COL. LINE 4 ON
 THE N.W. CORNER IS INDICATED AS 195 SF WITH 106 SF OF
 VERTICAL CONTRIBUTION.). PLEASE RECHECK AS SQUARE
 FOOTAGE AREA FOR ROOFS THAT DRAIN ONTO THE ROOF FROM
 ABOVE SHALL ALSO BE ADDED TO THE SQUARE FOOT AREA OF
 EACH DRAIN. SECTIONS 1106.2 & 1106.3.
  
 46. SHT P-12.0 DOMESTIC RISERS SHOW 3" RPZV BACKFLOWS.
 PER TABLE 603.1 WATER SERVICE SIZE, FOOTNOTE D, ALL
 BACKFLOW ASSEMBLIES SHALL BE AT LEAST THE SAME SIZE AS
 THE LINE IN WHICH THEY ARE INSTALLED. SINCE THE WATER
 SERVICE LINE IS 4" THEN THE BACKFLOWS SHALL BE 4".
  
 47. SHT P-12.0 ALL WATER RISER DIAGRAMS SHALL BE
 SUBMITTED IN ISOMETRIC FORM SHOWING ALL PIPE SIZES.
 SECTION 106.1.3. THE RISERS SHALL REFLECT THE PIPING
 SHOWN ON THE FLOOR PLAN. PIPING INDICATED ON THE 9TH &
 10TH FLOORS DO NOT REFLECT THE FLOOR PLANS AND THE
 RISERS NO NOT REFLECT THE FLOOR PLANS. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 48. SHT P-12.1 THE DOMESTIC RISER W/2 AT THE 9TH FLOOR
 DOES NOT REFLECT TWR-1. RISERS W/2 THRU W/6 DO NOT
 REFLECT THE FLOOR PLANS AT THE LAVS. FLOOR PLAN SHOWS
 THE WATER TO THE LEFT SIDE OF THE RISERS WHERE AS THE
 RISERS SHOW THE LAVS TO THE RIGHT SIDE OF THE RISERS.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 49. RISER W/7 HAS NOT BEEN SUBMITTED. SECTIONS
 106.3.5.1.3 & 601.1.
  
 50. SHT P-12.3 RISER W/15 DOES NOT REFLECT THE FLOOR
 PLAN, NOR DOES IT REFLECT TWR/15 AT THE BASE OF THE
 RISER, AT THE OFFSET ON THE 9TH FLOOR, NOR AT THE TOP
 OF THE RISER. PLEASE CORRELATE. SECTIONS 106.1.1 &
 601.1.
  
 51. SHT P-12.3 RISER W/9. WATER HAMMER ARRESTORS ARE
 REQUIRED AT EACH ICE MAKER. SECTION 604.9.
  
 52. SHT P-12.3 RISER W/18. SHOW THE PIPING AND VALVES
 TO REFLECT THE 11TH FLOOR. SECTIONS 106.1.2 & 601.1.
  
 53. SHT P-12.3 THE RISER TO THE LEFT OF THE GANG BATHS
 HAS NO DESIGNATION NUMBER. PLEASE INDICATE NUMBER FOR
 RISER. SECTIONS 106.1.2 & 601.1.
  
 54. SHT P-12.4 RISER W/7 DOES NOT REFLECT THE FLOOR
 PLAN OR RISER TWR/11 AT THE LAVS. ALSO NO TWR NUMBER IS
 INDICATED FOR THE 7TH & 9TH FLOORS, NO TWR NUMBER OR
 PIPING TO THE LAV AT THE 10TH FLOOR AND NO FLOOR
 DESIGNATIONS FOR THE 9TH & 10TH FLOORS. PLEASE CLARIFY.
 SECTIONS 106.1.1 & 601.1.
  
 55. SHT P-12.4 RISER W/14 DOES NOT REFLECT TWR/13 AT
 THE HOT RETURN FOR THE LAVS, NOR FOR THE COLD WATER TO
 THE W/C'S & LAVS, THE OFFSETS AT THE 9TH FLOOR DO NOT
 REFLECT THE FLOOR PLAN FOR THE HOT RETURN AS WELL AS
 THE RISER SHOWS FIXTURES ON THE 9TH & 10TH FLOORS NOT
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS
 106.1.1 & 601.1.
  
 56. SHT P-12.4 RISER W/14 DOES NOT REFLECT THE FLOOR
 PLAN AS THE LAVS & W/C'S ARE ON THE OPPOSITE SIDE OF
 THE SHOWER ON THE FLOOR PLAN ON THE 3RD THRU 8TH
 FLOORS, NOR DO THE OFFSETS REFLECT THE FLOOR PLAN AT
 THE TOP OF THE RISER. SECTIONS 106.1.1 & 601.1.
  
 57. SHTS P-12.1 THRU P-12.4 ALL RISERS HAVE A NOTE THAT
 STATES "SEE DETAIL" AT THE TOP OF THE RISERS. PLEASE
 INDICATE WHICH DETAIL, AND ALSO INDICATE WHERE THE
 DETAIL CAN BE LOCATED. SECTIONS 106.1.2 & 601.1.
  
 58. SHT P-12.5 ALL TYPICAL RISERS HAVE A NOTE THAT
 STATES "SEE BACK TO BACK DETAIL". PLEASE INDICATE WHERE
 THE DETAIL CAN BE LOCATED. SECTIONS 106.1.2 & 601.1.
  
 59. SHT P-12.5 TWR/8 SHOWS NO HOT WATER TO THE LAV, &
 THE FLOOR PLAN SHOWS AN OFFSET TO THE W/C FOR ALL
 FLOORS EXCEPT THE 9TH FLOOR. PLEASE CORRELATE. SECTIONS
 106.1.1 & 601.1.
  
 60. SHT P-12.5 TWR/13 DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 61. SHT P-12.6 THE PUMP SCHEDULE SP-2 ELEVATOR PIT
 SUMP. PLEASE SUBMIT A DETAIL. SHOW ALL PIPE SIZES,
 VALVES & VENTS AS WELL AS THE TERMINIATION POINT.
 SECTION 106.1.2.. ALSO PLEASE NOTE THE ELEVATOR SUMP
 SHALL BE INDIRECTLY CONNECTED TO THE SANITARY AND WILL
 BE REQUIRED TO BE DRAINED THRU AN INTERCEPTOR IF
 DRAINING TO THE SANITARY. SECTIONS 301.6, 712 & 1003.1.
  
 62. SHT P-12.6 GAS WATER HEATER SCHEDULE. A SEPARATE
 GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE FOLLOWING
 INFORMATION REQUIRED FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 63. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM FOR THE
 PIPING AT THE HORIZONTAL CONDENSATE BUILDING DRAIN.
 SHOW ALL PIPE SIZES AND INDICATE WHERE ALL RISERS
 CONNECT TO THE BUILDING DRAIN. INDICATE THE TERMINATION
 POINT OF THE CONDENSATE. SECTIONS 106.1.2, 314.2.1 &
 314.2.2.
  
 64. ALL SANITARY, CONDENSATE & WATER RISER DESIGNATION
 NUMBERS SHALL BE INDICATED FROM THE START OF THE RISER
 THRU THE TOP. (EXAMPLE CONDENSATE RISERS C-1 & C-2 ARE
 NOT SHOWN UNTILL THE 3RD FLOOR). SHOW THE RISER AS
 RISER C-1, C-2 & C-3 ON SHEETS P-1.0 & P-2.0 SO THE
 RISERS CAN BE TRACKED FROM THE BUILDING DRAIN THRU THE
 TOP OF EACH RISER. SECTIONS 106.1.3, 314.2, 601.1, &
 701.1.
  
 65. SHTS P-13.0 & P-13.1 PER SECTION 917.3.2 A RELIEF
 VENT IS REQUIRED FOR ALL AIR ADMITTENCE VALVES FROM THE
 6TH FLOOR DOWN. (SEE RISERS S/1 THRU S/8 & S/10 THRU
 S/13).
  
 66. SHTS P-13.0 & P-13.1 RISERS S/1 THRU S/8 & S/10
 THRU S/13 A VENT STACK IS REQUIRED PER SECTION 903.2
 AND SHALL TERMINATE OUTDOORS IN OPEN AIR PER SECTION
 903.3. ALL VENTS SHALL CONNECT AT THE BASE OF THE
 DRAINAGE STACK. SECTION 903.4.
  
 67. SHT P-13.1 RISER S/9 IS INDICATED AS A 3" STACK.
 PER TABLE 912.3 A 4" STACK IS REQUIRED AND PER SECTION
 903.3 THE STACK VENT SHALL TERMINATE OUTDORRS IN OPEN
 AIR.
  
 68. SHTS P-13.0 & P-13.1 RISERS S/1 THRU S/13 AIR
 ADMITTENCE VALVES ARE NOT PERMITTED ON THE TOP OF THE
 STACKS PER SECTIONS 917.2 & 917.3 BUT ARE REQUIRED TO
 EXTEND TO OPEN AIR PER SECTION 903.3.
  
 69. SHTS P-13.0 & P-13.1 SUBMIT A DETAIL FOR THE STUDOR
 P.A.P.A. SHOWN ON RISERS S/1 THRU S/13. SECTION
 106.2.1. (MORE INFORMATION REQUIRED).
  
 70. SHT P-13.0 RISER S/2 9TH FLOOR P7 SINK SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP. SECTION
 909.1.1. (WET VENT).
  
 71. SHT P-13.0 RISER S/4 DOES NOT REFLECT THE FLOOR
 PLAN AT THE OFFSETS TO THE W/C'S & LAVS. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 72. SHT P-13.0 RISER S/5 DOES NOT REFLECT THE FLOOR
 PLAN FOR THE OFFSETS FOR THE SHOWER AT THE 3RD FLOOR,
 AND FOR THE LAV OFFSETS ON THE 4TH THRU 10TH FLOORS.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 73. SHT P-13.0 RISER S/6 9TH DOES NOT REFLECT THE FLOOR
 PLAN. THE FLOOR SHOWS 2 LAVS, BUT THERE IS ONLY ONE
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS
 106.1.1 & 701.1.
  
 74. SHT P-13.0 RISER S/7 DOES NOT REFLECT THE FLOOR
 PLAN. THERE ARE NO 2ND FLOOR FIXTURES SHOWN ON THE
 RISER AND SHOW ALL PIPING ON THE 9TH FLOOR AND THE P7
 SINK SHALL DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES PER SECTION 909.1.1.
  
 75. SHT P-13.2 RISER S/7 DOES NOT REFLECT THE FLOOR
 PLAN AT ROOM 214 FOR FIXTURE P6. PLEASE INDICATE WHERE
 RISER S/7 CONTINUES ON THE RISER DIAGRAM. ALSO INDICATE
 WHAT FLOOR THE RISER REPRESENTS. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 701.1.
  
 76. SHT P-13.2 ALL RISERS FROM THE 6TH FLOOR DOWN SHALL
 HAVE A RELIEF VENT FOR THE AIR ADMITTENCE VALVES.
 SECTION 917.3.2.
  
 77. SHT P-13.2 RISER S/18 WET VENT TO P6 & P2B FIXTURES
 TO BE 3" PER SECTION 909.3. PLEASE SHOW THE SECTION OF
 PIPE UPSTREAM OF THE W/C'S TO BE 3".
  
 78. SHT P-13.2 RISERS S/7 & S/13 THRU S/19 PLEASE
 INDICATE WHICH FLOOR THESE RISER REPRESENT. SECTION
 106.1.2
  
 79. SHT SHT P-13.3 RISERS S/22, S/23, S/24 & SND S/24.
 INDICATE THE RISERS REPRESENT AND CLAIRFY WHY 2 RISERS
 WITH THE S/24 DESIGNATION. SECTIONS 106.1.1 & 701.1.
  
 80. SHT P-13.3 RISER S/24 ON THE LEFT SIDE OF THE SHEET
 SHOWS NO VENT TERMINATION. SECTION 903.3. PLEASE
 INDICATE VENT TERMINATION.
  
 81. SHT P-13.3 SHOWS ISOMETRIC RISER DIAGRAM BELOW
 RISER S/24 ON THE RIGHT SIDE OF THE SHEET WITH NO RISER
 DESIGNATION. NO FIXTURE DESIGNATIONS, PIPE SIZES NOR
 FLOOR INDICATED. PLEASE CLARIFY. SECTIONS 106.1.1,
 106.2, 701.1, 709,1 & 710.1(2).
  
 82. SHT P-14.1 INDICATE THE RISER NUMBER FOR THE 1ST
 RISER ON THE LEFT SIDE OF THE SHEET. SECTIONS 106.1.2 &
 701.1.
  
 83. SHT P-14.1 RISERS DO NOT REFLECT THE FLOOR PLANS.
 RISERS C/2, C/7, C/8, C/10 THRU C/16, & C/18 ARE NOT
 SUBMITTED. PLEASE SUBMIT ALL RISERS FOR THE CONDENSATE
 SYSTEM THAT REFLECT THE FLOOR PLANS. SECTION
 106.3.5.1.3.
  
 84. ALL SHEETS SHALL BE SIGNED, SEALED AND DATED WHEN
 APPLYING FOR PERMIT. SECTION 106.1, FAC 61G1-16,
 61G15-23 & FS 471, 481.
  
 85. PLANS/DRAWING DO NOT APPEAR TO BE 100% THIS
 SUBMITTAL. MORE COMMENTS MAY BE FORTHCOMING WHEN
 RESPONSES TO THE ABOVE COMMENTS ARE SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  