Plan Review Notes
Plan Review Notes For Permit 09010006
Permit Number 09010006
Review Stop M
Sequence Number 1
Notes
Date Text
2009-08-22 17:20:24REVIEW #:1ST *PLAN CHECK ONLY*
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: REVIEW WAS COMPLETED PRIOR TO EFFECTIVE DATE OF
 THE 2007 FBC. RESULTS WERE ENTERED INTO SYSTEM AT A
 LATER DATE. BECAUSE A PERMIT APPLICATION HAS NOT BEEN
 SUBMITTED, SUBSEQUENT PLANS SUBMITTED AFTER MARCH 1,
 2009 WILL BE REVIEWED FOR COMPLIANCE WITH THE 2007 FBC
 WITH 2009 SUPPLEMENT.
  
 1. M-0.1: SEVERAL DUCT PENETRATIONS AND AIR TRANSFER
 OPENINGS IN 1 AND 2 HOUR RATED WALLS SHOWN WITHOUT
 PROTECTION AT SOILED LAUNDRY 005, SECURED STORAGE 007,
 A/C 008, ENGINEERING 009 AND CORRIDOR. SHOW HOW THESE
 PENETRATIONS AND OPENINGS ARE TO BE PROTECTED IN
 ACCORDANCE WITH FBC-M 607.5. ALSO, A 24X24 DOOR LOUVER
 IS SHOWN IN RATED DOOR AT SOILED LAUNDRY 005. VERIFY
 OPENING PROTECTION AT THIS LOCATION.
  
 2. M-0.1: SEVERAL R/A OPENINGS SHOWN IN WALLS WITH NO
 SIZE PROVIDED. SHOW SIZES OF ALL TRANSFER OPENINGS TO
 DEMONSTRATE BALANCED RETURN IN ACCORDANCE WITH FBC-M
 601.4.
  
 3. M-0.1: SOME R/A OPENINGS ARE SHOWN WHERE NO WALL OR
 DOOR IS SHOWN ON FLOOR PLAN. PLEASE CLARIFY LOCATION OF
 THESE OPENINGS TO DEMONSTRATE BALANCED RETURN IN
 ACCORDANCE WITH FBC-M 601.4.
  
 4. M-0.1: AHU-12 IS SHOWN OUTSIDE OF A/C CLOSET 004.
 PLEASE CLARIFY LOCATION TO DEMONSTRATE COMPLIANCE WITH
 ACCESS REQUIREMENTS FOR SERVICE, MAINTENANCE AND
 REPLACEMENT IN ACCORDANCE WITH FBC-M 306.1.
  
 5. M-1.0: NOTES FOR DIRECT-VENT PIPES ARE CUT OFF FROM
 PAGE AND NOT LEGIBLE. THIS CAN NOT BE REVIEWED AT THIS
 TIME. DIRECT-VENT APPLIANCES SHALL BE PROVIDED WITH
 COMBUSTION, VENTILATION AND DILUTION AIR IN ACCORDANCE
 WITH THE EQUIPMENT MANUFACTURER???S INSTRUCTIONS PER
 FBC-FG 304.1.
  
 6. M-1.0 AND M-1.1: MECH FLOOR PLANS DO NOT SHOW HOW
 DUCT SUPPLY DUCT FROM MEZZANINE WILL PASS THROUGH 1ST
 FL TO REACH CORRIDOR ON BASE FLOOR. SHOW ROUTING OF
 THIS DUCT ON FLOOR PLAN AND SHOW HOW ANY PENETRATIONS
 OF HORIZONTAL ASSEMBLIES ARE TO BE PROTECTED IN
 ACCORDANCE WITH FBC-M 607.6 AND 607.8.
  
 7. THROUGHOUT MECHANICAL PLANS THERE ARE RISER DUCTS
 WHICH APPEAR TO BE PENETRATING RATED HORIZONTAL
 ASSEMBLIES WITH NO PROTECTION. SHOW HOW ALL SUPPLY,
 RETURN, EXHAUST OR FRESH AIR DUCT PENETRATIONS OF RATED
 HORIZONTAL ASSEMBLIES ARE TO BE PROTECTED IN ACCORDANCE
 WITH FBC-M 607.5.5, 607.6 AND 607.8. NO SHAFT
 ENCLOSURES APPEAR TO BE IDENTIFIED ON PLANS. DUCT
 PENETRATIONS OF SHAFT ENCLOSURES SHALL BE PROTECTED
 WITH FIRE AND SMOKE DAMPERS IN ACCORDANCE WITH FBC-M
 607.5.5.1.
  
 8. M-1.0: GENERATOR ROOM EXHAUST AND INTAKE OPENINGS
 SHALL BE MINIMUM 10 FEET FROM STREETS, ALLEYS AND
 ADJACENT PROPERTY LINES IN ACCORDANCE WITH FBC-M 401.5.
  
 9. M-1.0: SHOW LOCATION OF GENERATOR COMBUSTION EXHAUST
 IN ACCORDANCE WITH FBC-M 401.5 AND FBC-M 501.2.
  
 10. NO VENTILATION SCHEDULE OR CALCULATIONS WERE
 PROVIDED FOR REVIEW. PROVIDE A SPACE-BY-SPACE SCHEDULE
 WITH CALCULATIONS BASED ON OCCUPANCY CLASSIFICATION,
 OCCUPANT LOAD AND REQUIRED VENTILATION RATES IN
 ACCORDANCE WITH FBC-M TABLE 403.3 OR FBC-M 403.4.
 COMPLIANCE WITH VENTILATION REQUIREMENTS FOR THIS
 BUILDING CAN NOT BE REVIEWED AT THIS TIME.
  
 11. M-1.0: A/V STORAGE 112 SHOWS AN UNIDENTIFIED
 EXHAUST FAN WITH 8??? DUCT DISCHARGING INTO MEETING
 ROOMS. ALL MECHANICAL EXHAUST SYSTEMS SHALL DISCHARGE
 DIRECTLY TO THE OUTDOORS IN ACCORDANCE WITH FBC-M
 501.2.
  
 12. M-1.0: FLOOR PLAN SHOWS A RETURN AIR PLENUM
 CEILING. THERE ARE MULTIPLE EXHAUST DUCTS AND GAS
 APPLIANCE VENTS SHOWN PASSING THROUGH THIS PLENUM
 CEILING AREA. EXHAUST DUCTS UNDER POSITIVE PRESSURE,
 CHIMNEYS, AND VENTS SHALL NOT EXTEND INTO OR PASS
 THROUGH RETURN AIR PLENUMS IN ACCORDANCE WITH FBC-M
 601.3.
  
 13. M-1.0 AND THROUGHOUT PLANS: THERE ARE EXHAUST FANS,
 VAV BOXES, FAN-COILS AND OTHER EQUIPMENT WHICH ARE NOT
 LABELED OR IDENTIFIED ON PLANS. UNLABELED OR
 UNIDENTIFIED EQUIPMENT ON PLANS PREVENTS A THOROUGH
 REVIEW OF PLANS AT THIS TIME. ALL APPLIANCES SHALL BE
 IDENTIFIED ON PLANS AS TO THE AREA SERVED IN ACCORDANCE
 WITH FBC-M 304.11.
  
 14. M-1.0 AND THROUGHOUT PLANS: THERE ARE MULTIPLE WALL
 PARTITIONS WHICH ARE NOT IDENTIFIED IN ARCHITECTURAL
 PLANS. IT IS NOT POSSIBLE TO DETERMINE THE LOCATION OF
 ALL RATED WALL ASSEMBLIES TO DETERMINE IF ALL DUCT
 PENETRATIONS AND AIR TRANSFER OPENINGS ARE PROTECTED IN
 ACCORDANCE WITH FBC-M SECTION 607. A THOROUGH REVIEW OF
 PLANS CAN NOT BE COMPLETED AT THIS TIME. ALL FIRE
 DAMPERS, SMOKE DAMPERS AND COMBINATION FIRE/SMOKE
 DAMPERS SHALL BE SHOWN AND IDENTIFIED ON PLANS IN
 ACCORDANCE WITH FBC-M 607.8.
  
 15. M-1.1: O.A INTAKES FOR AHU-1 AND AHU-2 APPEAR TO BE
 DIRECTLY ADJACENT TO A PROPERTY LINE AND AN ALLEY. O.A.
 INTAKES SHALL BE MIN. 10 FEET FROM THE ALLEY IN
 ACCORDANCE WITH FBC-M 401.4.1.
  
 16. M-1.1: A 6X4 DUCT IS SHOWN PENETRATING WHAT MAY BE
 A RATED STAIR ENCLOSURE. PENETRATIONS OF RATED EXIT
 ENCLOSURES ARE PROHIBITED IN ACCORDANCE WITH FBC-B
 SECTION 1019.
  
 17. SECOND THROUGH 10TH FLOORS: ALL DUCT PENETRATIONS
 OF CORRIDOR WALLS SHALL BE PROTECTED WITH FIRE AND
 SMOKE DAMPERS IN ACCORDANCE WITH FBC-M 607.5.3 AND
 607.5.4.
  
 18. THROUGHOUT PLANS: CFM AND GRILL DESIGNATIONS ARE
 MISSING ON PLANS. A REVIEW OF REQUIRED SYSTEMS AND
 AIRFLOW RATES CAN NOT BE PERFORMED AT THIS TIME.
 PROVIDE MISSING INFORMATION IN ACCORDANCE WITH FBC-M
 SECTION 403, SECTION 501 AND 603.1.
  
 19. NO INFORMATION WAS PROVIDED REGARDING WIND
 RESISTANCE OF OUTDOOR APPLIANCES. ALL OUTDOOR
 APPLIANCES INCLUDING, BUT NOT LIMITED TO FANS,
 CONDENSERS, CHILLERS, INTAKE VENTS, DUCTS AND SUPPORTS
 SHALL BE DESIGNED AND INSTALLED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.13. PROVIDE MANUFACTURER???S
 DATA SHOWING OUTDOOR APPLIANCES ARE DESIGNED FOR WIND
 RESISTANCE. ALSO PROVIDE ENGINEERED INSTALLATION
 INSTRUCTIONS FOR WIND RESISTANT INSTALLATION OF ALL
 OUTDOOR APPLIANCES AND EQUIPMENT.
  
 20. PROVIDE PRODUCT APPROVALS FOR LOUVERS AND ANY
 PRE-ENGINEERED A/C STANDS TO BE INSTALLED IN ACCORDANCE
 WITH FBC-B 106.1.4.
  
 21. VENTILATION FOR ELEVATOR MACHINE ROOM COULD NOT BE
 FOUND ON PLANS. INDEPENDENT VENTILATION OR AIR
 CONDITIONING SYSTEM IS REQUIRED IN THE MACHINE ROOM IN
 ACCORDANCE WITH FBC-B 3006.2. VENTS ARE REQUIRED IN THE
 HOISTWAYS IN ACCORDANCE WITH FBC-B SECTION 3004. ALSO,
 IF THE ELEVATORS ARE CONNECTED TO STANDBY POWER, THE
 VENTILATION SYSTEM SHALL BE CONNECTED TO THE STANDBY
 POWER IN ACCORDANCE WITH FBC-B 3003.1.4.
  
 22. NO ENERGY CODE COMPLIANCE FORMS WERE SUBMITTED FOR
 REVIEW. THIS BUILDING MAY OR MAY NOT BE EXEMPT FROM
 FLORIDA ENERGY CODE COMPLIANCE AS A DESIGNATED HISTORIC
 BUILDING IN ACCORDANCE WITH FBC-B 13-101.5.5. IF A
 HISTORIC EXEMPTION IS CLAIMED, PROVIDE SUPPORTING
 DOCUMENTATION OF THE HISTORIC DESIGNATION. OTHERWISE,
 PROVIDE FULL ENERGY CODE COMPLIANCE DOCUMENTATION FOR
 REVIEW. A REVIEW FOR ENERGY CODE COMPLIANCE IS NOT
 BEING PERFORMED AT THIS TIME.
  
 23. THERE IS NO INDICATION ON PLANS REGARDING STAIR
 PRESSURIZATION OF EXIT ENCLOSURE(S). IDENTIFY ON PLANS
 ANY STAIR ENCLOSURES WHICH REQUIRE PRESSURIZATION IN
 ACCORDANCE WITH FBC-B 1019.1.8. SHOW MEANS OF
 PRESSURIZATION ON MECHANICAL PLANS.
  
 24. NO MEANS OF SMOKE CONTROL IS SHOWN ON PLANS.
 PROVIDE SUPPORTING DOCUMENTATION FOR BUILDING SMOKE
 CONTROL SYSTEM INCLUDING RATIONAL ANALYSIS AND SHOW ALL
 SYSTEM COMPONENTS ON PLANS IN ACCORDANCE WITH FBC-M
 SECTION 513, FBC-B SECTION 909 AND FBC-B 106.1.1.
  
 25. NO LAUNDRY FACILITIES WERE IDENTIFIED ON PLANS
 (COMMERCIAL OR DOMESTIC). IF ANY ON-SITE LAUNDRY
 FACILITIES ARE TO BE PROVIDED, SHOW THE LOCATION ON
 PLANS ALONG WITH MEANS OF EXHAUST, COMBUSTION AND
 MAKEUP AIR IN ACCORDANCE WITH FBC-M SECTION 504.
  
 26. NO COMMERCIAL KITCHEN COOKING EQUIPMENT WAS SHOWN
 ON PLANS. SEPARATE PLANS AND PERMIT WILL BE REQUIRED
 FOR COMMERCIAL KITCHEN EXHAUST, HOOD AND SUPPRESSION
 SYSTEMS.
  
 27. NO INFORMATION WAS PROVIDED REGARDING THE GENERATOR
 OR RELATED FUEL STORAGE SYSTEMS. THE GENERATOR, FUEL
 STORAGE AND PIPING SHALL BE INSTALLED IN ACCORDANCE
 WITH NFPA 37-02 PER FBC-M SECTION 915. ALSO, ANY
 ABOVE-GROUND FUEL STORAGE TANKS IN EXCESS OF 550
 GALLONS SHALL BE APPROVED BY PALM BEACH COUNTY DERM.
 SUBMIT DERM APPROVED PLANS WITH PERMIT APPLICATION. FOR
 MORE INFORMATION VISIT HTTP://PBCGOV.COM/ERM
  
 28. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-M 307.2.1. SHOW MEANS AND LOCATION
 OF AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH FBC-M
 307.2.3. THIS APPLIES TO ALL COILS UNDER WHICH
 CONDENSATION WILL OCCUR WITHIN THE BUILDING AS WELL AS
 ANY DOWNDRAFT EQUIPMENT WHICH MAY BE LOCATED ON A ROOF.
 NOTE: CONDENSATE MAY NOT DISCHARGE INTO SANITARY SEWER
 SYSTEM PER CITY ORDINANCE.
  
 NOTE: IN ORDER TO FACILITATE A TIMELY AND ACCURATE
 SUBSEQUENT REVIEW, PLEASE RESPOND TO EACH COMMENT IN
 WRITING, WITH SUFFICIENT INFORMATION REGARDING HOW EACH
 COMMENT WAS ADDRESSED AND WHERE ANY REQUESTED OR
 PROVIDED INFORMATION IS LOCATED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]