| 2009-03-02 16:18:08 | ***DENIED*** |
| | |
| | PLEASE NOTE THAT PLANS HAVE BEEN SUBMITTED FOR PLAN |
| | REVIEW ONLY. EVEN AFTER THE PLANS HAVE PASSED AND ARE |
| | CODE COMPLIANT, THEY WILL REMAIN IN FAILED STATUS UNTIL |
| | THE PLANS HAVE BEEN REVIEWED AND APPROVED FOR PERMIT |
| | APPLICATION. |
| | |
| | 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE |
| | PREVENTION CODE, 2007 WHICH INCLUDES NFPA 101, 2006 AND |
| | NFPA 1, 2006 AS OF DECEMBER 31, 2008. |
| | |
| | 2) A TEMPORARY STANDPIPE IS REQUIRED WHEN THE BUILDING |
| | REACHES THREE (3) STORIES OR THIRTY (30) FEET IN |
| | HEIGHT. |
| | |
| | 3) PLEASE ADD FIRE SPRINKLER 2002 EDITION TO THE |
| | BUILDING CODE ANALYSIS, LIFE SAFETY SYSTEMS ON SHEET |
| | LS-1. |
| | |
| | 4) THERE APPEARS TO BE CONFLICTING INFORMATION |
| | REGARDING THE NUMBER OF STORIES ON THE COVER SHEET AND |
| | THE LIFE SAFETY SHEETS. PLEASE CORRELATE THE |
| | INFORMATION ON ALL SUBMITTED SHEETS FOR REVIEW. |
| | |
| | 5) TRAVEL DISTANCE TO THE NEAREST EXIT SHALL NOT EXCEED |
| | 200' IN ACCORDANCE WITH 101, SEC. 28.2.6.3.3.1 FOR |
| | STRUCTURES PROTECTED THROUGHOUT WITH AN AUTOMATIC FIRE |
| | SPRINKLER SYSTEM. CODE ANALYSIS EXIT REQUIREMENTS |
| | |
| | 6) THIS PROJECT SHALL COMPLY WITH THE REQUIREMENTS OF |
| | 101, SEC. 11.8 FOR HIGHRISE STRUCTURES. |
| | |
| | 7) TACTILE SIGNAGE IS REQUIRED FOR EXIT STAIRS |
| | INDICATING THE FLOOR LEVEL, STAIR IDENTIFICATION, AND |
| | TERMINUS OF THE TOP AND BOTTOM OF THE STAIR ENCLOSURE. |
| | |
| | 8) PLEASE SUBMIT FIRE PROTECTION DRAWINGS ILLUSTRATING |
| | THE FIRE SPRINKLER HEAD LAYOUT. IN ADDITON, SEPARATE |
| | SHOP DRAWINGS AND PERMIT ARE REQUIRED PRIOR TO |
| | EQUIPMENT INSTALLATION. |
| | |
| | 9) PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION AND |
| | DETAILS OF THE DOUBLE CHECK DETECTOR ASSEMBLY THAT IN |
| | ADDITION TO ELECTRONIC SUPERVISION, SHALL BE SECURED |
| | WITH A CHAIN AND LOCK. |
| | |
| | 10) SOME FIRE ALARM EQUIPMENT IS SHOWN ON THE E- |
| | SHEETS. PLEASE SUBMIT CLEAR DRAWINGS SHOWING ALL FIRE |
| | ALARM DEVICES AND ASSOCIATED EQUIPMENT. IN ADDITION, |
| | SEPARATE SHOP DRAWINGS AND PERMIT ARE REQUIRED PRIOR TO |
| | EQUIPMENT INSTALLATION. |
| | |
| | 11) FIRE ALARM TO BE UL CERTIFICATED FOR CENTRAL |
| | STATION SERVICE WITH PROOF OF CERTIFICATION REQUIRED AT |
| | OR BEFORE THE FINAL INSPECTION. |
| | |
| | 12) FIRE ALARM SYSTEM TO COMPLY WITH THE HIGHRISE |
| | REQUIREMENTS FOR SURVIVABILITY IN ACCORDANCE WITH NFPA |
| | 72, 2002. |
| | |
| | 13) HANDRAILS ARE REQUIRED ON BOTH SIDES OF STAIRS. |
| | |
| | 14) PROVIDE THE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR |
| | HANDRAILS AND GUARDRAILS. |
| | |
| | 15) A MINIMUM OF TWO (2) FIRE DEPARTMENT CONNECTIONS |
| | ARE REQUIRED ON HIGHRISE STRUCTURES THAT ARE LOCATED AT |
| | REMOTE LOCATIONS FROM ONE ANOTHER. FDC'S TO BE |
| | IDENTIFIED BY APPROVED SIGNAGE. |
| | |
| | 16) PROVIDE A SITE PLAN SHOWING ALL PERTINENT FIRE |
| | PROTECTION EQUIPMENT SUCH AS FDC LOCATIONS, DOUBLE |
| | CHECK DETECTOR ASSEMBLY LOCATION WITH DETAILS, FIRE |
| | HYDRANTS ETC. SHOW COMPLIANCE WITH NFPA 1, CHAPTER-18 |
| | FOR EMERGENCY VEHICLE ACCESS AND WATER SUPPLY. |
| | |
| | 17) CUTTING AND WELDING OPERATIONS ARE PROHIBITED WITH |
| | PRIOR APPROVAL FROM THE BUREAU OF FIRE PREVENTION. WORK |
| | TO COMPLY WITH THE REQUIREMENTS OF NFPA 51B. CONTACT |
| | FIRE PREVENTION AT (561) 804-4724. |
| | |
| | 18) IDENTIFY THE EQUIPMENT SHOWN IN STAIR #1 ON THE |
| | NORTH WALL. PLEASE ILLUSTRATE STANDPIPE LOCATIONS AND |
| | CONNECTIONS. |
| | |
| | 19) PERMANENT STANDPIPES SHALL BE PROVIDED WITH 2 1/2"- |
| | 1 1/2" CONNECTIONS WITH CAPS AND CHAINS. |
| | |
| | 20) FIRE SPRINKLER PROTECTION TO BE EXTENDED TO THE |
| | LINEN CHUTE. SHOW FIRE SPRINKLER DETAIL. |
| | |
| | 21) EXIT SIGNS TO BE PROVIDED AT LOCATIONS NOT TO |
| | EXCEED 100' DISTANCES BETWEEN SIGNS. PLEASE SHOW |
| | COMPLIANCE WITH EXIT SIGNS IN ALL CORRIDORS. |
| | |
| | 22) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS TO BE |
| | PLACED AT LOCATIONS NOT TO EXCEED THE 75' TRAVEL |
| | DISTANCE REQUIREMENT. |
| | |
| | 23) IN ADDITION TO ALL AREAS OF MEANS OF EGRESS, THE |
| | POOL WALKING SURFACES SHALL BE SLIP RESISTANT. |
| | |
| | 24) ALL APPLICABLE ENCLOSED ROOFTOP STRUCTURES SHALL BE |
| | PROTECTED BY AUTOMATIC FIRE SPRINKLER COVERAGE. |
| | |
| | 25) PLEASE SHOW ALL ROOFTOP FIRE PROTECTION EQUIPMENT |
| | TO INCLUDE FIRE SPRINKLER, STANDPIPE CONNECTION AND |
| | FIRE ALARM EQUIPMENT. |
| | |
| | 26) THE BUILDING ADDRESS APPEARS TO BE DISPLAYED ON THE |
| | EAST AND WEST SIDES OF THE STRUCTURE. AN APPROVED |
| | ADDRESS IS REQUIRED AT THE AREA OF THE FRONT ENTRANCE |
| | TO THE BUILDING, AND SHALL COMPLY WITH THE CITY OF WEST |
| | PALM BEACH SIZE AND CONTRASTING REQUIREMENTS FOR |
| | COMMERCIAL BUILDINGS. THE ADDRESS SHALL BE CLEAR AND |
| | VISIBLE FROM THE CENTER LINE OF THE MAIN STREET OF |
| | APPROACH. SHEETS A-12.0 AND A-13.0 |
| | |
| | 27) PROVIDE FLAME RETARDANT INFORMATION FOR BUILDING |
| | AND ROOFTOP AWNINGS. |
| | |
| | 28) NEW FIRE DEPARTMENT CONNECTIONS TO BE PROVIDED WITH |
| | KNOX LOCKING CAPS. |
| | |
| | 29) PROVIDE DETAILS AND MANUFACTURER SPECIFICATION |
| | INFORMATION FOR THE FIRE PUMP. |
| | |
| | 30) PROVIDE DETAILS AND MANUFACTURER SPECIFICATION |
| | INFORMATION FOR THE GENERATOR AND ALL SUPPORTING |
| | EQUIPMENT AND FUEL TANK. |
| | |
| | 31) PROVIDE A CLEAR DETAIL AND EXPLANATION REGARDING |
| | EXITING FROM STAIR #2 ON THE NORTH SIDE OF THE |
| | STRUCTURE. IS IT THE INTENT TO EXIT PERSONS DIRECTLY TO |
| | THE BUILDING EXTERIOR? |
| | |
| | 32) KNOX BOXES TO BE PROVIDED FOR AFTER NORMAL BUSINESS |
| | HOURS EMERGENCY ACCESS TO THE BUILDING. CONTACT THE |
| | BUREAU OF FIRE PREVENTION AT (561) 804-4724 FOR |
| | ASSISTANCE. |
| | |
| | 33) DURING IT'S SWING, ANY DOOR IN A MEANS OF EGRESS |
| | SHALL LEAVE NOT LESS THAN 1/2 OF THE REQUIRED WIDTH OF |
| | AN AISLE, CORRIDOR, PASSAGEWAY OR LANDING UNOBSTRUCTED. |
| | 101, SEC. 7.2.1.4.4 |
| | |
| | 34) THE FIRE COMMAND ROOM TO COMPLY WITH THE |
| | REQUIREMENTS OF 101, SEC. 11.8.5 AND SHALL BE |
| | IDENTIFIED BY APPROVED SIGNAGE. PROVIDE DETAILS FOR ALL |
| | APPLICABLE EQUIPMENT INCLUDING SMOKE MANAGEMENT PANEL |
| | AND ALL OTHER EQUIPMENT REQUIRED AS PER 101, SEC. |
| | 11.8.5. |
| | |
| | 35) THE DESIGN OF THIS PROJECT SUGGESTS AN ATRIUM BY |
| | DEFINITION. PLANS DO NOT APPEAR TO INDICATE ANY TYPE OF |
| | SMOKE MANAGEMENT SYSTEM. PLEASE PROVIDE NECESSARY |
| | INFORMATION AND DETAILS. |
| | |
| | 36) PROVIDE PLANS AND DETAILS DESCRIBING REQUIRED |
| | STAIRWELL PRESSURIZATION SYSTEM. |
| | |
| | 37) FIRE DAMPERS ARE SHOWN PASSING THROUGH STAIR #2. |
| | PLEASE REFER TO 101, SEC. 7.1.3.2 (6) AND (7). NO |
| | PENETRATIONS ALLOWED IN EXIT ENCLOSURES THAT DO NOT |
| | MEET THE DEFINITION/EXCEPTIONS OF THAT SECTION OF THE |
| | LIFE SAFETY CODE. |
| | |
| | 38) THE FIRE PUMP IS IDENTIFIED AS 151 ON SHEET A-39.0 |
| | AND AS MECHANICAL 150 ON DETAILED PLAN. |
| | |
| | 39) THE DOOR SCHEDULE INDICATES CARD READERS. SEPARATE |
| | SHOP DRAWINGS AND PERMIT REQUIRED PRIOR TO EQUIPMENT |
| | INSTALLATION. ALL ASSOCIATED WORK TO COMPLY WITH 101, |
| | SEC. 7.2.1.6.2 FOR ACCESS CONTROLLED EGRESS DOORS. |
| | |
| | 40) ALL FIRE RATED DOORS TO BE PROVIDED WITH UL LISTED |
| | CLOSERS THAT CAUSE THE DOOR TO POSITIVELY LATCH. ADD |
| | NOTE TO THE DOOR SCHEDULE. |
| | |
| | 41) THE DOORS TO THE LINEN CHUTE SHALL POSITIVELY LATCH |
| | UPON CLOSING. |
| | |
| | 42 ELEVATOR LOBBIES SHALL BE PROVIDED WITH WARNING |
| | SIGNS IN CASE OF AN EMERGENCY. |
| | |
| | 43) FIRE/SMOKE DAMPERS TO BE TESTED FOR CLOSURE IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF UL 555 PRIOR TO |
| | FINAL INSPECTION. |
| | |
| | 44) DUCT SMOKE DETECTORS SHALL IN ADDITION TO FAN SHUT |
| | DOWN, INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH |
| | LOCAL REQUIREMENTS. |
| | |
| | 45) PLEASE CLARIFY IF THIS PROJECT MEETS THE DEFINITION |
| | OF A COMPLETE OR PARTIAL SMOKE DETECTION SYSTEM IN |
| | ACCORDANCE WITH NFPA 72, 2002. |
| | |
| | 46) HOW WILL THE SUITE SMOKE ALARMS FUNCTION WITH |
| | REGARD TO THE BUILDING FIRE ALARM SYSTEM? |
| | |
| | 47) PLEASE NOTE THAT SOME OF THE THE ELECTRICAL SHEETS |
| | ARE DIFFICULT TO READ TO REFERENCE THE LOCATION OF LIFE |
| | SAFETY EQUIPMENT. SHT E-2.0 AND E-2.1 |
| | |
| | 48) EMERGENCY INSTRUCTIONS SHALL BE POSTED ON EVERY |
| | GUEST ROOM DOOR IN ACCORDANCE WITH NFPA 101, SEC. |
| | 28.7.4. |
| | |
| | 49) PLEASE PROVIDE THE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS |
| | A,B OR C. |
| | |
| | 50) PLANS STATE THAT ROOF ACCESS IS FOR MAINTENANCE |
| | PURPOSES ONLY. THIS WOULD APPEAR TO BE IN CONFLICT WITH |
| | THE POOL THAT IS LOCATED AT THE ROOF LEVEL. |
| | |
| | 51) THE DOORS ON STAIR ENCLOSURES SHALL COMPLY WITH |
| | NFPA 101, SEC. 7.2.1.5.7.1. (1) - (5) |
| | |
| | |
| | MIKE WENNERGREN, ASST. FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |