Plan Review Notes
Plan Review Notes For Permit 09010006
Permit Number 09010006
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-03-02 16:18:08***DENIED***
  
 PLEASE NOTE THAT PLANS HAVE BEEN SUBMITTED FOR PLAN
 REVIEW ONLY. EVEN AFTER THE PLANS HAVE PASSED AND ARE
 CODE COMPLIANT, THEY WILL REMAIN IN FAILED STATUS UNTIL
 THE PLANS HAVE BEEN REVIEWED AND APPROVED FOR PERMIT
 APPLICATION.
  
 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2007 WHICH INCLUDES NFPA 101, 2006 AND
 NFPA 1, 2006 AS OF DECEMBER 31, 2008.
  
 2) A TEMPORARY STANDPIPE IS REQUIRED WHEN THE BUILDING
 REACHES THREE (3) STORIES OR THIRTY (30) FEET IN
 HEIGHT.
  
 3) PLEASE ADD FIRE SPRINKLER 2002 EDITION TO THE
 BUILDING CODE ANALYSIS, LIFE SAFETY SYSTEMS ON SHEET
 LS-1.
  
 4) THERE APPEARS TO BE CONFLICTING INFORMATION
 REGARDING THE NUMBER OF STORIES ON THE COVER SHEET AND
 THE LIFE SAFETY SHEETS. PLEASE CORRELATE THE
 INFORMATION ON ALL SUBMITTED SHEETS FOR REVIEW.
  
 5) TRAVEL DISTANCE TO THE NEAREST EXIT SHALL NOT EXCEED
 200' IN ACCORDANCE WITH 101, SEC. 28.2.6.3.3.1 FOR
 STRUCTURES PROTECTED THROUGHOUT WITH AN AUTOMATIC FIRE
 SPRINKLER SYSTEM. CODE ANALYSIS EXIT REQUIREMENTS
  
 6) THIS PROJECT SHALL COMPLY WITH THE REQUIREMENTS OF
 101, SEC. 11.8 FOR HIGHRISE STRUCTURES.
  
 7) TACTILE SIGNAGE IS REQUIRED FOR EXIT STAIRS
 INDICATING THE FLOOR LEVEL, STAIR IDENTIFICATION, AND
 TERMINUS OF THE TOP AND BOTTOM OF THE STAIR ENCLOSURE.
  
 8) PLEASE SUBMIT FIRE PROTECTION DRAWINGS ILLUSTRATING
 THE FIRE SPRINKLER HEAD LAYOUT. IN ADDITON, SEPARATE
 SHOP DRAWINGS AND PERMIT ARE REQUIRED PRIOR TO
 EQUIPMENT INSTALLATION.
  
 9) PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION AND
 DETAILS OF THE DOUBLE CHECK DETECTOR ASSEMBLY THAT IN
 ADDITION TO ELECTRONIC SUPERVISION, SHALL BE SECURED
 WITH A CHAIN AND LOCK.
  
 10) SOME FIRE ALARM EQUIPMENT IS SHOWN ON THE E-
 SHEETS. PLEASE SUBMIT CLEAR DRAWINGS SHOWING ALL FIRE
 ALARM DEVICES AND ASSOCIATED EQUIPMENT. IN ADDITION,
 SEPARATE SHOP DRAWINGS AND PERMIT ARE REQUIRED PRIOR TO
 EQUIPMENT INSTALLATION.
  
 11) FIRE ALARM TO BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE WITH PROOF OF CERTIFICATION REQUIRED AT
 OR BEFORE THE FINAL INSPECTION.
  
 12) FIRE ALARM SYSTEM TO COMPLY WITH THE HIGHRISE
 REQUIREMENTS FOR SURVIVABILITY IN ACCORDANCE WITH NFPA
 72, 2002.
  
 13) HANDRAILS ARE REQUIRED ON BOTH SIDES OF STAIRS.
  
 14) PROVIDE THE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDRAILS.
  
 15) A MINIMUM OF TWO (2) FIRE DEPARTMENT CONNECTIONS
 ARE REQUIRED ON HIGHRISE STRUCTURES THAT ARE LOCATED AT
 REMOTE LOCATIONS FROM ONE ANOTHER. FDC'S TO BE
 IDENTIFIED BY APPROVED SIGNAGE.
  
 16) PROVIDE A SITE PLAN SHOWING ALL PERTINENT FIRE
 PROTECTION EQUIPMENT SUCH AS FDC LOCATIONS, DOUBLE
 CHECK DETECTOR ASSEMBLY LOCATION WITH DETAILS, FIRE
 HYDRANTS ETC. SHOW COMPLIANCE WITH NFPA 1, CHAPTER-18
 FOR EMERGENCY VEHICLE ACCESS AND WATER SUPPLY.
  
 17) CUTTING AND WELDING OPERATIONS ARE PROHIBITED WITH
 PRIOR APPROVAL FROM THE BUREAU OF FIRE PREVENTION. WORK
 TO COMPLY WITH THE REQUIREMENTS OF NFPA 51B. CONTACT
 FIRE PREVENTION AT (561) 804-4724.
  
 18) IDENTIFY THE EQUIPMENT SHOWN IN STAIR #1 ON THE
 NORTH WALL. PLEASE ILLUSTRATE STANDPIPE LOCATIONS AND
 CONNECTIONS.
  
 19) PERMANENT STANDPIPES SHALL BE PROVIDED WITH 2 1/2"-
 1 1/2" CONNECTIONS WITH CAPS AND CHAINS.
  
 20) FIRE SPRINKLER PROTECTION TO BE EXTENDED TO THE
 LINEN CHUTE. SHOW FIRE SPRINKLER DETAIL.
  
 21) EXIT SIGNS TO BE PROVIDED AT LOCATIONS NOT TO
 EXCEED 100' DISTANCES BETWEEN SIGNS. PLEASE SHOW
 COMPLIANCE WITH EXIT SIGNS IN ALL CORRIDORS.
  
 22) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS TO BE
 PLACED AT LOCATIONS NOT TO EXCEED THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 23) IN ADDITION TO ALL AREAS OF MEANS OF EGRESS, THE
 POOL WALKING SURFACES SHALL BE SLIP RESISTANT.
  
 24) ALL APPLICABLE ENCLOSED ROOFTOP STRUCTURES SHALL BE
 PROTECTED BY AUTOMATIC FIRE SPRINKLER COVERAGE.
  
 25) PLEASE SHOW ALL ROOFTOP FIRE PROTECTION EQUIPMENT
 TO INCLUDE FIRE SPRINKLER, STANDPIPE CONNECTION AND
 FIRE ALARM EQUIPMENT.
  
 26) THE BUILDING ADDRESS APPEARS TO BE DISPLAYED ON THE
 EAST AND WEST SIDES OF THE STRUCTURE. AN APPROVED
 ADDRESS IS REQUIRED AT THE AREA OF THE FRONT ENTRANCE
 TO THE BUILDING, AND SHALL COMPLY WITH THE CITY OF WEST
 PALM BEACH SIZE AND CONTRASTING REQUIREMENTS FOR
 COMMERCIAL BUILDINGS. THE ADDRESS SHALL BE CLEAR AND
 VISIBLE FROM THE CENTER LINE OF THE MAIN STREET OF
 APPROACH. SHEETS A-12.0 AND A-13.0
  
 27) PROVIDE FLAME RETARDANT INFORMATION FOR BUILDING
 AND ROOFTOP AWNINGS.
  
 28) NEW FIRE DEPARTMENT CONNECTIONS TO BE PROVIDED WITH
 KNOX LOCKING CAPS.
  
 29) PROVIDE DETAILS AND MANUFACTURER SPECIFICATION
 INFORMATION FOR THE FIRE PUMP.
  
 30) PROVIDE DETAILS AND MANUFACTURER SPECIFICATION
 INFORMATION FOR THE GENERATOR AND ALL SUPPORTING
 EQUIPMENT AND FUEL TANK.
  
 31) PROVIDE A CLEAR DETAIL AND EXPLANATION REGARDING
 EXITING FROM STAIR #2 ON THE NORTH SIDE OF THE
 STRUCTURE. IS IT THE INTENT TO EXIT PERSONS DIRECTLY TO
 THE BUILDING EXTERIOR?
  
 32) KNOX BOXES TO BE PROVIDED FOR AFTER NORMAL BUSINESS
 HOURS EMERGENCY ACCESS TO THE BUILDING. CONTACT THE
 BUREAU OF FIRE PREVENTION AT (561) 804-4724 FOR
 ASSISTANCE.
  
 33) DURING IT'S SWING, ANY DOOR IN A MEANS OF EGRESS
 SHALL LEAVE NOT LESS THAN 1/2 OF THE REQUIRED WIDTH OF
 AN AISLE, CORRIDOR, PASSAGEWAY OR LANDING UNOBSTRUCTED.
 101, SEC. 7.2.1.4.4
  
 34) THE FIRE COMMAND ROOM TO COMPLY WITH THE
 REQUIREMENTS OF 101, SEC. 11.8.5 AND SHALL BE
 IDENTIFIED BY APPROVED SIGNAGE. PROVIDE DETAILS FOR ALL
 APPLICABLE EQUIPMENT INCLUDING SMOKE MANAGEMENT PANEL
 AND ALL OTHER EQUIPMENT REQUIRED AS PER 101, SEC.
 11.8.5.
  
 35) THE DESIGN OF THIS PROJECT SUGGESTS AN ATRIUM BY
 DEFINITION. PLANS DO NOT APPEAR TO INDICATE ANY TYPE OF
 SMOKE MANAGEMENT SYSTEM. PLEASE PROVIDE NECESSARY
 INFORMATION AND DETAILS.
  
 36) PROVIDE PLANS AND DETAILS DESCRIBING REQUIRED
 STAIRWELL PRESSURIZATION SYSTEM.
  
 37) FIRE DAMPERS ARE SHOWN PASSING THROUGH STAIR #2.
 PLEASE REFER TO 101, SEC. 7.1.3.2 (6) AND (7). NO
 PENETRATIONS ALLOWED IN EXIT ENCLOSURES THAT DO NOT
 MEET THE DEFINITION/EXCEPTIONS OF THAT SECTION OF THE
 LIFE SAFETY CODE.
  
 38) THE FIRE PUMP IS IDENTIFIED AS 151 ON SHEET A-39.0
 AND AS MECHANICAL 150 ON DETAILED PLAN.
  
 39) THE DOOR SCHEDULE INDICATES CARD READERS. SEPARATE
 SHOP DRAWINGS AND PERMIT REQUIRED PRIOR TO EQUIPMENT
 INSTALLATION. ALL ASSOCIATED WORK TO COMPLY WITH 101,
 SEC. 7.2.1.6.2 FOR ACCESS CONTROLLED EGRESS DOORS.
  
 40) ALL FIRE RATED DOORS TO BE PROVIDED WITH UL LISTED
 CLOSERS THAT CAUSE THE DOOR TO POSITIVELY LATCH. ADD
 NOTE TO THE DOOR SCHEDULE.
  
 41) THE DOORS TO THE LINEN CHUTE SHALL POSITIVELY LATCH
 UPON CLOSING.
  
 42 ELEVATOR LOBBIES SHALL BE PROVIDED WITH WARNING
 SIGNS IN CASE OF AN EMERGENCY.
  
 43) FIRE/SMOKE DAMPERS TO BE TESTED FOR CLOSURE IN
 ACCORDANCE WITH THE REQUIREMENTS OF UL 555 PRIOR TO
 FINAL INSPECTION.
  
 44) DUCT SMOKE DETECTORS SHALL IN ADDITION TO FAN SHUT
 DOWN, INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 45) PLEASE CLARIFY IF THIS PROJECT MEETS THE DEFINITION
 OF A COMPLETE OR PARTIAL SMOKE DETECTION SYSTEM IN
 ACCORDANCE WITH NFPA 72, 2002.
  
 46) HOW WILL THE SUITE SMOKE ALARMS FUNCTION WITH
 REGARD TO THE BUILDING FIRE ALARM SYSTEM?
  
 47) PLEASE NOTE THAT SOME OF THE THE ELECTRICAL SHEETS
 ARE DIFFICULT TO READ TO REFERENCE THE LOCATION OF LIFE
 SAFETY EQUIPMENT. SHT E-2.0 AND E-2.1
  
 48) EMERGENCY INSTRUCTIONS SHALL BE POSTED ON EVERY
 GUEST ROOM DOOR IN ACCORDANCE WITH NFPA 101, SEC.
 28.7.4.
  
 49) PLEASE PROVIDE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A,B OR C.
  
 50) PLANS STATE THAT ROOF ACCESS IS FOR MAINTENANCE
 PURPOSES ONLY. THIS WOULD APPEAR TO BE IN CONFLICT WITH
 THE POOL THAT IS LOCATED AT THE ROOF LEVEL.
  
 51) THE DOORS ON STAIR ENCLOSURES SHALL COMPLY WITH
 NFPA 101, SEC. 7.2.1.5.7.1. (1) - (5)
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW