| 2009-02-06 08:12:38 | |
| | |
| | |
| | *** DENIED REVIEW ** |
| | |
| | |
| | ** IMPORTANT: |
| | IT IS VERY IMPORTANT TO UNDERSTAND THE REVIEW IS BASED |
| | ON THE PLANS SUBMITTED AT THIS TIME. AS THERE IS MANY |
| | ITEMS NOT YET COMPLETED OR SUBMITTED FOR REVIEW A |
| | COMPLETE REVIEW OF CODE COMPLIANCE DETERMINATION CAN |
| | NOT BE DONE AT THIS TIME. THERE MAY CERTAINLY BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW DUE TO CHANGES IN |
| | PLANS, SUBMITTED DOCUMENTS ETC WHICH IS NOT POSSIBLE TO |
| | BE MADE AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLANS HAVE BEEN SUBMITTED FOR * PLAN REVIEW* |
| | ONLY AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE |
| | KNOW ONCE PERMIT APPLICATION IS MADE ITEMS SUCH AS |
| | LICENSING OF CONTRACTOR, AND OTHER DESIGN PROFESSIONALS |
| | WILL ALL BE VERIFIED AT THAT TIME. PLAN REVIEW DOES NOT |
| | *LOCK* A PROJECT IN UNDER THE CODE IN EFFECT AT THE |
| | TIME OF THE REVIEW. ONLY PLANS SUBMITTED FOR PERMIT |
| | APPLICATION WITH LICENSED CONTRACTOR. THIS IS GIVEN FOR |
| | INFORMATION ONLY AS THE FLORIDA BUILDING CODE IS SET TO |
| | CHANGE ON MARCH 1ST, 2009. |
| | EVEN ONCE ALL ITEMS NOTED FOR CODE COMPLIANCE ARE |
| | ADDRESSED AND PERMIT APPLICATION HAS NOT BEEN MADE THE |
| | REVIEW STATUS WILL STILL REMAIN FAILED. |
| | |
| | 2) NOTE: PLANS NEED TO BE COMPLETE IN ORDER TO RECEIVE |
| | A COMPLETE REVIEW FOR CODE COMPLIANCE. AS THERE ARE |
| | SEVERAL ITEMS ON THE PLANS MISSING IT IS VERY POSSIBLE |
| | THERE WILL BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| | WHICH CAN NOT BE MADE AT THIS TIME. |
| | PLEASE BE SURE PLANS ARE PRINTED CLEARLY. THERE ARE |
| | SEVERAL SHEETS IN WHICH THE PRINT IS VERY FAINT AND NOT |
| | READABLE. THERE ARE SOME LOCATIONS IN WHICH WALLS ARE |
| | MISSING OR THERE IS SOME SORT OF SHIFT IN THE PLANS. |
| | PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON PLANS. |
| | PLEASE COMPLETE ALL LOAD CALCULATIONS. NEC 220 |
| | PLEASE SEE FBC 106.1.1, 106.1.2 FOR CLARITY, |
| | COORDINATION AND ADDITIONAL INFORMATION. IT IS |
| | RECOMMENDED TO TAKE A LOOK AT THE CONSTRUCTION SERVICES |
| | DEPARTMENT WEBSITE WHICH CONTAINS A LIST OF SEVERAL |
| | ITEMS FOR MOST COMMON FAILURE ITEMS. |
| | PLEASE ALSO SEE FBC 106.1.3 FOR QUALITY OF PLANS BEING |
| | SUBMITTED. |
| | |
| | 3) NOTE: THE CODES FOR THIS REVIEWER NEED TO BE STATED |
| | ON PLANS AS FOLLOWS. THERE IS NO COVER SHEET, NO PAGE |
| | IDENTIFICATION PAGE ETC |
| | THE FOLLOWING CODES ARE THE CURRENT CODES IN EFFECT. |
| | THERE ARE SEVERAL OF THESE WHICH WILL BE REVISED COME |
| | MARCH 1ST, 2009. THIS WILL AFFECT REVIEW AND DESIGN. |
| | CURRENT CODES ARE: |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 (NATIONAL ELECTRICAL CODE) |
| | 2006 NFPA-101 (LIFE SAFETY CODE) |
| | 2002 NFPA-72 (NATIONAL FIRE ALARM CODE) |
| | 2003 NFPA-20 ( STANDARD FOR STATIONARY FIRE PUMP) |
| | PLEASE ALSO BE SURE THE FP SHEETS CONTAIN THE REFERENCE |
| | TO NFPA-20 2003. |
| | |
| | ** THESE ARE NOTED FOR THIS REVIEWER. THERE MAY BE |
| | OTHERS NOTED BY OTHER TRADES. |
| | PLEASE SEE SOME NOTES BELOW AS THERE ARE SOME CODE |
| | REFERENCES TO CODES WHICH ARE NO LONGER ADOPTED IN THE |
| | STATE OF FLORIDA. |
| | |
| | 4) NOTE: PLANS ARE NOT SIGNED, DATED OR SEALED. FS 481, |
| | 471, FAC 61G15-23.002, .001 ETC |
| | AS PLANS WERE ONLY SUBMITTED FOR PARTIAL PLAN REVIEW IT |
| | IS UNDERSTOOD WHY THEY WERE NOT SIGNED AND SEALED. |
| | |
| | 5) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| | EGRESS PATHS. SOME WERE SUBMITTED AND SHOWN FOR GARAGE |
| | AREAS HOWEVER THESE ARE NOT ALL EGRESS PATHS. PLEASE BE |
| | SURE TO SEE NFPA-101 7.8.1.3, 7.9.1.2, 7.9.2.2, FBC |
| | 1006.2.1, .2.3. ALL EGRESS STAIRS SHALL CONTAIN A |
| | MINIMUM OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED |
| | TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. |
| | THIS IS BASED ON AN AVERAGE PER FORMULA STATED IN THE |
| | LIFE SAFETY CODE. |
| | ** IMPORTANT** |
| | IF THIS BUILDING IS GOING TO REMAIN OCCUPIED UNDER |
| | EMERGENCY POWER DURING OR AFTER AN EVEN SUCH AS A |
| | HURRICANE OR OTHER TIME WHEN NORMAL POWER IS LOST THE |
| | BUILDING SHALL CONTAIN BATTERY BACK UP LIGHTING IN ALL |
| | EGRESS PATHS TO MEET THE 1FT CANDLE AVERAGE. THE LIFE |
| | SAFETY CODE AS WELL AS CHAPTER 10 OF THE FLORIDA |
| | BUILDING CODE ADDRESSES THE REQUIRED EGRESS LIGHTING TO |
| | EXIT *ALL* OCCUPANTS OUT OF THE BUILDING IN EMERGENCY |
| | EVENT OR LOSS OF NORMAL POWER. |
| | WHEN A BUILDING IS OCCUPIED UNDER EMERGENCY POWER THE |
| | BACK UP SYSTEM OF THE PREVIOUS NORMAL POWER HAS NOW |
| | BECOME THE NORMAL POWER. A LOSS OF ONE BREAKER SUCH AS |
| | THE GENERATOR MAIN OR THE GENERATOR ITSELF GOING DOWN |
| | WOULD REMOVE ALL LIFE SAFETY BACK UP FOR LIGHTING AND |
| | EGRESS PATHS. |
| | PLEASE CALL TO GO OVER OTHER OPTIONS WHICH WOULD |
| | REQUIRE A LETTER THE OWNER WHICH WOULD BE REQUIRED TO |
| | EVACUATE ALL OCCUPANTS WHEN THE BUILDING GOES INTO |
| | EMERGENCY POWER BACK UP. THE WORDING TO THAT AFFECT |
| | WOULD BE GONE OVER AT A LATER DATE IF THAT IS THE |
| | OPTION. |
| | BASED ON THE PLANS SUBMITTED OTHER LOCATIONS WHICH WILL |
| | REQUIRE BATTERY BACK UP LIGHTING FIXTURES OF SOME TYPE |
| | WHETHER OR NOT BUILDING REMAINS OCCUPIED WILL BE THE |
| | STAIRS, EMERGENCY GENERATOR ROOM, FIRE PUMP ROOM, MAIN |
| | ELECTRICAL ROOM, ELEVATOR EQUIPMENT ROOMS AND FIRE |
| | COMMAND ROOM AND OTHER POSSIBLE LOCATIONS AS NOT ALL |
| | ARE COMPLETE. THERE ARE AREAS OF THE PLANS WHICH DO NOT |
| | MEET THE WIRING REQUIREMENTS AND ARE ALSO REQUIRED TO |
| | CONTAIN BATTERY BACK UP FIXTURE FOR EGRESS LIGHTING. |
| | PLEASE SEE SECTIONS ABOVE AS WELL AS 700.12F, 700.16 |
| | ETC. |
| | ALL STAIRS BASED ON WIRING AS SHOWN ARE REQUIRED TO BE |
| | BATTERY BACK UP. |
| | BATTERY BACK UP LIGHTING SHALL BE INSTALLED. THE |
| | GENERATOR MAY NOT BE USED AS THE SOLE BACK UP FOR |
| | EGRESS LIGHTING. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| | FROM THE LIFE SAFETY CODE. 7.9.2.2. |
| | PLEASE ALSO SEE 7.8.2.1 AS THE SOURCE SHALL BE |
| | ACCEPTABLE TO THE AHJ. |
| | |
| | THE EMERGENCY LIGHTING SYSTEM SHALL BE ARRANGED TO |
| | PROVIDE THE REQUIRED ILLUMINATION AUTOMATICALLY IN THE |
| | EVENT OF ANY INTERRUPTION OF NORMAL LIGHTING DUE TO ANY |
| | OF THE FOLLOWING: |
| | (1) FAILURE OF A PUBLIC UTILITY OR OTHER OUTSIDE |
| | ELECTRICAL POWER SUPPLY |
| | (2) OPENING OF A CIRCUIT BREAKER OR FUSE |
| | (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A |
| | SWITCH CONTROLLING NORMAL LIGHTING FACILITIES |
| | |
| | |
| | |
| | 6) NOTE: LOCATIONS SUCH AS THE FIRE COMMAND ROOM AND |
| | THE EMERGENCY GENERATOR ROOM WOULD REQUIRE SUCH |
| | SIGNAGE. ALL OF THESE ROOMS ARE ALSO REQUIRED TO |
| | CONTAIN PERMANENT MAPPING CONTAINING A LAYOUT OF THE |
| | BUILDING SHOWING THE LOCATIONS OF EACH OF THESE ROOMS |
| | CLEARLY IDENTIFIED. THIS WOULD BE REQUIRED IN ALL ROOMS |
| | NOTING EACH OF THE OTHERS. THIS COMMENT MAY BE ADDRESS |
| | BY NOTES ON PLANS. THIS WILL ONE OF THE REQUIRED ITEMS |
| | BY THE CONTRACTOR TO HAVE ALL SIGNAGE UP FOR ALL MAINS, |
| | ELECTRICAL SERVICES, FIRE PUMPS, FIRE COMMAND ROOM ETC |
| | BEFORE ANY RELEASE OF POWER. THIS IS NOT THE ONLY |
| | REQUIREMENT OTHERS WILL BE DIRECTED AT A LATER DATE BY |
| | THE INSPECTION STAFF. |
| | 230.2E, 700.8,701.9, ETC |
| | |
| | 7) NOTE: PLEASE BE SURE TO LIST ALL OF THE FOLLOWING |
| | ITEMS REQUIRED TO BE LOCATED IN THE FIRE COMMAND ROOM. |
| | NFPA-101 11.8.5 THESE ARE SYSTEMS AT A MINIMUM. PLEASE |
| | SEE NOTES FORM OTHER TRADES SUCH AS THE FIRE MARSHAL |
| | WHICH MAY ALSO NOTE OTHER ITEMS. |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER |
| | SECTION OF THIS CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) SPRINKLER VALVE AND WATER-FLOW ANNUNCIATORS |
| | (6) EMERGENCY GENERATOR STATUS INDICATORS |
| | (7) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | |
| | 8) NOTE: PLEASE BE SURE THE ELEVATION OF ALL EMERGENCY |
| | ELECTRICAL SYSTEMS SUCH AS THE GENERATOR, EQUIPMENT, |
| | FIRE PUMP ETC IS LISTED ON PLANS. THE ELEVATIONS ARE |
| | REQUIRED TO MEET ONE OF THE FOLLOWING; EITHER THE 100 |
| | YEAR STORM ELEVATION OR THE ELEVATION SET FORTH BY THE |
| | SLOSH (SEA, LAKE, OVERLAND SURGES BY HURRICANES) CHARTS |
| | BASED ON A CATEGORY 4 HURRICANE. |
| | PLEASE SEE NFPA-110 CHAPTER 7.2.3 |
| | |
| | 9) NOTE: AS NOTED ABOVE FOR COMPLETE PHOTO-METRICS FOR |
| | EGRESS. PLEASE ALSO INCLUDE THE LIGHTING LEVELS IN THE |
| | EMERGENCY GENERATOR ROOM. PLEASE SEE NFPA-110 7.3.3. |
| | THE LIGHTING LEVELS IN THIS ROOM SHALL BE AT A MINIMUM |
| | OF 30FT CANDLES. |
| | |
| | 10) NOTE: PLEASE ALSO INCLUDE THE LIGHTING LEVELS FOR |
| | ELEVATOR PITS TO MEET THE MINIMUM OF 5FT CANDLES. |
| | PLEASE SEE NEC 620.23 WHICH CONTAINS REFERENCE TO |
| | MINIMUM REQUIREMENTS. SEE HANDBOOK COMMENTARY; ASME |
| | A17.1-2004, SAFETY CODE FOR ELEVATORS AND ESCALATORS, |
| | REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) AT THE PIT |
| | FLOOR AND REQUIRES LUMINAIRES TO BE EXTERNALLY GUARDED |
| | TO PREVENT ACCIDENTAL BREAKAGE. |
| | |
| | |
| | 11) NOTE: PLEASE SUBMIT MORE INFORMATION ON ALL |
| | PROPOSED LIGHTING CONTROL SYSTEMS. SEE NOTES WITH |
| | RESPECT TO FBC EXISTING BUILDING CODE WITH RESPECT TO |
| | HISTORIC BUILDINGS AND REQUIREMENTS PER THE BUILDING |
| | CODE. |
| | SEE CHAPTER 13, 13-415.1.ABC.1 ETC. |
| | AS PLANS ARE NOT COMPLETE WITH INFORMATION, ACTUAL |
| | DESIGN AND SEVERAL OTHER ASPECTS BEING INCOMPLETE IT IS |
| | VERY DIFFICULT TO GIVE MANY TECHNICAL CODE SECTIONS. |
| | |
| | 12) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE FOLLOWING ITEMS. |
| | THE GENERATOR. |
| | FIRE PUMP. |
| | FIRE PUMP CONTROLLER. |
| | ATS (AUTOMATIC TRANSFER SWITCH). |
| | FUEL TANK. THE FUEL TANK WILL BE REVIEWED BY OTHERS) |
| | |
| | MINIMUM EQUIPMENT MEETING THE CODE AT THIS TIME MUST BE |
| | VERIFIED. EVEN IF THE EQUIPMENT IS NOT FINAL EQUIPMENT |
| | WILL NEED TO BE CHOSEN AT THIS TIME MEETING MINIMUM |
| | PERMITTED BY CODE. THE MANUFACTURE OR BRAND OF |
| | EQUIPMENT MAY ALWAYS BE CHANGED AT A LATE DATE. |
| | 90.7,110.3, NFPA_20, NFPA-101, NFPA-70, NFPA-110. |
| | FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | 13) NOTE: PLEASE PROVIDE ALL SHUT DOWN OF ALL EQUIPMENT |
| | IN IT ROOM INCLUDING A/C UNIT. THE PLANS DO NOT SHOW |
| | ANY EPO (EMERGENCY POWER OFF) BUTTON AS REQUIRED PER |
| | 645.10. THE PLANS IDENTIFY LOCATIONS AS *IT ROOMS* |
| | HOWEVER BASED ON PLANS NOT BEING COMPLETE THERE ARE |
| | SEVERAL UNANSWERED QUESTIONS. PLEASE SEE 645.10 FOR |
| | DISCONNECTING REQUIREMENTS. |
| | PLEASE SEE NEC 645.4 REQUIREMENTS OF AN IT ROOM. WHEN |
| | ANY PROPOSED ROOM DOES MEETS ALL ITEMS LISTED PER 645.4 |
| | THE WIRING METHODS WHICH ARE LESS STRINGENT IN THIS |
| | CODE SECTION MAY NOT BE USED. |
| | PLEASE MEET ALL OF 645.4 OR PLEASE CHANGE DESIGNATION |
| | AND PROVIDE NOTE FOR WIRING METHODS OF CHAPTERS 1-4 |
| | MUST BE USED. IT MAY BE HELPFUL TO CONTACT IT PERSONNEL |
| | FOR MARRIOTT OR OWNER TO CONFIRM WIRING METHODS TO BE |
| | USED. |
| | THE FOLLOWING IS EXTRACTED FROM THE NEC FOR EASE OF |
| | CODE SECTIONS: |
| | |
| | |
| | THIS ARTICLE SHALL APPLY, PROVIDED ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) DISCONNECTING MEANS COMPLYING WITH 645.10 ARE |
| | PROVIDED. |
| | (2) A SEPARATE HEATING/VENTILATING/AIR-CONDITIONING |
| | (HVAC) SYSTEM IS PROVIDED THAT IS DEDICATED FOR |
| | INFORMATION TECHNOLOGY EQUIPMENT USE AND IS SEPARATED |
| | FROM OTHER AREAS OF OCCUPANCY. ANY HVAC SYSTEM THAT |
| | SERVES OTHER OCCUPANCIES SHALL BE PERMITTED TO ALSO |
| | SERVE THE INFORMATION TECHNOLOGY EQUIPMENT ROOM IF |
| | FIRE/SMOKE DAMPERS ARE PROVIDED AT THE POINT OF |
| | PENETRATION OF THE ROOM BOUNDARY. SUCH DAMPERS SHALL |
| | OPERATE ON ACTIVATION OF SMOKE DETECTORS AND ALSO BY |
| | OPERATION OF THE DISCONNECTING MEANS REQUIRED BY |
| | 645.10. |
| | FPN: FOR FURTHER INFORMATION, SEE NFPA 75-2003, |
| | STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY |
| | EQUIPMENT, CHAPTER 10, 10.1, 10.1.1, 10.1.2, AND |
| | 10.1.3. |
| | (3) LISTED INFORMATION TECHNOLOGY EQUIPMENT IS |
| | INSTALLED. |
| | (4) THE ROOM IS OCCUPIED ONLY BY THOSE PERSONNEL NEEDED |
| | FOR THE MAINTENANCE AND FUNCTIONAL OPERATION OF THE |
| | INSTALLED INFORMATION TECHNOLOGY EQUIPMENT. |
| | (5) THE ROOM IS SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTANT-RATED WALLS, FLOORS, AND CEILINGS WITH |
| | PROTECTED OPENINGS. |
| | FPN: FOR FURTHER INFORMATION ON ROOM CONSTRUCTION |
| | REQUIREMENTS, SEE NFPA 75-2003, STANDARD FOR THE |
| | PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT, CHAPTER |
| | 5. |
| | |
| | ALL ITEMS ABOVE WITH THE EXCEPTION OF # 1 ABOVE ARE |
| | SHOWN ON PLANS. |
| | |
| | 14) NOTE: PLEASE PLACE NOTES ON PLANS FOR SIGNAGE |
| | REQUIRED FOR ARC FLASH OF ALL EQUIPMENT MEETING 110.16 |
| | |
| | 15) NOTE: PLEASE SEE FBC 3006.2 FOR REQUIRED |
| | CONDITIONING/VENTILATION OF ELEVATOR EQUIPMENT ROOMS. |
| | THE ELECTRICAL PLANS DO SHOW ELECTRICAL FOR ELEVATOR |
| | EQUIPMENT. |
| | |
| | 16) NOTE: PLEASE SEE 620.23 AS NOTED ABOVE FOR ELEVATOR |
| | PIT AREAS FOR LIGHTING LEVELS. THIS SAME SECTION |
| | REQUIRES THE LIGHTING AS WELL AS RECEPTACLES IN THESE |
| | EQUIPMENT ROOMS TO BE ON DEDICATED CIRCUITS. AS PLANS |
| | ARE NOT COMPLETE WITH CIRCUITING NO REVIEW WITH |
| | NUMEROUS SECTIONS OF 620 CAN NOT BE DONE. |
| | |
| | 17) NOTE: PLEASE OBTAIN PHOTO-METRIC LEVELS FOR |
| | SWIMMING POOL AREA FOR ANY NIGHT TIME SWIMMING PER PALM |
| | BEACH COUNTY HEALTH DEPARTMENT. ALL PHOTO-METRICS FOR |
| | ANY SWIMMING AFTER DUSK OR BEFORE DAWN SHALL BE STAMPED |
| | BY THE HEALTH DEPARTMENT. |
| | THIS IS NOT A CITY OF WEST PALM BEACH ADOPTED LEVEL OF |
| | LIGHTING HOWEVER UNLESS PLANS ARE STAMPED PERMIT MAY |
| | NOT BE ISSUED. PLEASE ALSO KEEP IN MIND IF THERE IS NOT |
| | GOING TO BE ANY SWIMMING OUTSIDE OF THE DAYLIGHTS HOURS |
| | PER THE HEALTH DEPARTMENT PLEASE PLACE NOTES ON PLANS |
| | ACCORDINGLY. |
| | |
| | 18) NOTE: ANY PROPOSED LIGHTNING PROTECTION SYSTEM IS |
| | GOING TO BE REQUIRED TO BE UNDER SEPARATE PERMIT. |
| | HOWEVER PLEASE PLACE NOTES ON PLANS THAT ANY PROPOSED |
| | LIGHTNING PROTECTION SYSTEM SHALL MEET NFPA-780. (OR |
| | WORDS TO THAT AFFECT). |
| | THERE ARE MANY SYSTEMS ON THE MARKET WHICH DO NOT MEET |
| | ANY ACCEPTABLE STANDARD AND ARE NOT LISTED TO MEET |
| | NFPA-780. |
| | |
| | 19) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS |
| | PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE |
| | SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE |
| | LIFE SAFETY PLANS. |
| | * TO THE BEST OF THE ARCHITECT???S OR ENGINEER???S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633, FLORIDA STATUTES* |
| | |
| | 20) NOTE: PLEASE SEE FA PLANS. PLEASE SEE CHAPTER 11 OF |
| | THE FBC. PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR |
| | REFERENCES AND PLEASE BE SURE TO REFLECT THESE CODES. |
| | |
| | 21) NOTE: PLEASE PROVIDE INFORMATION ON FUEL |
| | CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP |
| | AND ALL EMERGENCY SYSTEMS PER 700 AND 701. |
| | PLEASE BE SURE TO INCLUDE 5% FOR SUMP AND 5% FOR |
| | EXPANSION. |
| | PLEASE SEE NFPA-110, NFPA-20 9.6.2.2 |
| | |
| | 22) NOTE: WHEN COMPLETING PLANS PLEASE BE SURE TO LABEL |
| | ALL MAINS AND EQUIPMENT. 230.2E, 700.8, 701.9 ETC. |
| | |
| | 23) NOTE: NO INFORMATION FOR FIRE PUMP CONTROLLER AS |
| | SERVICE ENTRANCE RATED OR ANY OTHER INFORMATION AT THIS |
| | TIME. PLEASE SEE NEC 695,695.4 AND NFPA-20. PLEASE SEE |
| | NOTES ABOVE AND EXPANDED ON THE FIRE PUMP CONTROLLER |
| | INFORMATION. |
| | PLEASE BE SURE TO SEE NOTES ON TRANSFER SWITCHES. |
| | |
| | 24) NOTE: PLEASE SEE 230.95,240.13 ETC. THE CODE |
| | REQUIRES GROUND FAULT PROTECTION FOR ANY SYSTEMS 150V |
| | OR MORE TO GROUND AND 1000AMPS OR OVER. THE RISER |
| | INDICATES GFI PROTECTION WHICH IS CLASS A PROTECTION |
| | FOR PERSONNEL. THIS IS NOT THE SAME KING OF PROTECTION |
| | WHICH IS GFP WHICH IS WHAT IS REQUIRED IN THE SECTIONS |
| | GIVEN. PLEASE PROVIDE INFORMATION ON THE TRANSFER |
| | SWITCHES AND PLEASE SEE THE FOLLOWING COMMENT WHICH MAY |
| | AFFECT THE USE OF 3-POLE OR 4-POLE TRANSFER SWITCHES. |
| | |
| | 25) NOTE: PLEASE SEE NEC |
| | ,250.20,250.30,250.66,240.13.230.95, 700.7D AND 700.26. |
| | GFP PROTECTION IS REQUIRED ON THE NORMAL SIDE OF THE |
| | SERVICE HOWEVER ONLY GROUND FAULT SENSING IS REQUIRED |
| | TO BE ON THE SECONDARY SIDE. THE CODE ACTUALLY DOES NOT |
| | REQUIRE NOR DOES IT RECOMMEND GFP ON THE EMERGENCY |
| | EQUIPMENT. |
| | PLEASE SEVERAL WHITE PAPERS WHICH HAVE NOTES ON THE |
| | ABOVE SITUATION WHEN GROUND FAULT PROTECTION IS |
| | TRIGGERED BY THE CODE. MANY OF THESE IN FACT NOTE A |
| | COORDINATION LOSS OF EQUIPMENT WHEN THE USE OF 3-POLE |
| | ATS SWITCHES IS USED. |
| | PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL |
| | CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING |
| | CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND |
| | THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY |
| | GROUNDED TO ACHIEVE GROUND-FAULT SENSING. |
| | PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM *ASCO* |
| | WHITE PAPERS: |
| | |
| | WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE CODE |
| | AND AN ALTERNATE POWER SUPPLY IS INCLUDED, SWITCHING OF |
| | THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT SHOWN ABOVE |
| | ILLUSTRATES SUCH A CIRCUMSTANCE. THE SERVICE IS LARGER |
| | THAN 1,000 AMPS. CONSEQUENTLY, GROUND FAULT PROTECTION |
| | IS REQUIRED AT THE MAIN SERVICE DISCONNECT AT A |
| | MINIMUM. IF IT IS INSTALLED THERE AND THE GENERATOR |
| | NEUTRAL GROUNDING WAS THROUGH A SOLID CONNECTION TO THE |
| | MAIN SERVICE NEUTRAL, A GROUND FAULT WHEN THE GENERATOR |
| | IS FEEDING THE LOAD WILL CAUSE THE MAIN SERVICE |
| | DISCONNECT TO OPEN. THIS WILL NOT DISCONNECT THE ARCING |
| | FAULT FROM THE GENERATOR. COORDINATION IS THUS LOST." |
| | |
| | THIS HAS BEEN READ AND NOTED BY OTHER MANUFACTURES. |
| | PLEASE OBTAIN AND VERIFY COORDINATION FROM THE PROPOSED |
| | MANUFACTURE AND ADJUST PLANS. |
| | AS THE PLANS DO NOT INDICATE THE USE OF 3 OR 4 POLE |
| | DEVICES AT THIS TIME FINAL COMMENT CAN NOT BE MADE. |
| | PLEASE ALSO SEE GENERATOR GROUNDING DETAIL MAYBE BE |
| | REQUIRED TO BE REVISED. |
| | |
| | 26) NOTE: PLEASE SEE 700.9 OF THE NEC ALONG WITH |
| | EXHIBITS IN 700.1 ETC. |
| | *** IMPORTANT** |
| | PLEASE SEE NEC 700 AND 701 DEFINITIONS AND OTHER |
| | ADOPTED CODES AS NOT ALL SYSTEMS, FEEDERS, BRANCH |
| | CIRCUITS ETC ARE LIFE SAFETY/EMERGENCY SYSTEMS. SOME |
| | SHALL BE CONSIDERED LEGALLY REQUIRED. THIS WOULD |
| | REQUIRE SEPARATION. |
| | AN EXAMPLE IS THE ELEVATOR IS THIS OCCUPANCY IS |
| | CONSIDERED LEGALLY REQUIRE AND NOT LIFE SAFETY. THIS IS |
| | A BACK UP REQUIRED TO COME ON IN 60SECONDS INSTEAD OF |
| | THE REQUIRED 10 SECONDS LISTED IN 700 SYSTEMS. |
| | AN ELEVATOR IN A HOSPITAL WOULD BE DIFFERENT AND WOULD |
| | BE CONSIDERED LIFE SAFETY. |
| | THIS COMMENT WILL ALL TIE INTO THE COMMENTS ABOVE WITH |
| | RESPECT TO THE LIGHTING AND BACK UP OF THE EGRESS |
| | LIGHTS. |
| | PLEASE BE AWARE OF ANY PHONE SYSTEMS BEING PROPOSED |
| | WHICH WOULD BE REQUIRED TO CONTAIN UPS FOR BACK AS |
| | EMERGENCY COMMUNICATIONS IS REQUIRED TO CONTAIN BACK UP |
| | WHICH MAY THEN BE PART OF THE GENERATOR WHICH IS 10, 60 |
| | SECOND BACK UP. NO DELAY IN PHONE SYSTEM IS PERMITTED. |
| | |
| | 27) NOTE: PLEASE SUBMIT A COMPLETE COORDINATION STUDY |
| | FOR ALL LIFE SAFETY/EMERGENCY SERVICE EQUIPMENT AND |
| | BREAKERS. PLEASE SEE 240.12, 700.27 AND 701.18. THIS |
| | REQUIRES ALL BREAKERS AND EQUIPMENT TO BE COORDINATE. |
| | |
| | 28) NOTE: PLEASE PROVIDE NOTE FOR SUPPORT OF VERTICAL |
| | CONDUCTORS PER 300.19. |
| | |
| | 29) NOTE: PLEASE INDICATE AIC RATING FOR ALL SERVICE |
| | EQUIPMENT INCLUDING RATINGS OF ALL PANELS. 110.9. COULD |
| | NOT LOCATE ALL REQUIRED. |
| | |
| | 30) NOTE: EVEN AS THE SWIMMING POOL IS UNDER A SEPARATE |
| | PERMIT PLEASE SEE 2005 NEC WHICH REQUIRES AN EQUAL |
| | POTENTIAL BOND. |
| | PLEASE PROVIDE DETAIL ON PLANS AS THIS MAY BE PART OF |
| | THE STRUCTURAL ELEMENTS OF THE PROPOSED STRUCTURE AND |
| | POOL AREA. 680.26 |
| | |
| | 31) NOTE: PLEASE PROVIDE THROUGH WALL AND FLOORS |
| | PENETRATION DETAILS PER 300.21. THE SPREAD OF FIRE IS |
| | REQUIRED TO BE CONTAINED PER SEVERAL ADOPTED REFERENCES |
| | AND STANDARDS. |
| | PLEASE SEE THE HANDBOOK COMMENTARY WHICH PROVIDES THE |
| | REFERENCES SUCH AS NFPA-221,251, ASTM AND ANSI |
| | REQUIREMENTS. |
| | |
| | 32) NOTE: PLEASE COORDINATE ALL ITEMS ON RISER AND |
| | PANEL SCHEDULES. PLEASE SUBMIT COMPLETE PLANS FOR FULL |
| | REVIEW. THERE ARE SEVERAL ASPECTS OF RISER AND PANELS |
| | WHICH ARE NOT COMPLETED. NO CONDUCTORS, ETC ARE SHOWN. |
| | 310.16,215.5 ETC |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2 |
| | |
| | 33) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| | FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED |
| | THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES |
| | A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END |
| | DEVICE ON A CIRCUIT. THIS MAY GREATLY AFFECT FEEDERS OR |
| | BRANCH CIRCUIT CONDUCTORS. |
| | PLEASE SEE 13-413.1ABC.1. |
| | |
| | 34) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER |
| | 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN |
| | THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH FLORIDA |
| | BUILDING COMMISSION/DCA. |
| | |
| | 35) NOTE: PLEASE INCLUDE LOAD CALCULATIONS FOR ALL |
| | PANELS AND SERVICES. SOME INFORMATION IS SHOWN ON PLANS |
| | HOWEVER MOST IS NOT COMPLETE AT THIS TIME. |
| | PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%. |
| | 230.42,215.5. |
| | 220. |
| | PLEASE SEE SECTIONS SUCH AS 220.12,220.14,220.42, |
| | 220.44 AND OTHERS SUCH AS 220.43 FOR TRACK LIGHTING. |
| | THERE ARE SEVERAL ASPECTS OF THE LOAD CALCULATIONS AND |
| | HOW LOADS WERE DERIVED WHICH NEED TO BE SHOWN |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2 FOR ADDITIONAL |
| | INFORMATION, CLARITY AND COORDINATION. |
| | |
| | 36) NOTE: PLEASE COMPLETE ALL PANELS WITH THE CONDUCTOR |
| | SIZES PER 310.16, 240.4 ETC |
| | MANY ARE NOTED AND SHOWN HOWEVER DUE TO SOME PANELS NOT |
| | BEING COMPLETE AND SEVERAL OTHER ITEMS ARE MISSING ALL |
| | ITEMS CAN NOT BE REVIEWED. |
| | |
| | 37) NOTE: PLEASE KNOW THAT THE PLANS NEED TO BE |
| | COMPLETE WITH ALL CIRCUITING AND COORDINATE4 WITH ALL |
| | SUBMITTED PANEL SCHEDULES BEFORE A COMPLETE REVIEW FOR |
| | CODE COMPLIANCE CAN BE ACHIEVED. |
| | THERE ARE LITERALLY HUNDREDS OF ITEMS NOT COMPLETE. |
| | THERE ARE TOO NUMEROUS AMOUNT OF ITEMS TO LIST WHICH |
| | ALSO ONLY SHOW QUESTION MARKS |
| | PLEASE LABEL AND PROVIDE ROOM AND AREA DESIGNATIONS ON |
| | PLANS AND CORRELATE WITH THE PANEL SCHEDULES SHOWING |
| | ALL ROOMS AND AREAS IN WHICH CIRCUITS FEED WILL BE |
| | REQUIRED FOR EACH PANEL. AS MANY SHEETS ARE VERY FAINT |
| | OR ITEMS OVER LAY PLANS ARE NOT EASILY READ. |
| | PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE |
| | CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT |
| | ACCEPTABLE. THIS INCLUDES ALL SUITES/ROOMS. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 38) NOTE: PLEASE SEE FBC 1019.1.25 AS NO OTHER SYSTEMS |
| | ARE PERMITTED IN THE VERTICAL EGRESS STAIRS WITH THE |
| | EXCEPTION OF THOSE SYSTEMS REQUIRED TO BE PART OF THE |
| | STAIRS. |
| | |
| | 39) NOTE: PLEASE BE SURE TO SHOW/IDENTIFY THE REQUIRED |
| | SMOKE ALARMS, DETECTORS, AND CARBON MONOXIDE DETECTORS |
| | ON UNIT ROOM LAYOUT FOR ELECTRICAL PLANS AS THE FIRE |
| | ALARM WILL BE UNDER SEPARATE PERMIT. |
| | PLEASE SEE NFPA-72 CHAPTER 11, FBC CHAPTER 9. FS 553.85 |
| | |
| | 40) NOTE: PLEASE SEE 240.13,230.95 FOR REQUIRED GROUND |
| | FAULT PROTECTION. |
| | |
| | |
| | 41) NOTE: ** PLEASE SEE ELECTRICAL ROOM 153 FOR EXAMPLE |
| | AS THE DOOR SWINGS INTO THE ELECTRICAL PANELS. A |
| | SITUATION COULD OCCUR WHICH WOULD CREATE A SERIOUS |
| | INJURY OR DEATH IF AN OCCUPANT OPENS THIS DOOR WHILE AN |
| | ELECTRICIAN WORKING IN ONE OF THESE PANELS. THE DOOR |
| | SWING WOULD POSSIBLY PUSH THE WORKER INTO A *HOT |
| | PANEL*. THIS WILL NOT BE PERMITTED. PLEASE ALSO CHECK |
| | THE DOOR SWING ON THE FIRST FLOOR MAIN ELECTRICAL DOOR |
| | AS BOTH NEEDS TO SWING OUT. |
| | PLEASE ALSO PROVIDE A LAYOUT OF ALL ELECTRICAL, FIRE |
| | PUMP ROOMS ETC SO COMPLIANCE FOR MINIMUM CLEARANCES |
| | AREA REVIEWED. THERE ARE TWO FIRE PUMP ROOMS SHOWN. |
| | PLANS ARE NOT COMPLETE IN EITHER CASE FOR EITHER OF |
| | THESE LOCATIONS. |
| | |
| | PLEASE SEE NOTES ABOVE WITH RESPECT TO PERMITTED |
| | SYSTEMS SUCH AS 700 AND 701 IN THE SAME LOCATIONS. |
| | NFPA-110 SECTION 7.2.2 AS EPSS EQUIPMENT SHALL NOT BE |
| | INSTALLED IN THE SAME ROOM WHERE THE NORMAL ELECTRICAL |
| | SERVICE EQUIPMENT IS INSTALLED. THE CODE; SECTION |
| | 7.2.2.1 DOES PERMIT TRANSFER SWITCHES TO BE INSTALLED |
| | IN THE NORMAL ELECTRICAL SERVICE ROOM ONLY WHERE TWICE |
| | THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF NFPA 70, |
| | NATIONAL ELECTRICAL CODE, EXISTS BETWEEN EQUIPMENT |
| | ENCLOSURES. |
| | EMERGENCY EQUIPMENT ROOMS WITH THE 2HR RATING AS |
| | REQUIRED PER 7.2.1.1 PROVIDES THE SAFE LOCATION SO ANY |
| | FIRE IN THE MAIN SWITCH GEAR BY AN EXPLOSION ETC WOULD |
| | NOT DAMAGE THE LIFE SAFETY OR LEGALLY REQUIRED SYSTEMS. |
| | PLEASE SEE LOCATION WHERE THE GENERATOR IS RUNNING AT |
| | FULL SPEED CAN ALSO BE DISTRACTING FOR ANY EMERGENCY |
| | PERSONNEL WHEN ATTEMPTING TO SHUT DOWN ANY SPECIFIC |
| | SYSTEMS. MEETING THE SECTION ABOVE FOR SEPARATION AND |
| | CLEARANCE REQUIREMENTS NEEDS TO BE ADDRESSED. |
| | LOCATIONS OF ALL ELECTRICAL EQUIPMENT NEED TO BE |
| | VERIFIED. |
| | |
| | PLEASE COMPLETE PLANS WITH ALL FURNITURE AS PROPOSED. |
| | |
| | 42) NOTE: PLEASE SEE 210.8B3,4 AND 5 OF THE 2005 NEC |
| | WHICH REQUIRES ALL RECEPTACLES OUTSIDE EVEN IF FOR |
| | DEDICATE EQUIPMENT TO BE GFI/GFI PROTECTED. |
| | |
| | 43) NOTE: PLEASE SUBMIT A COMPLETE FIXTURE LEGEND FOR |
| | ALL SPECIFIC FIXTURES AND IDENTIFY ALL FIXTURES ON |
| | PLANS. THERE ARE SEVERAL ITEMS FOR FBC CHAPTER 13 AS |
| | NOTED ABOVE ALONG WITH OTHER ITEMS SUCH AS POOL AREA |
| | LIGHTS WHICH NEED TO BE REVIEWED. |
| | PLEASE SEE 411.4B, 680.22 AND 680.23 WHICH WILL GREATLY |
| | AFFECT THE REVIEW FOR TYPES OF FIXTURES PERMITTED. |
| | PLEASE PLACE NOTE ON LIGHTING PLANS FOR POOL AREA WHICH |
| | DOES NOT PERMIT ANY LOW VOLTAGE LIGHTING SYSTEMS WITHIN |
| | 10FT OF THE WATERS EDGE. |
| | FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION, CLARITY |
| | AND COORDINATION. |
| | |
| | 44) NOTE: PLEASE KEEP IN MIND TO INDICATE THE REQUIRED |
| | WIND LOAD RATINGS FOR ANY ROOF-TOP OR OUTSIDE POLE |
| | LIGHT PER SECTION 1609 OF THE FBC. THE CALCULATIONS |
| | WHICH NEED TO BE SUBMITTED WILL NEED TO SHOW THE EPA |
| | (EFFECTIVE PROJECTED AREA) OF ANY PROPOSED LIGHT |
| | FIXTURE. THE CALCULATIONS WILL BE PART OF THE |
| | STRUCTURAL REVIEW ONCE SHOWN AND SUBMITTED. |
| | ELECTRICAL PLANS MUST SHOW MINIMUM WIND LOAD DESIGNS. |
| | |
| | 45) NOTE: PLEASE PLACE NOTE ON PLANS FOR COLOR CODING |
| | FOR 277/480V SYSTEMS AS FOLLOWS: |
| | BROWN, PURPLED, AND YELLOW. |
| | PLEASE KNOW AS THE NEC DOES NOT PROVIDE COLOR CODING OF |
| | ALL SYSTEMS AND ORANGE IS FOR OPEN DELTA HIGH LEG |
| | SYSTEMS THE CITY OF WEST PALM BEACH USED TO HAVE |
| | TECHNICAL AMENDMENTS FOR THIS ITEM. THE LOCAL TECHNICAL |
| | AMENDMENTS ARE NO LONGER IN EFFECT HOWEVER IN KEEPING |
| | WITH THE UNIFORMITY WITH ALL OTHER BUILDING SYSTEMS |
| | WITHIN THIS JURISDICTION AND IN THE INTEREST OF LIFE |
| | SAFETY AND FIRE HAZARD THE ABOVE COLOR CODING IS |
| | REQUIRED PER 90.4. |
| | |
| | 46) NOTE: PLEASE INDICATE THE REQUIRED SIGN CIRCUIT PER |
| | 600.5. |
| | |
| | 47) NOTE: PLEASE CHECK WITH THE LOCAL FAA AUTHORITY FOR |
| | REQUIREMENTS OF ANY AIRCRAFT WARNING LIGHTS WHICH MAY |
| | BE REQUIRED. PLEASE CHECK WITH THE FAA WEBSITE OR |
| | CONTACT THE LOCAL AIRPORT AUTHORITY. |
| | THIS WILL AFFECT ELECTRICAL ON PLANS IF SO REQUIRED. |
| | ( OTHER HIGH-RISE BUILDINGS IN AREA DO CONTAIN AIRCRAFT |
| | WARNING LIGHTING). |
| | |
| | |
| | ** PLEASE BE SURE TO SUBMIT THE ABOVE INFORMATION AS |
| | WELL AS INFORMATION NOT YET SUBMITTED. |
| | PLEASE CALL TO GO OVER ANY COMMENTS WHICH MAY NOT BE |
| | CLEAR IN ANY MANNER. CONTACT INFORMATION IS BELOW. IF |
| | VOICE MAIL IS CONTACTED PLEASE BE SURE TO LISTEN TO |
| | MESSAGE AS I MAY NOT BE IN THE OFFICE. |
| | PLEASE LEAVE A MESSAGE WHEN CALLING AND THE CALL WILL |
| | BE RETURNED AS SOON AS POSSIBLE. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |