Plan Review Notes
Plan Review Notes For Permit 09010006
Permit Number 09010006
Review Stop E
Sequence Number 1
Notes
Date Text
2009-02-06 08:12:38 
  
  
 *** DENIED REVIEW **
  
  
 ** IMPORTANT:
 IT IS VERY IMPORTANT TO UNDERSTAND THE REVIEW IS BASED
 ON THE PLANS SUBMITTED AT THIS TIME. AS THERE IS MANY
 ITEMS NOT YET COMPLETED OR SUBMITTED FOR REVIEW A
 COMPLETE REVIEW OF CODE COMPLIANCE DETERMINATION CAN
 NOT BE DONE AT THIS TIME. THERE MAY CERTAINLY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW DUE TO CHANGES IN
 PLANS, SUBMITTED DOCUMENTS ETC WHICH IS NOT POSSIBLE TO
 BE MADE AT THIS TIME.
  
  
 1) NOTE: PLANS HAVE BEEN SUBMITTED FOR * PLAN REVIEW*
 ONLY AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE
 KNOW ONCE PERMIT APPLICATION IS MADE ITEMS SUCH AS
 LICENSING OF CONTRACTOR, AND OTHER DESIGN PROFESSIONALS
 WILL ALL BE VERIFIED AT THAT TIME. PLAN REVIEW DOES NOT
 *LOCK* A PROJECT IN UNDER THE CODE IN EFFECT AT THE
 TIME OF THE REVIEW. ONLY PLANS SUBMITTED FOR PERMIT
 APPLICATION WITH LICENSED CONTRACTOR. THIS IS GIVEN FOR
 INFORMATION ONLY AS THE FLORIDA BUILDING CODE IS SET TO
 CHANGE ON MARCH 1ST, 2009.
 EVEN ONCE ALL ITEMS NOTED FOR CODE COMPLIANCE ARE
 ADDRESSED AND PERMIT APPLICATION HAS NOT BEEN MADE THE
 REVIEW STATUS WILL STILL REMAIN FAILED.
  
 2) NOTE: PLANS NEED TO BE COMPLETE IN ORDER TO RECEIVE
 A COMPLETE REVIEW FOR CODE COMPLIANCE. AS THERE ARE
 SEVERAL ITEMS ON THE PLANS MISSING IT IS VERY POSSIBLE
 THERE WILL BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
 PLEASE BE SURE PLANS ARE PRINTED CLEARLY. THERE ARE
 SEVERAL SHEETS IN WHICH THE PRINT IS VERY FAINT AND NOT
 READABLE. THERE ARE SOME LOCATIONS IN WHICH WALLS ARE
 MISSING OR THERE IS SOME SORT OF SHIFT IN THE PLANS.
 PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON PLANS.
 PLEASE COMPLETE ALL LOAD CALCULATIONS. NEC 220
 PLEASE SEE FBC 106.1.1, 106.1.2 FOR CLARITY,
 COORDINATION AND ADDITIONAL INFORMATION. IT IS
 RECOMMENDED TO TAKE A LOOK AT THE CONSTRUCTION SERVICES
 DEPARTMENT WEBSITE WHICH CONTAINS A LIST OF SEVERAL
 ITEMS FOR MOST COMMON FAILURE ITEMS.
 PLEASE ALSO SEE FBC 106.1.3 FOR QUALITY OF PLANS BEING
 SUBMITTED.
  
 3) NOTE: THE CODES FOR THIS REVIEWER NEED TO BE STATED
 ON PLANS AS FOLLOWS. THERE IS NO COVER SHEET, NO PAGE
 IDENTIFICATION PAGE ETC
 THE FOLLOWING CODES ARE THE CURRENT CODES IN EFFECT.
 THERE ARE SEVERAL OF THESE WHICH WILL BE REVISED COME
 MARCH 1ST, 2009. THIS WILL AFFECT REVIEW AND DESIGN.
 CURRENT CODES ARE:
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70 (NATIONAL ELECTRICAL CODE)
 2006 NFPA-101 (LIFE SAFETY CODE)
 2002 NFPA-72 (NATIONAL FIRE ALARM CODE)
 2003 NFPA-20 ( STANDARD FOR STATIONARY FIRE PUMP)
 PLEASE ALSO BE SURE THE FP SHEETS CONTAIN THE REFERENCE
 TO NFPA-20 2003.
  
 ** THESE ARE NOTED FOR THIS REVIEWER. THERE MAY BE
 OTHERS NOTED BY OTHER TRADES.
 PLEASE SEE SOME NOTES BELOW AS THERE ARE SOME CODE
 REFERENCES TO CODES WHICH ARE NO LONGER ADOPTED IN THE
 STATE OF FLORIDA.
  
 4) NOTE: PLANS ARE NOT SIGNED, DATED OR SEALED. FS 481,
 471, FAC 61G15-23.002, .001 ETC
 AS PLANS WERE ONLY SUBMITTED FOR PARTIAL PLAN REVIEW IT
 IS UNDERSTOOD WHY THEY WERE NOT SIGNED AND SEALED.
  
 5) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS. SOME WERE SUBMITTED AND SHOWN FOR GARAGE
 AREAS HOWEVER THESE ARE NOT ALL EGRESS PATHS. PLEASE BE
 SURE TO SEE NFPA-101 7.8.1.3, 7.9.1.2, 7.9.2.2, FBC
 1006.2.1, .2.3. ALL EGRESS STAIRS SHALL CONTAIN A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED
 TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 THIS IS BASED ON AN AVERAGE PER FORMULA STATED IN THE
 LIFE SAFETY CODE.
 ** IMPORTANT**
 IF THIS BUILDING IS GOING TO REMAIN OCCUPIED UNDER
 EMERGENCY POWER DURING OR AFTER AN EVEN SUCH AS A
 HURRICANE OR OTHER TIME WHEN NORMAL POWER IS LOST THE
 BUILDING SHALL CONTAIN BATTERY BACK UP LIGHTING IN ALL
 EGRESS PATHS TO MEET THE 1FT CANDLE AVERAGE. THE LIFE
 SAFETY CODE AS WELL AS CHAPTER 10 OF THE FLORIDA
 BUILDING CODE ADDRESSES THE REQUIRED EGRESS LIGHTING TO
 EXIT *ALL* OCCUPANTS OUT OF THE BUILDING IN EMERGENCY
 EVENT OR LOSS OF NORMAL POWER.
 WHEN A BUILDING IS OCCUPIED UNDER EMERGENCY POWER THE
 BACK UP SYSTEM OF THE PREVIOUS NORMAL POWER HAS NOW
 BECOME THE NORMAL POWER. A LOSS OF ONE BREAKER SUCH AS
 THE GENERATOR MAIN OR THE GENERATOR ITSELF GOING DOWN
 WOULD REMOVE ALL LIFE SAFETY BACK UP FOR LIGHTING AND
 EGRESS PATHS.
 PLEASE CALL TO GO OVER OTHER OPTIONS WHICH WOULD
 REQUIRE A LETTER THE OWNER WHICH WOULD BE REQUIRED TO
 EVACUATE ALL OCCUPANTS WHEN THE BUILDING GOES INTO
 EMERGENCY POWER BACK UP. THE WORDING TO THAT AFFECT
 WOULD BE GONE OVER AT A LATER DATE IF THAT IS THE
 OPTION.
 BASED ON THE PLANS SUBMITTED OTHER LOCATIONS WHICH WILL
 REQUIRE BATTERY BACK UP LIGHTING FIXTURES OF SOME TYPE
 WHETHER OR NOT BUILDING REMAINS OCCUPIED WILL BE THE
 STAIRS, EMERGENCY GENERATOR ROOM, FIRE PUMP ROOM, MAIN
 ELECTRICAL ROOM, ELEVATOR EQUIPMENT ROOMS AND FIRE
 COMMAND ROOM AND OTHER POSSIBLE LOCATIONS AS NOT ALL
 ARE COMPLETE. THERE ARE AREAS OF THE PLANS WHICH DO NOT
 MEET THE WIRING REQUIREMENTS AND ARE ALSO REQUIRED TO
 CONTAIN BATTERY BACK UP FIXTURE FOR EGRESS LIGHTING.
 PLEASE SEE SECTIONS ABOVE AS WELL AS 700.12F, 700.16
 ETC.
 ALL STAIRS BASED ON WIRING AS SHOWN ARE REQUIRED TO BE
 BATTERY BACK UP.
 BATTERY BACK UP LIGHTING SHALL BE INSTALLED. THE
 GENERATOR MAY NOT BE USED AS THE SOLE BACK UP FOR
 EGRESS LIGHTING.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE LIFE SAFETY CODE. 7.9.2.2.
 PLEASE ALSO SEE 7.8.2.1 AS THE SOURCE SHALL BE
 ACCEPTABLE TO THE AHJ.
  
 THE EMERGENCY LIGHTING SYSTEM SHALL BE ARRANGED TO
 PROVIDE THE REQUIRED ILLUMINATION AUTOMATICALLY IN THE
 EVENT OF ANY INTERRUPTION OF NORMAL LIGHTING DUE TO ANY
 OF THE FOLLOWING:
 (1) FAILURE OF A PUBLIC UTILITY OR OTHER OUTSIDE
 ELECTRICAL POWER SUPPLY
 (2) OPENING OF A CIRCUIT BREAKER OR FUSE
 (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A
 SWITCH CONTROLLING NORMAL LIGHTING FACILITIES
  
  
  
 6) NOTE: LOCATIONS SUCH AS THE FIRE COMMAND ROOM AND
 THE EMERGENCY GENERATOR ROOM WOULD REQUIRE SUCH
 SIGNAGE. ALL OF THESE ROOMS ARE ALSO REQUIRED TO
 CONTAIN PERMANENT MAPPING CONTAINING A LAYOUT OF THE
 BUILDING SHOWING THE LOCATIONS OF EACH OF THESE ROOMS
 CLEARLY IDENTIFIED. THIS WOULD BE REQUIRED IN ALL ROOMS
 NOTING EACH OF THE OTHERS. THIS COMMENT MAY BE ADDRESS
 BY NOTES ON PLANS. THIS WILL ONE OF THE REQUIRED ITEMS
 BY THE CONTRACTOR TO HAVE ALL SIGNAGE UP FOR ALL MAINS,
 ELECTRICAL SERVICES, FIRE PUMPS, FIRE COMMAND ROOM ETC
 BEFORE ANY RELEASE OF POWER. THIS IS NOT THE ONLY
 REQUIREMENT OTHERS WILL BE DIRECTED AT A LATER DATE BY
 THE INSPECTION STAFF.
 230.2E, 700.8,701.9, ETC
  
 7) NOTE: PLEASE BE SURE TO LIST ALL OF THE FOLLOWING
 ITEMS REQUIRED TO BE LOCATED IN THE FIRE COMMAND ROOM.
 NFPA-101 11.8.5 THESE ARE SYSTEMS AT A MINIMUM. PLEASE
 SEE NOTES FORM OTHER TRADES SUCH AS THE FIRE MARSHAL
 WHICH MAY ALSO NOTE OTHER ITEMS.
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER
 SECTION OF THIS CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) SPRINKLER VALVE AND WATER-FLOW ANNUNCIATORS
 (6) EMERGENCY GENERATOR STATUS INDICATORS
 (7) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (8) FIRE PUMP STATUS INDICATORS
 (9) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
  
 8) NOTE: PLEASE BE SURE THE ELEVATION OF ALL EMERGENCY
 ELECTRICAL SYSTEMS SUCH AS THE GENERATOR, EQUIPMENT,
 FIRE PUMP ETC IS LISTED ON PLANS. THE ELEVATIONS ARE
 REQUIRED TO MEET ONE OF THE FOLLOWING; EITHER THE 100
 YEAR STORM ELEVATION OR THE ELEVATION SET FORTH BY THE
 SLOSH (SEA, LAKE, OVERLAND SURGES BY HURRICANES) CHARTS
 BASED ON A CATEGORY 4 HURRICANE.
 PLEASE SEE NFPA-110 CHAPTER 7.2.3
  
 9) NOTE: AS NOTED ABOVE FOR COMPLETE PHOTO-METRICS FOR
 EGRESS. PLEASE ALSO INCLUDE THE LIGHTING LEVELS IN THE
 EMERGENCY GENERATOR ROOM. PLEASE SEE NFPA-110 7.3.3.
 THE LIGHTING LEVELS IN THIS ROOM SHALL BE AT A MINIMUM
 OF 30FT CANDLES.
  
 10) NOTE: PLEASE ALSO INCLUDE THE LIGHTING LEVELS FOR
 ELEVATOR PITS TO MEET THE MINIMUM OF 5FT CANDLES.
 PLEASE SEE NEC 620.23 WHICH CONTAINS REFERENCE TO
 MINIMUM REQUIREMENTS. SEE HANDBOOK COMMENTARY; ASME
 A17.1-2004, SAFETY CODE FOR ELEVATORS AND ESCALATORS,
 REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) AT THE PIT
 FLOOR AND REQUIRES LUMINAIRES TO BE EXTERNALLY GUARDED
 TO PREVENT ACCIDENTAL BREAKAGE.
  
  
 11) NOTE: PLEASE SUBMIT MORE INFORMATION ON ALL
 PROPOSED LIGHTING CONTROL SYSTEMS. SEE NOTES WITH
 RESPECT TO FBC EXISTING BUILDING CODE WITH RESPECT TO
 HISTORIC BUILDINGS AND REQUIREMENTS PER THE BUILDING
 CODE.
 SEE CHAPTER 13, 13-415.1.ABC.1 ETC.
 AS PLANS ARE NOT COMPLETE WITH INFORMATION, ACTUAL
 DESIGN AND SEVERAL OTHER ASPECTS BEING INCOMPLETE IT IS
 VERY DIFFICULT TO GIVE MANY TECHNICAL CODE SECTIONS.
  
 12) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING ITEMS.
 THE GENERATOR.
 FIRE PUMP.
 FIRE PUMP CONTROLLER.
 ATS (AUTOMATIC TRANSFER SWITCH).
 FUEL TANK. THE FUEL TANK WILL BE REVIEWED BY OTHERS)
  
 MINIMUM EQUIPMENT MEETING THE CODE AT THIS TIME MUST BE
 VERIFIED. EVEN IF THE EQUIPMENT IS NOT FINAL EQUIPMENT
 WILL NEED TO BE CHOSEN AT THIS TIME MEETING MINIMUM
 PERMITTED BY CODE. THE MANUFACTURE OR BRAND OF
 EQUIPMENT MAY ALWAYS BE CHANGED AT A LATE DATE.
 90.7,110.3, NFPA_20, NFPA-101, NFPA-70, NFPA-110.
 FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 13) NOTE: PLEASE PROVIDE ALL SHUT DOWN OF ALL EQUIPMENT
 IN IT ROOM INCLUDING A/C UNIT. THE PLANS DO NOT SHOW
 ANY EPO (EMERGENCY POWER OFF) BUTTON AS REQUIRED PER
 645.10. THE PLANS IDENTIFY LOCATIONS AS *IT ROOMS*
 HOWEVER BASED ON PLANS NOT BEING COMPLETE THERE ARE
 SEVERAL UNANSWERED QUESTIONS. PLEASE SEE 645.10 FOR
 DISCONNECTING REQUIREMENTS.
 PLEASE SEE NEC 645.4 REQUIREMENTS OF AN IT ROOM. WHEN
 ANY PROPOSED ROOM DOES MEETS ALL ITEMS LISTED PER 645.4
 THE WIRING METHODS WHICH ARE LESS STRINGENT IN THIS
 CODE SECTION MAY NOT BE USED.
 PLEASE MEET ALL OF 645.4 OR PLEASE CHANGE DESIGNATION
 AND PROVIDE NOTE FOR WIRING METHODS OF CHAPTERS 1-4
 MUST BE USED. IT MAY BE HELPFUL TO CONTACT IT PERSONNEL
 FOR MARRIOTT OR OWNER TO CONFIRM WIRING METHODS TO BE
 USED.
 THE FOLLOWING IS EXTRACTED FROM THE NEC FOR EASE OF
 CODE SECTIONS:
  
  
 THIS ARTICLE SHALL APPLY, PROVIDED ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) DISCONNECTING MEANS COMPLYING WITH 645.10 ARE
 PROVIDED.
 (2) A SEPARATE HEATING/VENTILATING/AIR-CONDITIONING
 (HVAC) SYSTEM IS PROVIDED THAT IS DEDICATED FOR
 INFORMATION TECHNOLOGY EQUIPMENT USE AND IS SEPARATED
 FROM OTHER AREAS OF OCCUPANCY. ANY HVAC SYSTEM THAT
 SERVES OTHER OCCUPANCIES SHALL BE PERMITTED TO ALSO
 SERVE THE INFORMATION TECHNOLOGY EQUIPMENT ROOM IF
 FIRE/SMOKE DAMPERS ARE PROVIDED AT THE POINT OF
 PENETRATION OF THE ROOM BOUNDARY. SUCH DAMPERS SHALL
 OPERATE ON ACTIVATION OF SMOKE DETECTORS AND ALSO BY
 OPERATION OF THE DISCONNECTING MEANS REQUIRED BY
 645.10.
 FPN: FOR FURTHER INFORMATION, SEE NFPA 75-2003,
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT, CHAPTER 10, 10.1, 10.1.1, 10.1.2, AND
 10.1.3.
 (3) LISTED INFORMATION TECHNOLOGY EQUIPMENT IS
 INSTALLED.
 (4) THE ROOM IS OCCUPIED ONLY BY THOSE PERSONNEL NEEDED
 FOR THE MAINTENANCE AND FUNCTIONAL OPERATION OF THE
 INSTALLED INFORMATION TECHNOLOGY EQUIPMENT.
 (5) THE ROOM IS SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTANT-RATED WALLS, FLOORS, AND CEILINGS WITH
 PROTECTED OPENINGS.
 FPN: FOR FURTHER INFORMATION ON ROOM CONSTRUCTION
 REQUIREMENTS, SEE NFPA 75-2003, STANDARD FOR THE
 PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT, CHAPTER
 5.
  
 ALL ITEMS ABOVE WITH THE EXCEPTION OF # 1 ABOVE ARE
 SHOWN ON PLANS.
  
 14) NOTE: PLEASE PLACE NOTES ON PLANS FOR SIGNAGE
 REQUIRED FOR ARC FLASH OF ALL EQUIPMENT MEETING 110.16
  
 15) NOTE: PLEASE SEE FBC 3006.2 FOR REQUIRED
 CONDITIONING/VENTILATION OF ELEVATOR EQUIPMENT ROOMS.
 THE ELECTRICAL PLANS DO SHOW ELECTRICAL FOR ELEVATOR
 EQUIPMENT.
  
 16) NOTE: PLEASE SEE 620.23 AS NOTED ABOVE FOR ELEVATOR
 PIT AREAS FOR LIGHTING LEVELS. THIS SAME SECTION
 REQUIRES THE LIGHTING AS WELL AS RECEPTACLES IN THESE
 EQUIPMENT ROOMS TO BE ON DEDICATED CIRCUITS. AS PLANS
 ARE NOT COMPLETE WITH CIRCUITING NO REVIEW WITH
 NUMEROUS SECTIONS OF 620 CAN NOT BE DONE.
  
 17) NOTE: PLEASE OBTAIN PHOTO-METRIC LEVELS FOR
 SWIMMING POOL AREA FOR ANY NIGHT TIME SWIMMING PER PALM
 BEACH COUNTY HEALTH DEPARTMENT. ALL PHOTO-METRICS FOR
 ANY SWIMMING AFTER DUSK OR BEFORE DAWN SHALL BE STAMPED
 BY THE HEALTH DEPARTMENT.
 THIS IS NOT A CITY OF WEST PALM BEACH ADOPTED LEVEL OF
 LIGHTING HOWEVER UNLESS PLANS ARE STAMPED PERMIT MAY
 NOT BE ISSUED. PLEASE ALSO KEEP IN MIND IF THERE IS NOT
 GOING TO BE ANY SWIMMING OUTSIDE OF THE DAYLIGHTS HOURS
 PER THE HEALTH DEPARTMENT PLEASE PLACE NOTES ON PLANS
 ACCORDINGLY.
  
 18) NOTE: ANY PROPOSED LIGHTNING PROTECTION SYSTEM IS
 GOING TO BE REQUIRED TO BE UNDER SEPARATE PERMIT.
 HOWEVER PLEASE PLACE NOTES ON PLANS THAT ANY PROPOSED
 LIGHTNING PROTECTION SYSTEM SHALL MEET NFPA-780. (OR
 WORDS TO THAT AFFECT).
 THERE ARE MANY SYSTEMS ON THE MARKET WHICH DO NOT MEET
 ANY ACCEPTABLE STANDARD AND ARE NOT LISTED TO MEET
 NFPA-780.
  
 19) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS
 PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE
 SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE
 LIFE SAFETY PLANS.
 * TO THE BEST OF THE ARCHITECT???S OR ENGINEER???S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633, FLORIDA STATUTES*
  
 20) NOTE: PLEASE SEE FA PLANS. PLEASE SEE CHAPTER 11 OF
 THE FBC. PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR
 REFERENCES AND PLEASE BE SURE TO REFLECT THESE CODES.
  
 21) NOTE: PLEASE PROVIDE INFORMATION ON FUEL
 CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP
 AND ALL EMERGENCY SYSTEMS PER 700 AND 701.
 PLEASE BE SURE TO INCLUDE 5% FOR SUMP AND 5% FOR
 EXPANSION.
 PLEASE SEE NFPA-110, NFPA-20 9.6.2.2
  
 22) NOTE: WHEN COMPLETING PLANS PLEASE BE SURE TO LABEL
 ALL MAINS AND EQUIPMENT. 230.2E, 700.8, 701.9 ETC.
  
 23) NOTE: NO INFORMATION FOR FIRE PUMP CONTROLLER AS
 SERVICE ENTRANCE RATED OR ANY OTHER INFORMATION AT THIS
 TIME. PLEASE SEE NEC 695,695.4 AND NFPA-20. PLEASE SEE
 NOTES ABOVE AND EXPANDED ON THE FIRE PUMP CONTROLLER
 INFORMATION.
 PLEASE BE SURE TO SEE NOTES ON TRANSFER SWITCHES.
  
 24) NOTE: PLEASE SEE 230.95,240.13 ETC. THE CODE
 REQUIRES GROUND FAULT PROTECTION FOR ANY SYSTEMS 150V
 OR MORE TO GROUND AND 1000AMPS OR OVER. THE RISER
 INDICATES GFI PROTECTION WHICH IS CLASS A PROTECTION
 FOR PERSONNEL. THIS IS NOT THE SAME KING OF PROTECTION
 WHICH IS GFP WHICH IS WHAT IS REQUIRED IN THE SECTIONS
 GIVEN. PLEASE PROVIDE INFORMATION ON THE TRANSFER
 SWITCHES AND PLEASE SEE THE FOLLOWING COMMENT WHICH MAY
 AFFECT THE USE OF 3-POLE OR 4-POLE TRANSFER SWITCHES.
  
 25) NOTE: PLEASE SEE NEC
 ,250.20,250.30,250.66,240.13.230.95, 700.7D AND 700.26.
 GFP PROTECTION IS REQUIRED ON THE NORMAL SIDE OF THE
 SERVICE HOWEVER ONLY GROUND FAULT SENSING IS REQUIRED
 TO BE ON THE SECONDARY SIDE. THE CODE ACTUALLY DOES NOT
 REQUIRE NOR DOES IT RECOMMEND GFP ON THE EMERGENCY
 EQUIPMENT.
 PLEASE SEVERAL WHITE PAPERS WHICH HAVE NOTES ON THE
 ABOVE SITUATION WHEN GROUND FAULT PROTECTION IS
 TRIGGERED BY THE CODE. MANY OF THESE IN FACT NOTE A
 COORDINATION LOSS OF EQUIPMENT WHEN THE USE OF 3-POLE
 ATS SWITCHES IS USED.
 PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL
 CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING
 CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND
 THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM *ASCO*
 WHITE PAPERS:
  
 WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE CODE
 AND AN ALTERNATE POWER SUPPLY IS INCLUDED, SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT SHOWN ABOVE
 ILLUSTRATES SUCH A CIRCUMSTANCE. THE SERVICE IS LARGER
 THAN 1,000 AMPS. CONSEQUENTLY, GROUND FAULT PROTECTION
 IS REQUIRED AT THE MAIN SERVICE DISCONNECT AT A
 MINIMUM. IF IT IS INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID CONNECTION TO THE
 MAIN SERVICE NEUTRAL, A GROUND FAULT WHEN THE GENERATOR
 IS FEEDING THE LOAD WILL CAUSE THE MAIN SERVICE
 DISCONNECT TO OPEN. THIS WILL NOT DISCONNECT THE ARCING
 FAULT FROM THE GENERATOR. COORDINATION IS THUS LOST."
  
 THIS HAS BEEN READ AND NOTED BY OTHER MANUFACTURES.
 PLEASE OBTAIN AND VERIFY COORDINATION FROM THE PROPOSED
 MANUFACTURE AND ADJUST PLANS.
 AS THE PLANS DO NOT INDICATE THE USE OF 3 OR 4 POLE
 DEVICES AT THIS TIME FINAL COMMENT CAN NOT BE MADE.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL MAYBE BE
 REQUIRED TO BE REVISED.
  
 26) NOTE: PLEASE SEE 700.9 OF THE NEC ALONG WITH
 EXHIBITS IN 700.1 ETC.
 *** IMPORTANT**
 PLEASE SEE NEC 700 AND 701 DEFINITIONS AND OTHER
 ADOPTED CODES AS NOT ALL SYSTEMS, FEEDERS, BRANCH
 CIRCUITS ETC ARE LIFE SAFETY/EMERGENCY SYSTEMS. SOME
 SHALL BE CONSIDERED LEGALLY REQUIRED. THIS WOULD
 REQUIRE SEPARATION.
 AN EXAMPLE IS THE ELEVATOR IS THIS OCCUPANCY IS
 CONSIDERED LEGALLY REQUIRE AND NOT LIFE SAFETY. THIS IS
 A BACK UP REQUIRED TO COME ON IN 60SECONDS INSTEAD OF
 THE REQUIRED 10 SECONDS LISTED IN 700 SYSTEMS.
 AN ELEVATOR IN A HOSPITAL WOULD BE DIFFERENT AND WOULD
 BE CONSIDERED LIFE SAFETY.
 THIS COMMENT WILL ALL TIE INTO THE COMMENTS ABOVE WITH
 RESPECT TO THE LIGHTING AND BACK UP OF THE EGRESS
 LIGHTS.
 PLEASE BE AWARE OF ANY PHONE SYSTEMS BEING PROPOSED
 WHICH WOULD BE REQUIRED TO CONTAIN UPS FOR BACK AS
 EMERGENCY COMMUNICATIONS IS REQUIRED TO CONTAIN BACK UP
 WHICH MAY THEN BE PART OF THE GENERATOR WHICH IS 10, 60
 SECOND BACK UP. NO DELAY IN PHONE SYSTEM IS PERMITTED.
  
 27) NOTE: PLEASE SUBMIT A COMPLETE COORDINATION STUDY
 FOR ALL LIFE SAFETY/EMERGENCY SERVICE EQUIPMENT AND
 BREAKERS. PLEASE SEE 240.12, 700.27 AND 701.18. THIS
 REQUIRES ALL BREAKERS AND EQUIPMENT TO BE COORDINATE.
  
 28) NOTE: PLEASE PROVIDE NOTE FOR SUPPORT OF VERTICAL
 CONDUCTORS PER 300.19.
  
 29) NOTE: PLEASE INDICATE AIC RATING FOR ALL SERVICE
 EQUIPMENT INCLUDING RATINGS OF ALL PANELS. 110.9. COULD
 NOT LOCATE ALL REQUIRED.
  
 30) NOTE: EVEN AS THE SWIMMING POOL IS UNDER A SEPARATE
 PERMIT PLEASE SEE 2005 NEC WHICH REQUIRES AN EQUAL
 POTENTIAL BOND.
 PLEASE PROVIDE DETAIL ON PLANS AS THIS MAY BE PART OF
 THE STRUCTURAL ELEMENTS OF THE PROPOSED STRUCTURE AND
 POOL AREA. 680.26
  
 31) NOTE: PLEASE PROVIDE THROUGH WALL AND FLOORS
 PENETRATION DETAILS PER 300.21. THE SPREAD OF FIRE IS
 REQUIRED TO BE CONTAINED PER SEVERAL ADOPTED REFERENCES
 AND STANDARDS.
 PLEASE SEE THE HANDBOOK COMMENTARY WHICH PROVIDES THE
 REFERENCES SUCH AS NFPA-221,251, ASTM AND ANSI
 REQUIREMENTS.
  
 32) NOTE: PLEASE COORDINATE ALL ITEMS ON RISER AND
 PANEL SCHEDULES. PLEASE SUBMIT COMPLETE PLANS FOR FULL
 REVIEW. THERE ARE SEVERAL ASPECTS OF RISER AND PANELS
 WHICH ARE NOT COMPLETED. NO CONDUCTORS, ETC ARE SHOWN.
 310.16,215.5 ETC
 FBC 106.1.1, 106.1.2, 106.3.5.1.2
  
 33) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED
 THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES
 A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END
 DEVICE ON A CIRCUIT. THIS MAY GREATLY AFFECT FEEDERS OR
 BRANCH CIRCUIT CONDUCTORS.
 PLEASE SEE 13-413.1ABC.1.
  
 34) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER
 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN
 THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH FLORIDA
 BUILDING COMMISSION/DCA.
  
 35) NOTE: PLEASE INCLUDE LOAD CALCULATIONS FOR ALL
 PANELS AND SERVICES. SOME INFORMATION IS SHOWN ON PLANS
 HOWEVER MOST IS NOT COMPLETE AT THIS TIME.
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%.
 230.42,215.5.
 220.
 PLEASE SEE SECTIONS SUCH AS 220.12,220.14,220.42,
 220.44 AND OTHERS SUCH AS 220.43 FOR TRACK LIGHTING.
 THERE ARE SEVERAL ASPECTS OF THE LOAD CALCULATIONS AND
 HOW LOADS WERE DERIVED WHICH NEED TO BE SHOWN
 FBC 106.1.1, 106.1.2, 106.3.5.1.2 FOR ADDITIONAL
 INFORMATION, CLARITY AND COORDINATION.
  
 36) NOTE: PLEASE COMPLETE ALL PANELS WITH THE CONDUCTOR
 SIZES PER 310.16, 240.4 ETC
 MANY ARE NOTED AND SHOWN HOWEVER DUE TO SOME PANELS NOT
 BEING COMPLETE AND SEVERAL OTHER ITEMS ARE MISSING ALL
 ITEMS CAN NOT BE REVIEWED.
  
 37) NOTE: PLEASE KNOW THAT THE PLANS NEED TO BE
 COMPLETE WITH ALL CIRCUITING AND COORDINATE4 WITH ALL
 SUBMITTED PANEL SCHEDULES BEFORE A COMPLETE REVIEW FOR
 CODE COMPLIANCE CAN BE ACHIEVED.
 THERE ARE LITERALLY HUNDREDS OF ITEMS NOT COMPLETE.
 THERE ARE TOO NUMEROUS AMOUNT OF ITEMS TO LIST WHICH
 ALSO ONLY SHOW QUESTION MARKS
 PLEASE LABEL AND PROVIDE ROOM AND AREA DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULES SHOWING
 ALL ROOMS AND AREAS IN WHICH CIRCUITS FEED WILL BE
 REQUIRED FOR EACH PANEL. AS MANY SHEETS ARE VERY FAINT
 OR ITEMS OVER LAY PLANS ARE NOT EASILY READ.
 PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE
 CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE. THIS INCLUDES ALL SUITES/ROOMS.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 38) NOTE: PLEASE SEE FBC 1019.1.25 AS NO OTHER SYSTEMS
 ARE PERMITTED IN THE VERTICAL EGRESS STAIRS WITH THE
 EXCEPTION OF THOSE SYSTEMS REQUIRED TO BE PART OF THE
 STAIRS.
  
 39) NOTE: PLEASE BE SURE TO SHOW/IDENTIFY THE REQUIRED
 SMOKE ALARMS, DETECTORS, AND CARBON MONOXIDE DETECTORS
 ON UNIT ROOM LAYOUT FOR ELECTRICAL PLANS AS THE FIRE
 ALARM WILL BE UNDER SEPARATE PERMIT.
 PLEASE SEE NFPA-72 CHAPTER 11, FBC CHAPTER 9. FS 553.85
  
 40) NOTE: PLEASE SEE 240.13,230.95 FOR REQUIRED GROUND
 FAULT PROTECTION.
  
  
 41) NOTE: ** PLEASE SEE ELECTRICAL ROOM 153 FOR EXAMPLE
 AS THE DOOR SWINGS INTO THE ELECTRICAL PANELS. A
 SITUATION COULD OCCUR WHICH WOULD CREATE A SERIOUS
 INJURY OR DEATH IF AN OCCUPANT OPENS THIS DOOR WHILE AN
 ELECTRICIAN WORKING IN ONE OF THESE PANELS. THE DOOR
 SWING WOULD POSSIBLY PUSH THE WORKER INTO A *HOT
 PANEL*. THIS WILL NOT BE PERMITTED. PLEASE ALSO CHECK
 THE DOOR SWING ON THE FIRST FLOOR MAIN ELECTRICAL DOOR
 AS BOTH NEEDS TO SWING OUT.
 PLEASE ALSO PROVIDE A LAYOUT OF ALL ELECTRICAL, FIRE
 PUMP ROOMS ETC SO COMPLIANCE FOR MINIMUM CLEARANCES
 AREA REVIEWED. THERE ARE TWO FIRE PUMP ROOMS SHOWN.
 PLANS ARE NOT COMPLETE IN EITHER CASE FOR EITHER OF
 THESE LOCATIONS.
  
 PLEASE SEE NOTES ABOVE WITH RESPECT TO PERMITTED
 SYSTEMS SUCH AS 700 AND 701 IN THE SAME LOCATIONS.
 NFPA-110 SECTION 7.2.2 AS EPSS EQUIPMENT SHALL NOT BE
 INSTALLED IN THE SAME ROOM WHERE THE NORMAL ELECTRICAL
 SERVICE EQUIPMENT IS INSTALLED. THE CODE; SECTION
 7.2.2.1 DOES PERMIT TRANSFER SWITCHES TO BE INSTALLED
 IN THE NORMAL ELECTRICAL SERVICE ROOM ONLY WHERE TWICE
 THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF NFPA 70,
 NATIONAL ELECTRICAL CODE, EXISTS BETWEEN EQUIPMENT
 ENCLOSURES.
 EMERGENCY EQUIPMENT ROOMS WITH THE 2HR RATING AS
 REQUIRED PER 7.2.1.1 PROVIDES THE SAFE LOCATION SO ANY
 FIRE IN THE MAIN SWITCH GEAR BY AN EXPLOSION ETC WOULD
 NOT DAMAGE THE LIFE SAFETY OR LEGALLY REQUIRED SYSTEMS.
 PLEASE SEE LOCATION WHERE THE GENERATOR IS RUNNING AT
 FULL SPEED CAN ALSO BE DISTRACTING FOR ANY EMERGENCY
 PERSONNEL WHEN ATTEMPTING TO SHUT DOWN ANY SPECIFIC
 SYSTEMS. MEETING THE SECTION ABOVE FOR SEPARATION AND
 CLEARANCE REQUIREMENTS NEEDS TO BE ADDRESSED.
 LOCATIONS OF ALL ELECTRICAL EQUIPMENT NEED TO BE
 VERIFIED.
  
 PLEASE COMPLETE PLANS WITH ALL FURNITURE AS PROPOSED.
  
 42) NOTE: PLEASE SEE 210.8B3,4 AND 5 OF THE 2005 NEC
 WHICH REQUIRES ALL RECEPTACLES OUTSIDE EVEN IF FOR
 DEDICATE EQUIPMENT TO BE GFI/GFI PROTECTED.
  
 43) NOTE: PLEASE SUBMIT A COMPLETE FIXTURE LEGEND FOR
 ALL SPECIFIC FIXTURES AND IDENTIFY ALL FIXTURES ON
 PLANS. THERE ARE SEVERAL ITEMS FOR FBC CHAPTER 13 AS
 NOTED ABOVE ALONG WITH OTHER ITEMS SUCH AS POOL AREA
 LIGHTS WHICH NEED TO BE REVIEWED.
 PLEASE SEE 411.4B, 680.22 AND 680.23 WHICH WILL GREATLY
 AFFECT THE REVIEW FOR TYPES OF FIXTURES PERMITTED.
 PLEASE PLACE NOTE ON LIGHTING PLANS FOR POOL AREA WHICH
 DOES NOT PERMIT ANY LOW VOLTAGE LIGHTING SYSTEMS WITHIN
 10FT OF THE WATERS EDGE.
 FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION, CLARITY
 AND COORDINATION.
  
 44) NOTE: PLEASE KEEP IN MIND TO INDICATE THE REQUIRED
 WIND LOAD RATINGS FOR ANY ROOF-TOP OR OUTSIDE POLE
 LIGHT PER SECTION 1609 OF THE FBC. THE CALCULATIONS
 WHICH NEED TO BE SUBMITTED WILL NEED TO SHOW THE EPA
 (EFFECTIVE PROJECTED AREA) OF ANY PROPOSED LIGHT
 FIXTURE. THE CALCULATIONS WILL BE PART OF THE
 STRUCTURAL REVIEW ONCE SHOWN AND SUBMITTED.
 ELECTRICAL PLANS MUST SHOW MINIMUM WIND LOAD DESIGNS.
  
 45) NOTE: PLEASE PLACE NOTE ON PLANS FOR COLOR CODING
 FOR 277/480V SYSTEMS AS FOLLOWS:
 BROWN, PURPLED, AND YELLOW.
 PLEASE KNOW AS THE NEC DOES NOT PROVIDE COLOR CODING OF
 ALL SYSTEMS AND ORANGE IS FOR OPEN DELTA HIGH LEG
 SYSTEMS THE CITY OF WEST PALM BEACH USED TO HAVE
 TECHNICAL AMENDMENTS FOR THIS ITEM. THE LOCAL TECHNICAL
 AMENDMENTS ARE NO LONGER IN EFFECT HOWEVER IN KEEPING
 WITH THE UNIFORMITY WITH ALL OTHER BUILDING SYSTEMS
 WITHIN THIS JURISDICTION AND IN THE INTEREST OF LIFE
 SAFETY AND FIRE HAZARD THE ABOVE COLOR CODING IS
 REQUIRED PER 90.4.
  
 46) NOTE: PLEASE INDICATE THE REQUIRED SIGN CIRCUIT PER
 600.5.
  
 47) NOTE: PLEASE CHECK WITH THE LOCAL FAA AUTHORITY FOR
 REQUIREMENTS OF ANY AIRCRAFT WARNING LIGHTS WHICH MAY
 BE REQUIRED. PLEASE CHECK WITH THE FAA WEBSITE OR
 CONTACT THE LOCAL AIRPORT AUTHORITY.
 THIS WILL AFFECT ELECTRICAL ON PLANS IF SO REQUIRED.
 ( OTHER HIGH-RISE BUILDINGS IN AREA DO CONTAIN AIRCRAFT
 WARNING LIGHTING).
  
  
 ** PLEASE BE SURE TO SUBMIT THE ABOVE INFORMATION AS
 WELL AS INFORMATION NOT YET SUBMITTED.
 PLEASE CALL TO GO OVER ANY COMMENTS WHICH MAY NOT BE
 CLEAR IN ANY MANNER. CONTACT INFORMATION IS BELOW. IF
 VOICE MAIL IS CONTACTED PLEASE BE SURE TO LISTEN TO
 MESSAGE AS I MAY NOT BE IN THE OFFICE.
 PLEASE LEAVE A MESSAGE WHEN CALLING AND THE CALL WILL
 BE RETURNED AS SOON AS POSSIBLE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717