| 2009-01-21 10:43:50 | 319 CLEMATIS ST. |
| | COMEAU, A RENAISSANCE HOTEL |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 09010006 |
| | ADD: 319 CLEMATIS ST |
| | CONT: PLAN REVIEW/ DAVID MILLER |
| | TEL: (561)358-4439 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. PLANS |
| | SUBMITTED FOR A PERMIT APPLICATION ON OR AFTER MARCH 1, |
| | 2009 WILL BE REVIEWED UNDER THE 2007 FBC BASE CODE. |
| | NOTE MAJOR WORKING DRAWINGS OR PLAN REVIEWS THAT HAVE |
| | NOT BEEN CONVERTED OVER TO A PERMIT APPLICATION BY THE |
| | END OF FEBRUARY 27TH WILL BE REVIEWED UNDER THE 2007 |
| | FBC. |
| | |
| | 1F) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2) ) THE PLANS THAT ARE CURRENTLY UNDER REVIEW WERE |
| | BROUGHT IN AS A MAJOR WORKING DRAWING REVIEW BEFORE |
| | PLANS ARE TO BE BROUGHT IN AS A PERMIT APPLICATION |
| | PLEASE HAVE THEM STAMPED BY HISTORIC PRESERVATION |
| | DIVISION INDICATING THERE APPROVAL. |
| | |
| | 3) 2004 EXISTING BUILDING CODE CHAPTER 10, 1005.1. |
| | STRICT COMPLIANCE, 1005.2 COMPLIANCE OPTIONS AND |
| | 1005.3. PLEASE REVIEW THESE CODE SECTIONS AND INDICATE |
| | WHICH OF THE LIFE SAFETY AND PROPERTY CONSERVATION |
| | OPTIONS SHALL BE PROVIDED IN ACCORDANCE WITH ONE OF THE |
| | FOLLOWING OPTIONS 1-3. PLEASE PROVIDE DOCUMENTATION FOR |
| | CODE COMPLIANCE FOR THE LISTED CODE SECTIONS ABOVE. |
| | |
| | 4) 2004 EXISTING BUILDING CODE CHAPTER 10, 1006.1. |
| | INVESTIGATION AND EVALUATION REPORT. |
| | AN HISTORIC BUILDING UNDERGOING ALTERATION OR CHANGE OF |
| | OCCUPANCY SHALL BE INVESTIGATED AND EVALUATED. IF IT IS |
| | INTENDED THAT THE BUILDING MEET THE REQUIREMENTS OF |
| | THIS CHAPTER, A WRITTEN REPORT SHALL BE PREPARED AND |
| | FILED WITH THE BUILDING OFFICIAL BY A |
| | FLORIDA-REGISTERED ARCHITECT OR ENGINEER. SUCH REPORT |
| | SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF SECTIONS |
| | 4.3.1.2 THROUGH 4.3.2 OF NFPA 914, CODE FOR FIRE |
| | PROTECTION OF HISTORIC STRUCTURES AND SHALL IDENTIFY |
| | EACH REQUIRED SAFETY FEATURE THAT IS IN COMPLIANCE WITH |
| | THIS CHAPTER AND WHERE COMPLIANCE WITH THIS OR OTHER |
| | CHAPTERS WOULD BE DAMAGING TO THE CONTRIBUTING HISTORIC |
| | FEATURES. IN ADDITION, THE REPORT SHALL DESCRIBE EACH |
| | FEATURE THAT IS NOT IN COMPLIANCE AND DEMONSTRATE HOW |
| | THE INTENT OF THE PROVISIONS OF THIS OR OTHER CHAPTERS |
| | ARE COMPLIED WITH IN PROVIDING AN EQUIVALENT LEVEL OF |
| | SAFETY. PLEASE PROVIDE COMPLIANCE WITH THIS SECTION. |
| | |
| | NOTE: SINCE WE HAVE NOT RECEIVED ANY INFORMATION |
| | CONCERNING COMMENT 3 NOR COMMENT 4 THIS REVIEW WILL BE |
| | COMPLETED AS 2004 EXISTING BUILDING CODE CHAPTER 8 |
| | CHANGE IN OCCUPANCY AND CHAPTER 9 ADDITIONS. TABLE |
| | 812.4.1 HAZARD CATEGORIES & CLASSIFICATION LIFE SAFETY |
| | & EXITS PLACES THIS BUILDING INTO A HIGHER HAZARD GROUP |
| | FROM A BUSINESS (4) TO A R-1 (3) OR HIGHER HAZARD |
| | CATEGORY (LOWER NUMBER) WHICH ENACTS CHAPTER 10 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | EXISTING BUILDING CODE 1004.1 HISTORIC BUILDINGS. |
| | EQUIVALENCY. NOTHING IN THIS CODE SHALL BE INTENDED TO |
| | PREVENT THE USE OF SYSTEMS, METHODS OR DEVICES OF |
| | EQUIVALENT OR SUPERIOR QUALITY, STRENGTH, FIRE |
| | RESISTANCE OR EFFECTIVENESS, PROVIDED THAT THE |
| | FOLLOWING CONDITIONS ARE MEET: |
| | 1. TECHNICAL DOCUMENTATION IS SUBMITTED TO THE BUILDING |
| | OFFICIAL TO DOCUMENT |
| | EQUIVALENCY. |
| | 2. THE SYSTEMS, METHOD OR DEVICE IS ACCEPTABLE TO THE |
| | BUILDING OFFICIAL. |
| | |
| | 5)THIS BUILDING IS TO BE CLASSIFIED AS A THRESHOLD |
| | BUILDING. : |
| | 5A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 5B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 5C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 5D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND FLOOR/ CEILING ASSEMBLY???S. |
| | |
| | 6) SHOW COMPLIANCE WITH: 903.3.1. 2004 EXISTING |
| | BUILDING CODE VERTICAL ADDITIONS, ANY ELEMENT OF THE |
| | LATERAL-FORCE-RESISTING SYSTEM OF AN EXISTING BUILDING |
| | SUBJECTED TO AN INCREASE IN VERTICAL OR LATERAL LOADS |
| | FROM THE VERTICAL ADDITION SHALL COMPLY WITH LATERAL |
| | LOAD PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 7) INFORMATIONAL; 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 8) INFORMATIONAL: 109.3.10.1 HURRICANE PROTECTION. IT |
| | SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| | RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| | OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| | HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 9) TABLE 503OF THE FBC INDICATES THE MINIMUM BUILDING |
| | TYPE CONSTRUCTION TO BE TYPE 1-B |
| | CONSTRUCTION R-1 OCCUPANCY 11 STORIES. |
| | |
| | 9A) THE COVERSHEET INDICATES THIS PROJECT AS A TYPE |
| | III-A , 12 STORY, BASEMENT INCLUSIVE. |
| | WHERE AS THE LIFE SAFETY SHEETS INDICATE THE BUILDING |
| | CONSTRUCTION TYPE AS TYPE II-B AND 10 STORIES. |
| | |
| | 9B) THERE ARE TWO ISSUES WHEN CONSIDERING THE HEIGHT OF |
| | THE BUILDING (1) THE BASEMENT IS NOT TO BE CONSIDERED A |
| | STORY WHEN CALCULATING THE HEIGHT OF A BUILDING PER |
| | SECTION 503.1.1. |
| | THE SECOND ISSUE IS THE NEW POOL DECK AND RESTROOMS, |
| | PLEASE REVIEW 1509.2. |
| | 1509.2 PENTHOUSES OR BULKHEADS USED FOR PURPOSES OTHER |
| | THAN PERMITTED BY THIS SECTION SHALL CONFORM TO THE |
| | REQUIREMENTS OF THIS CODE FOR AN ADDITIONAL STORY. THE |
| | PLANS WITH THE NEW POOL DECK BEING THE 11TH STORY WILL |
| | MEET THE REQUIREMENTS FOR A TYPE 1-B BUILDING. |
| | |
| | 9C) THE QUESTION IS WAS THE STRUCTURE BUILT YEARS AGO |
| | AS A TYPE III-A STRUCTURE OR WAS THIS A MISPRINT? |
| | PLEASE CORRELATE PLANS TO REFLECT THE SAME BUILDING |
| | TYPE FOR THE COMPLETE SET OF PLANS. |
| | |
| | 10) THE LIFE SAFETY PLANS INDICATE THE STRUCTURE TO BE |
| | WITHIN A FIRE DISTRICT, UNDER THE 2004 FBC THERE IS NO |
| | LONGER FIRE DISTRICTS. PLEASE UPDATE. |
| | |
| | 11) THE LIFE SAFETY SHEETS ALSO INDICATE UNDER THE |
| | BUILDING CODE ANALYSIS FIRE RESISTANCE RATING AND |
| | NOTATION N/A ASSUMING THIS MEANS NOT APPLICABLE? PLEASE |
| | REVIEW |
| | EXISTING BUILDING CODE TABLE 812.4.2 AND SECTION |
| | 812.4.2.1 AS WELL AS TABLE 601 FBC FOR FIRE-RESISTANCE |
| | RATING REQUIREMENTS FOR BUILDING ELEMENTS IN HOURS. |
| | |
| | 12) LIFE SAFETY PLANS DOES NOT INDICATE THE RATING FOR |
| | TENANT SEPARATION WALLS (708.1(5), OCCUPANCY SEPARATION |
| | (TABLE 302.3.2), SHAFT WALL CONSTRUCTION (707.2), RATED |
| | WALLS FOR FIRE COMMAND CENTER (403./ 911.1), EXIT |
| | ACCESS CORRIDORS (TABLE 1016.1) NOR VERTICAL EXIT |
| | ENCLOSURES (1019.1.) THIS LIST IS NOT INCLUSIVE BUT A |
| | SAMPLING OF WHAT WALLS ARE INDICATED ON LIFE SAFETY |
| | PLANS AS WELL AS ARCHITECTURAL PLANS. |
| | |
| | 13) LIFE SAFETY PLANS ALSO INDICATE DEAD END CORRIDORS |
| | MAXIMUM CONDITION OF 75 FEET. PLEASE REVIEW 2004 FBC |
| | EXISTING BUILDING CODE 812.4.1.1(6) EXISTING DEAD-END |
| | CORRIDORS SHALL COMPLY WITH THE REQUIREMENTS IN SECTION |
| | 605.6 OF THE EXISTING BUILDING CODE.2004 EXISTING |
| | BUILDING CODE 605.6 DEAD-END CORRIDORS IN ANY WORK AREA |
| | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 1016.3 |
| | FLORIDA BUILDING CODE, BUILDING. |
| | 2004 FBC BUILDING 1016.3 THE MAXIMUM LENGTH OF DEAD END |
| | IN CORRIDORS NO MORE THAN 20 FEET IN LENGTH: |
| | EXCEPTIONS: |
| | 1) GROUP I-3 50 FEET |
| | 2) B & F OCCUPANCIES 50 FEET |
| | 3) DEAD END CORRIDORS SHALL NOT BE LIMITED IN LENGTH |
| | WHERE THE LENGTH OF THE DEAD END CORRIDOR IS LESS THAN |
| | 2.5 TIMES THE LEAST WIDTH OF THE DEAD END CORRIDOR. |
| | NOTE WHERE THERE IS A DIFFERENCE BETWEEN CODES AND OR |
| | STANDARDS THE MOST STRINGENT SHALL APPLY, 102.4*. |
| | |
| | 14) LIFE SAFETY PLANS INDICATE COMMON PATH OF TRAVEL |
| | MAXIMUM LENGTH OF 100 FEET. PLEASE DEFINE COMMON PATH |
| | OF TRAVEL BY OCCUPANCY FOR SPRINKLED BUILDINGS, EXAMPLE |
| | 1013.3 (6) GROUP R1-R2 FULLY SPRINKLED BUILDING COMMON |
| | PATH OF TRAVEL SHALL NOT EXCEED 50 FEET. |
| | |
| | 15) LIFE SAFETY PLANS INDICATE THE MAXIMUM TRAVEL |
| | DISTANCE TO AN EXIT IS 200 FEET PLEASE REVIEW TABLE |
| | 1015.1 BY OCCUPANCY. |
| | |
| | 16) LIFE SAFETY PLAN, OCCUPANCY AND EGRESS ANALYSIS, IS |
| | MISSING THE SQUARE FOOTAGE FOR |
| | EACH OF THE AREAS SERVED . THE OCCUPANCY COUNT CAN???T |
| | BE VERIFIED. TABLE 1004.1.2 TIES TO FLOOR AREA IN |
| | SQUARE FOOTAGE. |
| | |
| | 17) SHEET B-1.0 VERSES A30.0 THE DETAILED BASEMENT PLAN |
| | WALL RATING DO NOT MATCH OR THERE IS NO WALL TAG RATING |
| | THE WALL. EXAMPLE B-1.0 THE TWO HR RATED STAIRS IS |
| | MISSING THE RATING TO THE WALL JUST RIGHT OF DOOR# 801 |
| | IT IS INDICATED ON THE WALL LEGEND AS A NEW WALL. |
| | THE DETAILED PLAN A30.0 DOES NOT PROVIDE ANY WALL |
| | RATING OF THE STAIRWELL AT ALL. |
| | |
| | 18) SHEET A30.0 THE DETAILED BASEMENT PLAN DOES NOT |
| | PROVIDE ANY DOOR IDENTIFICATION TAGS AT ALL. YOU HAVE |
| | TO GO BACK TO THE 1/8 INCH SCALE PLAN. |
| | |
| | 19) BOTH SHEET B-1.0 AND A-30.0 INDICATE ROOM 005 AS |
| | SOILED LAUNDRY HOLDING ROOM. WITH A WALL RATING OF 1 HR |
| | SHEET A-30.0 INDICATES A WALL TAG TYPE (1) BLOCK WALL |
| | WITH 1 5/8 METAL STUDS AND DRYWALL, THE PLANS ARE NOT |
| | DRAWN WITH THIS TYPE OF CONFIGURATION. THIS IS COMMON |
| | FOR THIS LEVEL. |
| | |
| | 20) IN BOTH SHEETS B-1.0 AND A-30.0 ROOM # 005 ALSO |
| | HOLDS THE LINEN CHUTE WHICH DOES NOT INDICATE A 2HR |
| | SHAFT BUT DETAIL# 4 SHEET A-43.1 DOES INDICATE. PLEASE |
| | PROVIDE WALL TAG MARKERS INDICATING TYPE OF SHAFT WALL |
| | CONSTRUCTION. |
| | |
| | 21) LINEN CHUTE DETAIL# 4 SHEET A-43.1 DOE NOT INDICATE |
| | COMPLIANCE WITH THE REQUIREMENTS OF 707.13.6 AND |
| | 903.2.10.2. REQUIRED FIRE SPRINKLERS. |
| | |
| | 22) SHEET A-1.0 THE FIRST FLOOR AND MEZZANINE LEVELS, |
| | NONE OF THE WALLS ARE IDENTIFIED WITH WALL TAGS. IN |
| | REVIEWING ALL FLOOR PLANS NO WALLS ARE MARKED WITH WALL |
| | IDENTIFICATION TAGS, THIS COMMENT WILL STAND FOR ALL |
| | FLOORS. TENANT SEPARATION WALLS (708.1(5), OCCUPANCY |
| | SEPARATION (TABLE 302.3.2), SHAFT WALL CONSTRUCTION |
| | (707.2), RATED WALLS FOR FIRE COMMAND CENTER (403./ |
| | 911.1), EXIT ACCESS CORRIDORS (TABLE 1016.1) NOR |
| | VERTICAL EXIT ENCLOSURES (1019.1.) THIS LIST IS NOT |
| | INCLUSIVE. |
| | |
| | 23) SHEET A-1.0 FIRST FLOOR AND MEZZANINE FLOOR BOTH |
| | INDICATE TWO EXIT ENCLOSURES, NEITHER HAVE |
| | IDENTIFICATION TAGS OR NUMERALS. THE EXIT STAIRWAY THAT |
| | IS CENTERED WITHIN THE BUILDING AND CONTINUES TO THE |
| | ROOF TOP POOL DECK. SECTION 1019.1.8.1 A SMOKE PROOF |
| | ENCLOSURE OR PRESSURIZED STAIRWAY SHALL EXIT INTO A |
| | PUBLIC WAY OR INTO AN EXIT PASSAGEWAY, YARD OR OPEN |
| | SPACE HAVING DIRECT ACCESS TO THE PUBLIC WAY. 1019.1.8 |
| | ALSO REQUIRES SMOKE PROOF ENCLOSURES. 403.13 SMOKE |
| | PROOF EXIT ENCLOSURES. |
| | EVERY REQUIRED STAIRWAY SERVING FLOORS MORE THAN 75 |
| | FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE |
| | DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH SECTIONS |
| | 909.20 AND 1019.1.8. |
| | |
| | |
| | 24) ON THE MEZZANINE LEVEL PLAN THERE APPEARS TO BE 5 |
| | COLUMNS MISSING: |
| | 24A) GRIDLINES MIDWAY BETWEEN 5 & 6, & ROW A IN ROOM |
| | 156 |
| | 24B) GRIDLINES MIDWAY BETWEEN 5 & 6, & ROW C IN ROOM |
| | 159 AT DOOR 156 |
| | 24C) GRIDLINE5 AND ROW C COLUMN MISSING IN A?C UNIT |
| | 24D & E) MECHANICAL ROOM152 EXTERIOR WALL |
| | ARE THESE COLUMNS BEING REMOVED OR WAS A LAYER JUST |
| | TURNED OFF? ADDITIONAL INFORMATION REQUIRED 106.1.2. |
| | |
| | 25A) SHEET A-1.0 THE MEETING ROOM 114 TWO ISSUES PLANS |
| | INDICATE COLUMN TO BE REMOVED S-2 ALSO INDICATES THE |
| | REMOVAL OF THIS COLUMN BUT THERE IS NO MENTION OF HOW |
| | TO REINFORCE THE FLOOR SYSTEM ABOVE. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 25B) THE SECOND ISSUE IS THE FOLDING DOOR SYSTEM |
| | SEPARATING ROOM 114 INTO A & B, IN EACH ROOM THE |
| | OCCUPANT LOAD WOULD STILL BE ABOVE 70 OCCUPANTS IN EACH |
| | ROOM REQUIRING TWO EXITS? TABLE 1014.1. |
| | |
| | 26) THERE ARE AREAS OF CONCERN IN THE BACK OF HOUSE AND |
| | MEZZANINE LEVELS SHOW COMPLIANCE WITH; |
| | GENERATOR ROOM 2HR. NFPA 110.7.2.1.2/ NFPA 110.7.2.2 |
| | FIRE PUMP ROOM 2HR NFPA 20.5.12.1.1 |
| | MAIN ELECTRIC ROOM NFPA 13.8.14.10 |
| | |
| | 27) SHEET A-1.0 THE NUMBERED DOORS LISTED ARE MISSING |
| | THE REQUIRED 18??? ON THE PULL SIDE OF LATCH 11-4.13.6. |
| | DOORS; 103, 124, 125, 127,131, 145 & 153. |
| | |
| | 28) SHOW COMPLIANCE WITH: FIRE COMMAND CENTER 911.1 |
| | FEATURES. |
| | WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, A FIRE |
| | COMMAND CENTER FOR FIRE DEPARTMENT OPERATIONS SHALL BE |
| | PROVIDED. THE LOCATION AND ACCESSIBILITY OF THE FIRE |
| | COMMAND CENTER SHALL BE SEPARATED FROM THE REMAINDER OF |
| | THE BUILDING BY NOT LESS THAN A 1-HOUR |
| | FIRE-RESISTANCE-RATED FIRE BARRIER. THE ROOM SHALL BE A |
| | MINIMUM OF 96 SQUARE FEET (9 M2) WITH A MINIMUM |
| | DIMENSION OF 8 FEET (2438 MM). A LAYOUT OF THE FIRE |
| | COMMAND CENTER AND ALL FEATURES REQUIRED BY THE SECTION |
| | TO BE CONTAINED THEREIN SHALL BE SUBMITTED FOR APPROVAL |
| | PRIOR TO INSTALLATION. THE FIRE COMMAND CENTER SHALL |
| | COMPLY WITH NFPA 72 AND SHALL CONTAIN THE FOLLOWING |
| | FEATURES. |
| | 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT. |
| | 2. THE FIRE DEPARTMENT COMMUNICATIONS UNIT. |
| | 3. FIRE DETECTION AND ALARM SYSTEM ENUNCIATOR UNIT. |
| | 4. ENUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL. |
| | 5. STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS. |
| | 6. THE FIRE-FIGHTER???S CONTROL PANEL REQUIRED BY |
| | SECTION 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN |
| | THE BUILDING. |
| | 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY. |
| | 8. SPRINKLER VALVE AND WATER-FLOW DETECTOR DISPLAY |
| | PANELS. |
| | 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS. |
| | 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM. |
| | 11. FIRE PUMP STATUS INDICATORS. |
| | 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS. |
| | 13. WORKTABLE. |
| | 14. GENERATOR SUPERVISION DEVICES, MANUAL START AND |
| | TRANSFER FEATURES. |
| | 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE. |
| | |
| | 29) SHEET A-2.0 THIS COMMENT WILL STAND FOR ALL FLOORS. |
| | PLANS FAIL TO INDICATE RATED WALLS |
| | PLANS ARE MISSING WALL IDENTIFICATION TAGS. SECTION |
| | 1016.1/ TABLE 1016.01 REQUIRE A ONE HOUR FIRE RATED |
| | CORRIDOR FOR RESIDENTIAL OCCUPANCY WHEN THE CORRIDOR |
| | SERVES A OCCUPANT LOAD GREATER THAN 10. |
| | |
| | 30) SHEET A-2.0 COMMON TO ALL FLOORS 2ND THROUGH 10TH |
| | FLOOR. MISSING ELEVATOR LOBBY 714.1. SEE CODE |
| | COMMENTARY. ALL FIVE STORY AND HIGHER FULLY SPRINKLED |
| | BUILDINGS OF GROUPS H, I-1 AND R. |
| | |
| | 707.14.1 ELEVATOR LOBBY. |
| | ELEVATORS OPENING INTO A FIRE-RESISTANCE-RATED CORRIDOR |
| | AS REQUIRED BY SECTION 1016.1 SHALL BE PROVIDED WITH AN |
| | ELEVATOR LOBBY AT EACH FLOOR CONTAINING SUCH A |
| | CORRIDOR. THE LOBBY SHALL SEPARATE THE ELEVATORS FROM |
| | THE CORRIDOR BY FIRE PARTITIONS AND THE REQUIRED |
| | OPENING PROTECTION. ELEVATOR LOBBIES SHALL HAVE AT |
| | LEAST ONE MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND |
| | OTHER PROVISIONS WITHIN THIS CODE. |
| | |
| | |
| | 31) SHEET A-2.0 IT-ROOM (201A) PLANS FAIL TO IDENTIFY |
| | THIS ROOM WITH WALL TAGS, THE NEC SECTION 645.2 |
| | INDICATES THESE WALLS ARE TO BE 1HR RATED WITH OPENING |
| | PROTECTIVE???S. THIS COMMENT WILL STAND FOR ALL FLOORS. |
| | |
| | 32) SHEET A-2.00 THIS COMMENT WILL STAND FOR ALL FLOORS |
| | THE ROOM# 201 SERV. ROOM ALSO HAS THE LINEN CHUTE |
| | LOCATED WITHIN THIS ROOM. PLANS FAIL TO INDICATE SHAFT |
| | WALL CONSTRUCTION 707.13.1 AND THE ACCESS ROOM DOES NOT |
| | INDICATE ANY RATING, NO WALL TAGS ARE APPERANT707.13.3. |
| | |
| | 33) SHEET A-2.0 THE SECOND FLOOR UNITS APPEAR TO HAVE |
| | ROOF TOP PATIOS WITH ROOF DRAINS BUT THE PLANS DO NOT |
| | PROVIDE DETAILS INDICATING EMERGENCY OVERFLOWS OR |
| | SCUPPERS1503.4.2 & 1503.4.3. |
| | |
| | 34) SHEET A-2.0. THERE IS NO DETAILS OF DIFFERENCE IN |
| | HEIGHT FROM THE INTERIOR ELEVATION TO THE DECK OR |
| | PATIO. 11-4.1.7.1. |
| | |
| | 35) SHEET A-2.0 THE BACK OF HOUSE STAIR ON THE SECOND |
| | FLOOR THROUGH TO THE 10TH FLOOR ARE A EXTERIOR TYPE OF |
| | STAIR THE FIRST ISSUE IS WINDOWS AND OR OPENINGS WITHIN |
| | 10???-0??? OF THE OPENING NEED TO BE RATED.. |
| | |
| | 1022.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. |
| | EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED |
| | FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN |
| | SECTION 1019.1. OPENINGS SHALL BE LIMITED TO THOSE |
| | NECESSARY FOR EGRESS FROM NORMALLY OCCUPIED SPACES. |
| | |
| | 1019.1.4 VERTICAL ENCLOSURE EXTERIOR WALLS. |
| | EXTERIOR WALLS OF A VERTICAL EXIT ENCLOSURE SHALL |
| | COMPLY WITH THE REQUIREMENTS OF SECTION 704 FOR |
| | EXTERIOR WALLS. WHERE NONRATED WALLS OR UNPROTECTED |
| | OPENINGS ENCLOSE THE EXTERIOR OF THE STAIRWAY AND THE |
| | WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE |
| | BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES (3.14 |
| | RAD), THE BUILDING EXTERIOR WALLS WITHIN 10 FEET (3048 |
| | MM) HORIZONTALLY OF A NONRATED WALL OR UNPROTECTED |
| | OPENING SHALL BE CONSTRUCTED AS REQUIRED FOR A MINIMUM |
| | 1-HOUR FIRE-RESISTANCE RATING WITH ??-HOUR OPENING |
| | PROTECTIVE???S. THIS CONSTRUCTION SHALL EXTEND |
| | VERTICALLY FROM THE GROUND TO A POINT 10 FEET (3048 MM) |
| | ABOVE THE TOPMOST LANDING OF THE STAIRWAY OR TO THE |
| | ROOF LINE, WHICHEVER IS LOWER. |
| | |
| | 1022.2 USE IN A MEANS OF EGRESS. EXTERIOR EXIT RAMPS |
| | AND STAIRWAYS SHALL NOT BE USED AS AN ELEMENT OF A |
| | REQUIRED MEANS OF EGRESS FOR OCCUPANCIES IN GROUP I-2. |
| | FOR OCCUPANCIES IN OTHER THAN GROUP I-2, EXTERIOR EXIT |
| | RAMPS AND STAIRWAYS SHALL BE PERMITTED AS AN ELEMENT OF |
| | A REQUIRED MEANS OF EGRESS FOR BUILDINGS NOT EXCEEDING |
| | FOUR STORIES OR 75 FEET (22 860 MM) IN HEIGHT. |
| | |
| | 36) THE EAST SIDE OF THE 2ND FLOOR CORRIDOR SYSTEM DOES |
| | NOT PROVIDE ANY EGRESS LIGHTS OR SIGNAGE TO AN EXIT. |
| | 1006.3. |
| | |
| | 37) SHEET A-3.0 THE WINDOWS AND EXTERIOR DOORS HAVE |
| | IDENTIFICATION TAGS BUT NOT FILED IN. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 38) SHEET A-3.0 EXTERIOR GUARD RAIL SYSTEM, PLANS DO |
| | NOT INDICATE IF THESE ARE NEW OR EXISTING PLEASE REVIEW |
| | 1607.1 HANDRAIL AND GUARDS AND 1607.7.1.1 CONCENTRATED |
| | LOADS. |
| | |
| | 39) SHEETS A-3.0 THROUGH THE 10TH FLOOR IT APPEARS |
| | THERE IS A CHASE AT ROOM X 21 OF EACH FLOOR PLEASE |
| | PROVIDE WALL TAG IDENTIFYING WALL TYPE, SHAFT WALL |
| | CONSTRUCTION REQUIRES 2 HR |
| | CONSTRUCTION. 707.4. |
| | |
| | 40) SHEET A-4.0 NORTH EXTERIOR STAIRS IS MISSING THE |
| | MID LANDING? 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 41) SHEET A-11.0 THE NORTH OR EXTERIOR STAIRWAY HAS TWO |
| | DOORS WITHIN THE TOP LANDING ; |
| | 1) STORAGE ROOM R105 |
| | 2) R103 MECHANICAL ROOM ACCESS |
| | 1022.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. |
| | EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED |
| | FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN |
| | SECTION 1019.1. OPENINGS SHALL BE LIMITED TO THOSE |
| | NECESSARY FOR EGRESS FROM NORMALLY OCCUPIED SPACES. |
| | 1019.1 SPEAKS AS TO ENCLOSED STAIRWAYS BUT THE INTENT |
| | IS AN EXIT ENCLOSURE SHALL NOT BE USED FOR ANY PURPOSE |
| | OTHER THAN MEANS OF EGRESS. |
| | |
| | 42) SHEET A-11.0 DETAIL A/ A-11.1 IT APPEARS TO BE |
| | MISLABELED, I BELIEVE THIS IS TO REPRESENT A GLASS HAND |
| | RAIL DETAIL FOUND ON A-11.02 DETAIL A. MISPRINT |
| | |
| | 43) SHEET A-11.0 ALSO HAS TO DETAILS D& E THAT ARE TO |
| | BE FOUND ON A-11.2 BUT ARE MISSNG.106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED |
| | |
| | 44) SHEET A-11.0 LOWER ROOF DETAIL INDICATES WHAT |
| | APPEARS FIBERGLASS PLANTERS NEXT TO THE PLANTERS THERE |
| | APPEARS TO BE A 12???X12??? SQUARE? 106.1.2 ADDITIONAL |
| | INFORMATION. |
| | |
| | 45) A-11.0 THE DOOR FROM EACH STAIRWELL IS MISSING THE |
| | 18??? PULL SIDE OF THE DOOR.11-4.13.6. |
| | |
| | 46) SHEET A-11.0 INDICATES A AWNING BUT PLANS DO NOT |
| | INDICATE ANY DESIGN INFORMATION. WILL REQUIRE A |
| | SEPARATE PERMIT, REVIEW AND FEES. |
| | |
| | 47) SHEET A-11.0 INDICATES THE USE OF GLASS GUARD |
| | RAILS, PLEASE PROVIDE COMPLIANCE WITH |
| | 2407.1, 2407.1.1 LOADS, 2407.1.2 SUPPORTS. |
| | |
| | 48) SHEET A-11.0 DOES NOT PROVIDE ANY FENCING AROUND |
| | THE POOL AS REQUIRED IN 424.1.3.1.9 |
| | 424.1.3.1.9 ALL PUBLIC POOLS SHALL BE SURROUNDED BY A |
| | MINIMUM 48 INCH (1219 MM) IN HEIGHT FENCE. THE FENCE |
| | SHALL BE CONTINUOUS AROUND THE PERIMETER OF THE POOL |
| | AREA THAT IS NOT OTHERWISE BLOCKED OR OBSTRUCTED BY |
| | ADJACENT BUILDINGS OR STRUCTURES AND SHALL ADJOIN WITH |
| | ITSELF OR ABUT TO THE ADJACENT MEMBERS. ACCESS THROUGH |
| | THE BARRIER OTHER THAN FROM DOORED EXITS OF ADJACENT |
| | BUILDING(S) SHALL BE THROUGH SELF-CLOSING, |
| | SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM) |
| | MINIMAL HEIGHT WITH THE LATCH LOCATED NEAR THE TOP. |
| | |
| | 49) THE POOL AND WATER FEATURE WILL ALSO REQUIRE A |
| | SEPARATE PERMIT, REVIEW AND FEES. |
| | |
| | 50) A-11.0 PLANS DO NOT TRULY INDICATE THE POOL AND SPA |
| | EQUIPMENT, IS THERE GOING TO BE A SEPARATE SPA, OR IS |
| | THIS THE WATER FEATURE, ADDITIONAL INFORMATION |
| | REQUIRED, 106.1.2. |
| | |
| | 51) SHEET A-11.3 INDICATES THE PROPOSED WATER FEATURE |
| | TO BE PART OF A NEW STRUCTURE WITH WHAT APPEARS TO HAVE |
| | CLAY TILE. SINCE THIS BUILDING IS CLAIMING HISTORICAL |
| | SIGNIFICANCE WHAT TYPE OF ROOF TILE WILL BE USED? |
| | EXISTING BUILDING CODE APPENDIX B . |
| | |
| | 52) SHEET A-15.0 WINDOW AND LOUVER TYPES, THERE HAS |
| | BEEN NO SCHEDULE DEVELOPED FOR THE WINDOWS NOR LOUVERS. |
| | MISSING INFORMATION IS THE SIZE OF WINDOWS(ENTRY) IF |
| | WINDOWS ARE FIRE RATED, TYPE OF WINDOW, LARGE MISSILE, |
| | SMALL MISSILE OR RATED JUST FOR WIND PRESSURE, POSITIVE |
| | AND NEGATIVE PRESSURES, ZONE LOCATION 4 OR 5. |
| | ADDITIONAL INFORMATION REQUIED.106.1.2./ 1609.6.2.2 |
| | COMPONENTS AND CLADDING, & RULE 9B-72. |
| | |
| | 53) SHEET A-15.1 PLEASE PROVIDE THE LOCATION OF THE |
| | PROPERTY LINE THE PLANS INDICATE DOORS THAT APPEAR TO |
| | PROTRUDE PAST THE PROPERTY LINE. 3202.2. |
| | |
| | 54) SHEET A-15.1 PLANS INDICATE A DROPPED CURB OR FLUSH |
| | CURB AT THE DROP OFF ZONE PLEASE |
| | INDICATE COMPLIANCE WITH 11-4.29.5. |
| | |
| | 55) SHEET A-15.1 INDICATE A DETAILED MARQUEE PLAN BUT |
| | THERE IS NO INFORMATION FOR THIS DESIGN, MISSING WIND |
| | INFORMATION AS WELL AS FOUNDATION, COLUMNS FRAMING AND |
| | TYPE OF GLAZING REQUIRED FOR SLOPED GLAZING. |
| | 1609.61609.6.1.1/ 2405.2. |
| | |
| | 56) SHEET A-15.1 AS A POINT FOR REFERENCE ALTHOUGH THE |
| | FIRST FLOOR TENANT SPACES ARE TO BE UNDER A SEPARATE |
| | PERMIT WILL THE EXTERIOR STOREFRONTS TO BE PART OF THIS |
| | PERMIT? 106.1.2. |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | |
| | 57) A-18.01 DETAIL 3 & 4 INDICATES PART OF A WALL AND |
| | SLAB TO BE REMOVED A NEW CURB AND SLOPED ROOF TOP |
| | INSULATION. SINCE NO ENERGY CALCULATIONS WERE SUBMITTED |
| | PLEASE BE AWARE WHATEVER IS LISTED IN THE INPUT DATA |
| | REPORT AS A REQUIRED MINIMUM THAT IS WHAT WILL BE |
| | REQUIRED AT THE LOWEST POINT WITHIN THE ROOF SYSTEM AND |
| | INSULATION SHALL SLOPE UP FROM THERE. 13-404.1ABCD.1 |
| | AND INFORMAL BOAF INTERPRETATION 3746. |
| | |
| | 58) A-18.01 DETAIL# 6 INDICATES THE USE OF DROPPED |
| | CEILINGS AND SOFFITS PLEASE PROVIDE TYPE OF ANCHORS TO |
| | THE STRUCTURE ABOVE. 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED/ 2508.1 TABLE/ STEEL FRAMING FOR GYPSUM BOARDS |
| | . |
| | |
| | 59) A-21.01 DETAIL INDICATES THE UNIT SEPARATION WALL |
| | OR TENANT SEPARATION WALL AS A WALL TYPE (1) ON THE |
| | WALL SCHEDULE FOUND ON A-42.4 THIS IS A BLOCK WALL AND |
| | 1 5/8 METAL STUD AND DRYWALL ON ONE SIDE THIS DOES NOT |
| | APPEAR TO BE CORRECT. WALL TYPE# 1 IS INDICATED AS A |
| | EXTERIOR WALL, ALSO DOES NOT PROVIDE A STC RATING. SEE |
| | SECTION 1207.2. THIS WALL TYPE ALSO DOES NOT PROVIDE |
| | ANY WALL RATINGS. |
| | |
| | 60) A-21.01 THE CORRIDOR WALLS ARE INDICATES WITH A |
| | WALL TAG # 2 OR AT BACK OF HOUSE EXTERIOR WALL. AGAIN |
| | IT APPEARS TO BE THE WRONG WALL DESIGNATION AND NO STC |
| | RATING, SEE SECTION 1207.2. THIS WALL TYPE DOES NOT |
| | PROVIDE ANY WALL RATINGS. |
| | |
| | 61) SHEET A-36.0 DETAIL# 1 IS OF THE FITNESS CENTER BUT |
| | THE STAIRWELL WALLS THAT ARE INCLUDED INDICATE A 2HR |
| | RATING ON ONE SIDE OF THE STAIRWELL AND NO RATING ON |
| | THE OTHER SIDE. PLEASE SEE SECTION 1019.1. |
| | |
| | 62) SHEET A-36.0 INDICATES IN SOME WALLS WALL RATINGS |
| | BUT DOES NOT INDICATE WITH WALL TAGS THE TYPE OF WALL, |
| | RATING FOR FIRE, SMOKE NOR STC RATINGS. 708.1(2), |
| | 1019.1 AND 1207.2. THIS COMMENT WILL STAND FOR ALL |
| | A-3X.X SHEETS. |
| | |
| | 63) SHEET A42.2 THE DOOR SCHEDULE INDICATES TYPE OF |
| | DOOR HARDWARE AS SET NUMBERS, NO INFORMATION HAS BEEN |
| | PROVIDED AT THIS TIME. 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED, |
| | AND SECTION 1008. |
| | |
| | 64) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | |
| | 65) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | 65A) WINDOWS- CASEMENT WINDOWS |
| | 65B) WINDOWS- SINGLE HUNG WINDOWS |
| | 65C) FIXED SIDE LIGHTS/ STOREFRONT UNITS |
| | 65D) MULLIONS |
| | 65E) EXTERIOR INSULATED METAL DOORS |
| | 65F) EXTERIOR METAL/ GLAZED BI-PASS DOORS, AND |
| | SIDELIGHTS/ BREAK AWAY PANELS |
| | 65G) EXTERIOR METAL LOUVER DOORS |
| | 65H) EXTERIOR FOLDING DOOR SYSTEMS |
| | 65I) EXTERIOR GLAZED DOORS & SIDELIGHTS |
| | 65J) WALL LOUVERS |
| | 65K) PRE-ENGINEERED A/C STANDS |
| | 65L) ROOFING ASSEMBLIES |
| | 65M) ROOF HATCH |
| | |
| | 66) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 67) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 68) MISSING INFORMATION ON PLANS, I COULD NOT FIND THE |
| | POSITIVE AND NEGATIVE WIND PRESSURES FOR WINDOWS AND |
| | DOORS ON THE ELEVATION SHEETS, WINDOW NOR DOOR SHEETS. |
| | PLEASE PROVIDE THE INTERIOR AND END ZONE PRESSURES FOR |
| | THESE ZONES, INCLUDE HEIGHT AND EXPOSURE FACTORS WITHIN |
| | THE PRESSURES. TABLE 1609.6.2.1(2) |
| | |
| | 69) THE OTHER INFORMATION FOR WIND THAT WAS NOT |
| | AVAILABLE: |
| | 1609.6.2 WIND DESIGN PROCEDURES |
| | 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. |
| | THE WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL |
| | DIRECTION. |
| | |
| | 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE |
| | 1609.6.2.1(4) |
| | |
| | 70) SHEET A-12.0 INDICATES THE USE OF A NEW AWNING OR |
| | CANOPY, ALTHOUGH THIS WILL BE |
| | |
| | REVIEWED UNDER A SEPARATE PERMIT PLEASE BE AWARE OF THE |
| | WIND DESIGN CRITERIA: |
| | 3105.4.2 |
| | DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL BE BASED |
| | ON RATIONAL ANALYSIS, USING THE APPLICABLE WIND LOADS |
| | OF CHAPTER 16 AS SHOWN BELOW: |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| | CRITERIA: |
| | 1. MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90 MPH |
| | 2. IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN LIFE |
| | OF 0.77. |
| | 3. EXPOSURE CATEGORY B FOR OR C AS DEFINED IN CHAPTER |
| | 16. |
| | 3105.4.2.2 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE |
| | COVERED STRUCTURE DESIGNED WITH A PERMANENT OR |
| | NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE |
| | FOLLOWING CRITERIA: |
| | 1. MINIMUM WIND VELOCITY AS REQUIRED IN CHAPTER 16. |
| | 2. IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN LIFE |
| | OF 0.77. |
| | 3. EXPOSURE CATEGORY B OR C AS DEFINED IN CHAPTER 16. |
| | A LETTER FROM THE OWNER (NOT TENANT) IS TO ACCOMPANY |
| | ALL FABRIC OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH |
| | A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO |
| | ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE THE AWNING |
| | COVER REMOVED PRIOR TO ANY WIND EVENT WITH PROJECTED |
| | WIND SPEEDS OF 75 MPH OR GREATER. THE LETTER MUST BE |
| | SIGNED BY THE OWNER NOT TENANT. |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, |
| | |
| | 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS. |
| | 3105.5.1 LOADS. |
| | RIGID AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO |
| | RESIST THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE |
| | EXCEPT THAT STRUCTURES OR PARTS THEREOF WHICH ARE |
| | INTENDED TO BE REMOVED OR REPOSITIONED DURING PERIODS |
| | OF HIGH WIND VELOCITY SHALL BE DESIGNED IN THEIR OPEN |
| | OR EXTENDED POSITION TO DESIGN PRESSURES BASED ON A |
| | BASIC WIND SPEED OF MINIMUM 90 MPH, 3-SECOND WIND GUST |
| | WITH APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS |
| | THAN 10 PSF (478 PA) ROOF LIVE LOAD. |
| | 3105.5.3 |
| | STRUCTURES DESIGNED TO BE READILY REMOVED OR |
| | REPOSITIONED DURING PERIODS OF HIGH WIND VELOCITY SHALL |
| | BE POSTED WITH A LEGIBLE AND READILY VISIBLE DECAL OR |
| | PAINTED INSTRUCTIONS TO THE OWNER OR TENANT TO REMOVE |
| | OR REPOSITION THE STRUCTURE OR PART THEREOF DURING SUCH |
| | PERIODS OF TIME AS ARE DESIGNATED BY THE U.S. WEATHER |
| | BUREAU AS BEING A HURRICANE WARNING OR ALERT. |
| | |
| | 71) SHEET A-42.4 WALL TYPES INTERIOR PARTITION TYPE 1-4 |
| | DO NOT PROVIDE A UL LISTING OR OTHER AGENCY PROVIDING A |
| | TESTED ASSEMBLY FOR FIRE RESISTANCE RATINGS AND FOR |
| | SOUND. |
| | . 703.2 FIRE-RESISTANCE RATINGS. |
| | THE FIRE-RESISTANCE RATING OF BUILDING ELEMENTS SHALL |
| | BE DETERMINED IN ACCORDANCE WITH THE TEST PROCEDURES |
| | SET FORTH IN ASTM E 119 OR IN ACCORDANCE WITH SECTION |
| | 703.3. WHERE MATERIALS, SYSTEMS OR DEVICES THAT HAVE |
| | NOT BEEN TESTED AS PART OF A FIRE-RESISTANCE-RATED |
| | ASSEMBLY ARE INCORPORATED INTO THE ASSEMBLY, SUFFICIENT |
| | DATA SHALL BE MADE AVAILABLE TO THE BUILDING OFFICIAL |
| | TO SHOW THAT THE REQUIRED FIRE-RESISTANCE RATING IS NOT |
| | REDUCED. MATERIALS AND METHODS OF CONSTRUCTION USED TO |
| | PROTECT JOINTS AND PENETRATIONS IN |
| | FIRE-RESISTANCE-RATED BUILDING ELEMENTS SHALL NOT |
| | REDUCE THE REQUIRED FIRE-RESISTANCE RATING. |
| | SOUND: 1207.2. |
| | |
| | 72) SHEET A-42.4 DETAIL# 11 DOES NOT INDICATE THE USE |
| | OF HORIZONTAL BRACING ANGLES AS INDICATED IN THE |
| | ASSEMBLY. UL U-505. |
| | |
| | 73) SHEET A-43.0 DETAIL# 6 INDICATES THE USES OF ROOF |
| | HATCH AND SHIP???S LADDER, PLEASE PROVIDE THE LOCATION |
| | WHERE THIS SECTION WAS TAKEN, IT DOES NOT SHOW ON THE |
| | ROOF OR POOL DECK SHEET A-11.0. ADDITIONAL INFORMATION |
| | REQUIRED. NOTE THERE ARE NO MIAMI-DADE NOA???S |
| | AVAILABLE FOR ROOF HATCHES NOR STATE APPROVALS. |
| | CURRENTLY THE CITY OF WEST PALM BEACH HAS TWO LOCAL |
| | APPROVALS ONE FOR A NYSTROMRGH3630T AND SECOND A BILCO |
| | HATCH MODEL S-20. |
| | |
| | 74) SHEET A-44.0 STAIRWAYS IN VARIOUS DETAILS INDICATES |
| | THE USE OF A ADA AREA OF REFUGE THAT BLOCK THE |
| | STAIRWAY. THIS BEING A HIGH RISE WILL NEED TO HAVE A |
| | SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM, THIS IS THE |
| | EXCEPTION TO 11-4.1.3.9 NOT REQUIRING AREAS OF RESCUE |
| | ASSISTANCE. |
| | |
| | 75) SHEET A-44.1 DETAIL# 1 AND ???K??? BOTH INDICATE |
| | THE USE OF A HORIZONTAL GUARD RAIL SYSTEM BUT NEITHER |
| | DETAIL PROVIDES THE DISTANCE BETWEEN RAILS. PLEASE |
| | REVIEW 1012.3. |
| | |
| | 76) SHEET S-2 JUST WEST OF THE ELEVATORS THE PLANS |
| | INDICATE PORTIONS OF THE EXISTING SLAB TO BE IN FILLED |
| | BUT THERE IS NO STEEL REINFORCING INFORMATION ON PLAN. |
| | |
| | 77) SHEET S-2 THE EAST SIDE OF THE BUILDING IT APPEARS |
| | THERE TO BE NEW FOUNDATIONS THAT MAY PASS BEYOND THE |
| | PROPERTY LINE PLEASE SEE GRID LINE 1A, 1B & 1C. 3307.1 |
| | PROTECTION REQUIRED. ADJOINING PUBLIC AND PRIVATE |
| | PROPERTY SHALL BE PROTECTED FROM DAMAGE DURING |
| | CONSTRUCTION, REMODELING AND DEMOLITION WORK. |
| | PROTECTION MUST BE PROVIDED FOR FOOTINGS, FOUNDATIONS, |
| | PARTY WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. PROVISIONS |
| | SHALL BE MADE TO CONTROL WATER RUNOFF AND EROSION |
| | DURING CONSTRUCTION OR DEMOLITION ACTIVITIES. THE |
| | PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL |
| | PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING |
| | BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE |
| | MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE |
| | PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT |
| | LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE |
| | OF THE EXCAVATION. |
| | |
| | 78) SHEET S-3- S-6 ALL INDICATE THE REINFORCEMENT |
| | AROUND EXISTING OPENINGS WITH REBAR AND CONCRETE |
| | COLUMNS. ADDITIONAL INFORMATION IS REQUIRED. THE PLANS |
| | DO NOT INDICATE THE MINIMUM EMBEDMENT OF THE # 5 |
| | VERTICAL REBAR INTO THE SLAB ABOVE AND BELOW. THE OTHER |
| | ISSUE THAT I SEE IS THERE IS NO MINIMUM SIZE REQUIRED |
| | FOR THE COLUMN SIZE NEXT TO THE WINDOWS, AND IS THE |
| | BEAM ABOVE ( WHERE THE COLUMN IS BEING DOWELED INTO THE |
| | BEAM BOTTOM ) IS THIS THE WINDOW HEADER OR WILL A |
| | LINTEL ALSO BE REQUIRED? PLANS DO NOT MENTION ANY |
| | TREATMENT FOR A POURED CONCRETE SILL? ADDITIONAL |
| | INFORMATION REQUIRED106.1.2./ 1609.6.2.1 PART OF THE |
| | MAIN WIND-FORCE RESISTING SYSTEM. |
| | |
| | 79) SHEET S-7 THE NEW POOL DECK IS MISSING A LOT OF |
| | INFORMATION: |
| | 79A) PLANS DON???T IDENTIFY THE NEW COLUMNS SIZE OF |
| | REBAR, NUMBER OF REBAR NOR HOOPS |
| | 79B) PLANS DON???T INDICATE INFORMATION AS TO THE NEW |
| | TIE BEAM TB-1 |
| | 79C) PLANS DON???T INDICATE STEEL LAYOUT FOR POOL BEAM |
| | NOR GUTTER PLACEMENT WITHIN THE POOL |
| | BEAM AND DECK TRANSITION |
| | 79D) NEW WATER FEATURE AND STRUCTURE ARE NOT EVEN |
| | MENTIONED |
| | 79E) PLANS FAIL TO INDICATE NEW AWNING / CANOPY AND |
| | REINFORCEMENT OF SLAB |
| | 79F) STRUCTURE FOR RESTROOMS AGAIN NO INFORMATION |
| | PLANS FOR THE POOL DECK AND ROOF TOP A/C UNITS ARE |
| | INCOMPLETE AND NO REVIEW CAN BE ACCOMPLISHED! |
| | |
| | 80) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953. |
| | |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. UNDER FLORIDA STATE STATUTE SB80, E-MAIL ADDRESSES |
| | ARE PUBLIC RECORDS. WRITTEN COMMUNICATIONS TO OR FROM |
| | LOCAL OFFICIALS REGARDING CITY BUSINESS ARE PUBLIC |
| | RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST. YOUR |
| | E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO PUBLIC |
| | DISCLOSURE. |
| | |