Plan Review Notes
Plan Review Notes For Permit 08120584
Permit Number 08120584
Review Stop P
Sequence Number 1
Notes
Date Text
2009-01-12 14:02:22DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A004 CODE INFORMATION SHALL ALSO INCLUDE THE
 2007 AMENDMENTS. SECTION 106.1.1.
  
 2. SHTS P305 BUILDING TYPE V "L" LOWER FLOOR PLAN AND
 402 BUILDING "L" SANITARY ISOMETRIC RISER DIAGRAM SHOWS
 A BACKWATER VALVE IN THE SEWER. SECTION 715.1 STATES,
 WHERE THE FLOOD LEVEL RIMS OF PLUMBING FIXTURES ARE
 BELOW THE ELEVATION OF THE MANHOLE COVER OF THE NEXT
 UPSTREAM MANHOLE IN THE PUBLIC SEWER, SUGH FIXTURES
 SHALL BE PROTECTED BY A BACKWATER VALVE INSTALLED IN
 THE BUILDING DRAIN, BRANCH OF THE BUILDING DRAIN OR
 HORIZONTAL BRANCH SERVING SUCH FIXTURES. PLUMBING
 FIXTURES HAVING FLOOD LEVEL RIMS ABOVE THE ELEVATION OF
 THE MANHOLE COVER OF THE NEXT UPSTREAM MANHOLE IN THE
 PUBLIC SEWER SHALL NOT DISCHARGE THROUGH A BACKWATER
 VALVE. ALL FIXTURES, INCLUDING THE SECOND FLOOR
 FIXTURES ARE DISCHARGING THROUGH THE BACKWATER VALVE AS
 INDICATED ON THE PLANS. THIS IS PROHIBITED. SUBMIT THE
 ELEVATION OF THE MANHOLE COVER OF THE NEXT UPSTREAM
 MANHOLE IN THE PUBLIC SEWER AS WELL AS THE ELEVATION OF
 THE SLAB SO IT CAN BE DETERMINED WHAT FIXTURES SHALL
 DISCHARGE THROUGH THE BACKWATER VALVE. SUBMIT MANUF.
 SPECIFICATIONS FOR THE BATHTUBS AND THE WATER CLOSETS
 SHOWING THE HEIGHTS OF EACH FIXTURES TO DETERMINE THE
 HEIGHT OF THE FLOOD RIM LEVELS FOR THESE FIXTURES.
 SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  