Plan Review Notes
Plan Review Notes For Permit 08120584
Permit Number 08120584
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-22 10:01:28NEW RESIDENTIAL (R2) BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FBC WITH 2007 REVISIONS.
  
 1- EXHIBIT "A" SUBMITTED:
 A) MISSING PRODUCT APPROVAL FOR SINGLE HUNG WINDOWS TO
 VERIFY COMPLIANCE WITH THE U FACTOR AND SHGC FACTOR
 SHOWN ON EXHIBIT A.
  
 B) CLARIFY SPECIFICATIONS SHOWN ON SEC. 2.01 (A)
 REGARDING "ADDITIONAL AUTOMATIC ENGAGING SECONDARY LOCK
 WHICH LIMITS SINGLE HUNG WINDOWS TO AN INITAL OPENING
 HEIGHT OF 4". NEED TO CLARIFY THIS TO VERIFY COMPLIANCE
 WITH EGRESS REQUIREMENTS OF SEC. 1025 FBC 2004.
  
 C) PROVIDE THREE COPIES OF EVERY PAPER SUBMITTED.
  
 2- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 B) REVISE OWNER INFORMATION (REPEAT COMMENT).
  
 C) REVISE PERMIT NUMBER (REPEAT COMMENT).
  
 3- PROVIDE THREE COPIES OF EXHIBIT "B".
  
 4- PROVIDE THREE COPIES OF SOIL TEST REPORT. SEC.
 1802.1 FBC 2004 (REPEAT COMMENT).
  
 5- EXHIBIT "D":
 A) SHINGLES FLORIDA PRODUCT APPROVAL FL728-R1 AND NOA
 08-0305.04 SUBMITTED DON'T CORRESPOND TO EACH OTHER.
 SUBMIT EITHER COMPLETE FLORIDA PRODUCT APPROVAL
 FL728-R1 INCLUDING THE SHINGLES DRAWINGS SUBMITTED FOR
 APPROVAL OR SUBMIT THE NOA ALONE.
 NOTE: MAKE SURE EITHER OPTION HAS DESIGNER OF RECORD
 APPROVAL IN WRITING (REVIEW STAMP) AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- EXHIBIT "C":
 A) PROVIDE SKETCH SHOWING LOCATION OF WINDOWS, DOORS
 AND WALLS CONSIDERED FOR THE CALCULATIONS. SEE SHEET
 A100 FOR ACTUAL BUILDING ORIENTATION. NEED SURVEY TO
 VERIFY DIMENSIONS. ALSO, SEE SHEET A405 FOR ACTUAL TYPE
 OF WINDOWS AND DOORS TO BE CONSIDERED. THERE ARE NOT
 "C" TYPE WINDOWS ON THIS ELEVATION. CALCULATIONS DON'T
 SHOW DOOR OPENINGS. (NOTE: CALCULATIONS TO BE BASED ON
 WINDOWS/DOORS ROUGH OPENINGS).
  
 B) ARCHITECT'S WALL OPENINGS CALCULATIONS NEED TO HAVE
 ARCHITECT'S SEAL, SIGNATURE AND DATE AS REQUIRED BY
 SEC. 61G-16.003 FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 481 FLORIDA STATUTE (REPEAT COMMENT).
  
 C) PROVIDE THREE COPIES.
  
 D) REVISE PERMIT NUMBER TO MATCH NEW PERMIT NUMBER
 08120584.
  
 E) CLARIFY WHY PROVIDING WALL OPENING CALCULATIONS. ARE
 THERE TWO BUILDINGS ON THE SAME LOT CONSIDERED AS ONE
 BUILDING PER EXCEPTION ON SEC. 704.3 FBC 2004 OR THE
 TWO BUILDINGS ARE LOCATED ON TWO DIFFERENT PARCELS.
  
 7- NEED TO PROVIDE SURVEY TO VERIFY BUILDING LOCATION
 AND SETBACKS. SURVEY NOT SUBMITTED AT THIS TIME.
 NOTE: PROVIDE THREE COPIES.
  
 8- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 9- PROVIDE COMPLETE TRUSS PACKAGE. NONE SUBMITTED AT
 THIS TIME.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE PACKAGE
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 10- NEED TO PAY BALANCE OF PERMIT FEES: $28,787.43.
  
 11- SUBMITTAL IS MISSING THE REST OF THE PRODUCT
 APPROVALS:
 A) DOUBLE FRENCH DOORS AS SHOWN ON PLANS.
  
 B) SINGLE HUNG WINDOWS.
  
 C) PRECAST LINTELS AS SHOWN ON PLANS.
  
 D) FIXED WINDOWS AS SHOWN ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. FLORIDA PRODUCT APPROVALS NUMBERS
 SPECIFIED ON SHEET S-4 EXPIRED ON 10-01-08.
  
 F) ROOF RIDGE VENTS AS SHOWN ON PLANS.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712