| 2009-01-14 08:29:14 | ** DENIED ** |
| | |
| | |
| | ** PLEASE SEE THE NOTES BELOW WHICH ARE THE SAME NOTES |
| | FROM TWO PREVIOUS REVIEWS UNDER EXPIRED PERMIT |
| | APPLICATIONS. |
| | THESE ITEMS COULD HAVE BEEN SET UP AS A PROVISO HOWEVER |
| | THE PLANS ARE COMING BACK FOR COMMENTS FROM OTHER |
| | TRADES. PLEASE MAKE CORRECTIONS AT THIS TIME. THIS |
| | AFFECTS ALL UNITS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL OLD/VOIDED SHEETS AND |
| | REPLACE WITH THE NEW CORRECTED SHEETS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE 422.30, 31. THE PREVIOUS REVIEW |
| | GAVE THESE SECTIONS OF THE CODE FOR DISCONNECTS WHICH |
| | ARE REQUIRED FOR DISHWASHER, DISPOSAL AND HOOD. THE |
| | RESPONSE FROM THE ENGINEER STATES THESE DEVICES MEET |
| | 422.33A AND DO NOT NEED DISCONNECTS. AS SHOWN ON THE |
| | PLANS THESE APPLIANCES ARE BEING CONNECTED VIA HARD |
| | WIRED CONNECTIONS TO A JUNCTION BOXES. IN ORDER TO MEET |
| | 422.33A THESE WOULD BE REQUIRED TO BE CORD AND PLUG |
| | CONNECTED EQUIPMENT WITH THE CORDS BEING *PLUGGED IN* |
| | TO RECEPTACLES. AS THERE ARE ONLY JUNCTION BOXES WITH |
| | THE HARD WIRED CONNECTIONS THESE WOULD NEED TO BE |
| | REVISED ON THE PLANS FOR ALL UNITS TO CORD AND PLUG |
| | APPLIANCES WITH RECEPTACLES. |
| | I HAVE PLACED A CALL TO MR. NESTOR MARTINEZ AND SPOKE |
| | AT LENGTH ABOUT THE CODE SECTIONS. MR. MARTINEZ WILL |
| | MAKE THESE ADJUSTMENTS TO PLANS FOR ALL APPLIANCES IN |
| | ALL UNITS. |
| | |
| | 2) NOTE: PLANS FOR THIS SET DOES CONTAIN THE CORRECTED |
| | CODES. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |