Plan Review Notes
Plan Review Notes For Permit 08120583
Permit Number 08120583
Review Stop E
Sequence Number 1
Notes
Date Text
2009-01-14 08:29:14** DENIED **
  
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE THE SAME NOTES
 FROM TWO PREVIOUS REVIEWS UNDER EXPIRED PERMIT
 APPLICATIONS.
 THESE ITEMS COULD HAVE BEEN SET UP AS A PROVISO HOWEVER
 THE PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES. PLEASE MAKE CORRECTIONS AT THIS TIME. THIS
 AFFECTS ALL UNITS.
  
 ** PLEASE BE SURE TO REMOVE ALL OLD/VOIDED SHEETS AND
 REPLACE WITH THE NEW CORRECTED SHEETS.
  
  
  
 1) NOTE: PLEASE SEE 422.30, 31. THE PREVIOUS REVIEW
 GAVE THESE SECTIONS OF THE CODE FOR DISCONNECTS WHICH
 ARE REQUIRED FOR DISHWASHER, DISPOSAL AND HOOD. THE
 RESPONSE FROM THE ENGINEER STATES THESE DEVICES MEET
 422.33A AND DO NOT NEED DISCONNECTS. AS SHOWN ON THE
 PLANS THESE APPLIANCES ARE BEING CONNECTED VIA HARD
 WIRED CONNECTIONS TO A JUNCTION BOXES. IN ORDER TO MEET
 422.33A THESE WOULD BE REQUIRED TO BE CORD AND PLUG
 CONNECTED EQUIPMENT WITH THE CORDS BEING *PLUGGED IN*
 TO RECEPTACLES. AS THERE ARE ONLY JUNCTION BOXES WITH
 THE HARD WIRED CONNECTIONS THESE WOULD NEED TO BE
 REVISED ON THE PLANS FOR ALL UNITS TO CORD AND PLUG
 APPLIANCES WITH RECEPTACLES.
 I HAVE PLACED A CALL TO MR. NESTOR MARTINEZ AND SPOKE
 AT LENGTH ABOUT THE CODE SECTIONS. MR. MARTINEZ WILL
 MAKE THESE ADJUSTMENTS TO PLANS FOR ALL APPLIANCES IN
 ALL UNITS.
  
 2) NOTE: PLANS FOR THIS SET DOES CONTAIN THE CORRECTED
 CODES.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  