Plan Review Notes
Plan Review Notes For Permit 08120580
Permit Number 08120580
Review Stop P
Sequence Number 1
Notes
Date Text
2009-01-09 15:35:45DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING
  
 1. SHT CS-1 PLAN REVIEW DATA SHALL INDICATE THE 2007
 SUPPLEMENTS. SECTION 106.1.1.
  
 2. SHT CS-1 INDICATE THE LEVEL OF ALTERATION PER
 CHAPTER 3 OF THE EXISTING BUILDING CODE. SECTION
 106.1.1.
  
 3. SHT A-4 DETAIL 6. THE SINK WITH GARBAGE DISPOSAL AND
 GARBAGE DISPOSAL SHALL BE ADA APPROVED. PLEASE SUBMIT
 MANUF. SPECIFICATIONS FOR BOTH. SECTIONS 106.1.2 &
 11-4.24.
  
 4. SHT A-4 DETAIL 6. CLEARANCES SHALL COMPLY WITH
 SECTIONS 11-4.24.3, 11-4.24.5 AND FIGURE 11-32. DETAIL
 AS SHOWN DOES NOT COMPLY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  