| 2009-01-07 11:01:36 | BUILDING PLAN REVIEW |
| | PERMIT: 08120576 |
| | ADD: 3201 S. DIXIE HWY. |
| | CONT: TIM JOHNSON REMODELING INC. |
| | TEL: (561)832-7331 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) SHEET A1-1 AND 2 INDICATE THE LEVEL OF ALTERATION AS |
| | LEVEL 1; HOWEVER, LEVEL 2 ALTERATION INCLUDE THE |
| | RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION |
| | OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION |
| | OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL |
| | EQUIPMENT FBC (EXISTING) 304. THE PLANS SUBMITTED SHOW |
| | THE ADDITION OF NEW WALLS AND A DOOR AND THE REMOVAL OF |
| | SOME WALLS AND A DOOR WHICH DOES NOT MEET THE |
| | REQUIREMENTS OF LEVEL 1 ALTERATION. |
| | |
| | 4) IF THE BUILDING HAS A SPRINKLER SYSTEM, SHOW HOW THE |
| | RECONFIGURATION OF THE SPACE AFFECT THE NEW ROOM. SHOW |
| | THE LOCATION OF THE SPRINKLER HEADS LAYOUT ON A |
| | REFLECTED CEILING PLANS FBC 106.3.5.1.1(5) FS 553.79 |
| | (2). |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |