Plan Review Notes
Plan Review Notes For Permit 08120576
Permit Number 08120576
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-07 11:01:36BUILDING PLAN REVIEW
 PERMIT: 08120576
 ADD: 3201 S. DIXIE HWY.
 CONT: TIM JOHNSON REMODELING INC.
 TEL: (561)832-7331
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) SHEET A1-1 AND 2 INDICATE THE LEVEL OF ALTERATION AS
 LEVEL 1; HOWEVER, LEVEL 2 ALTERATION INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT FBC (EXISTING) 304. THE PLANS SUBMITTED SHOW
 THE ADDITION OF NEW WALLS AND A DOOR AND THE REMOVAL OF
 SOME WALLS AND A DOOR WHICH DOES NOT MEET THE
 REQUIREMENTS OF LEVEL 1 ALTERATION.
  
 4) IF THE BUILDING HAS A SPRINKLER SYSTEM, SHOW HOW THE
 RECONFIGURATION OF THE SPACE AFFECT THE NEW ROOM. SHOW
 THE LOCATION OF THE SPRINKLER HEADS LAYOUT ON A
 REFLECTED CEILING PLANS FBC 106.3.5.1.1(5) FS 553.79
 (2).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  