 APPLICATION #08120571 ELECTRICAL PLAN REVIEW
 @ 150 N. QUADRILLE BLVD 1/21/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC. WHEN SUBMITTING FOR PERMIT.
  
 THESE COMMENTS REFERENCE SHEET E-5 ELECTRICAL SERVICE
 RACK
  
 2} THE METER ENCLOSURE IS MOUNTED ON THE RACK AND
 EXPOSED TO WEATHER BUT IS LABELED AS NEMA-1 IN THE
 "KEYED NOTES" #1. 110.3(A)(1).
  
 3} THE 1/0 CONDUCTORS FROM THE METER TO THE PANEL ARE
 NOT ADEQUATE FOR THE 200 AMP OCP MAIN BREAKER THEY
 TERMINATE IN. 3/0 MINIMUM BEFORE CONSIDERING VOLTAGE
 DROP. 310.16 NEC.
  
 4} THERE IS NO INDICATION OF CONDUITS CARRYING THE
 CONDUCTORS TO THE CONTACTORS FROM THE PANEL, OR THE
 CONDUITS AND CONDUCTORS FROM THE CONTACTORS TO THE
 LOADS, INCLUDE SIZE OF AND NUMBER OF CONDUITS AND
 CONDUCTORS.
  
 5} THE #6 GEC WILL BE NONCOMPLIANT FOR THE 3/0
 CONDUCTORS REQUIRED FOR THE SERVICE PER 250.66. (#4
 MINIMUM). SEE COMMENT #3.
  
 6} THE METERED SERVICE RISER DIAGRAM HAS THE INCORRECT
 CONDUCTORS TO THE METER FROM THE HANDHOLE (NO
 TRANSFORMER SHOWN) FOR THE SERVICE SIZE PER 310.16, AND
 THE INCORRECT GEC PER 250.66. THE TRANSFORMER INDICATED
 ON SHEET E-2 SHOULD BE INCLUDED IN THE RISER DIAGRAM,
 AND PRIMARY/SECONDARY RATINGS GIVEN 215.5NEC. THE
 EQUIPMENT GROUNDING CONDUCTOR (#8) RAN WITH THE SERVICE
 CONDUCTORS TO THE PANEL PARALLELS THE GROUNDED
 CONDUCTOR (NEUTRAL) AND MUST NOT BE RUN TO THE PANEL.
 250.6 NEC.
  
 7} THE POWER RISER DIAGRAM HAS THE INCORRECT CONDUCTORS
 TO THE METER FROM THE HANDHOLE (NO TRANSFORMER SHOWN)
 FOR THE SERVICE SIZE PER 310.16 AND THE WRONG SIZE
 SERVICE CONDUCTORS TO PANEL "A". THE EQUIPMENT
 GROUNDING CONDUCTOR (#4) RAN WITH THE SERVICE
 CONDUCTORS TO THE PANEL PARALLELS THE GROUNDED
 CONDUCTOR (NEUTRAL) AND MUST NOT BE RUN TO THE PANEL.
 250.6 NEC.
  
 THE FOLLOWING COMMENTS REFERENCE PANEL "A" CIRCUITING
 VERSES THE CIRCUITING AT THE FIXTURES SHEETS-1 THROUGH
 E-3. 408.4 NEC.
  
 8} POLE #19, A-21, IS A-23 ON THE SCHEDULE.
  
 9} TWO POLES ARE NUMBERED "P23" ON SHEET E-2, ONE ON
 THE EAST AND ONE ON THE WEST SIDES OF THE STREET. THESE
 ARE CIRCUITED THE SAME.
  
 10} POLE NUMBER 25 CIRCUITS DO NOT CORRELATE WITH THE
 PANEL SCHEDULE. A10,12 POLE AND A23 RECEPTACLE AT THE
 POLE, A14,16, 25 ON THE SCHEDULE.
  
 11} POLE #31 LISTS CIRCUIT A-25 FOR THE RECEPTACLE, THE
 SCHEDULE STOPS ALL RECEPTACLE NUMBERS AT POLE #30.
  
 12} POLES #32 THROUGH #39 LISTS A-27 FOR RECEPTACLES,
 A-27 IS A SPACE ON THE SCHEDULE.
  
 13} RECALCULATE THE LOAD SUMMARY ON THE PANEL AFTER
 CORRECTING COMMENTS 8 THROUGH 12.
  
 14} LOCATE THE TRELLIS PANELS, LIGHTS AND RECEPTACLES
 ON SHEETS E-1 THROUGH E-3 WITH CORRELATING CIRCUIT
 NUMBERS AT SAME. THERE IS NO INDICATION IF THESE
 CIRCUITS ARE RAN WITH THE POLE CIRCUITS IN THOSE
 CONDUITS OR IF THEY ARE IN SEPARATE CONDUITS AS THE
 CIRCUIT NUMBERS DO NOT APPEAR ON THE PLAN.
  
 15} LOCATE THE FOUNTAIN CIRCUITS, INDICATE HOW ROUTED
 ON THE PLANS. SEE COMMENT #14.
  
 16} THE TRANSFORMER SHOWN ON SHEET E-2 MUST BE SHOWN ON
 THE RISER DIAGRAM AND THE RATINGS, WATTAGE PRIMARY AND
 SECONDARY MUST BE GIVEN. 215.5 NEC. THE REASON FOR THIS
 COMMENT IS TO REVIEW THE PROVIDED SERVICE VOLTAGE AND
 THE EQUIPMENT AND LUMINAIRE VOLTAGES THE SAME. EG;
 120/208 VOLT TRANSFORMER SECONDARY, 240 VOLT
 LUMINAIRES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  