| 2009-01-10 20:20:05 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | **********PLAN REVIEW ONLY********** |
| | |
| | 1. SHT GN-2 CODE DATA TO INCLUDE THE 2007 AMENDMENTS. |
| | SECTION 106.1.1. |
| | |
| | 2. SHT GN-2 GUEST UNIT INFORMATION: |
| | SECTION 11-9.1.3, SLEEPING ACCOMMODATION FOR PERSONS |
| | WITH HEARING IMPAIRMENTS. |
| | IN ADDITION TO THOSE ACCESSIBLE SLEEPING ROOMS AND |
| | SUITES REQUIRED BY SECTION 11-9.1.2, SLEEPING ROOMS AND |
| | SUITES THAT COMPLY WITH SECTION 11-9.3 SHALL BE |
| | PROVIDED IN CONFORMANCE WITH THE FOLLOWING TABLE. |
| | NUMBER OF ELEMENTS =151 TO 200 / ACCESSIBLE ELEMENTS 6. |
| | PLEASE INDICATE WHERE THE SIX ELMENTS WILL BE LOCATED. |
| | INDICATE WITH ROOM NUMBERS IN THE GUEST INFORMATION. |
| | |
| | 3. SHT GN-2 GUEST UNIT INFORMATION: |
| | SECTION 11-9.1.4 CLASSES OF SLEEPING ACCOMMODATIONS. |
| | (1) IN ORDER TO PROVIDE PERSONS WITH DISABILITIES A |
| | RANGE OF OPTIONS EQUIVALENT TO THOSE AVAILABLE TO OTHER |
| | PESONS SERVED BY THE FACILITY, SLEEPING ROOMS AND |
| | SUITES REQUIRED TO BE ACCESSIBLE BY SECTION 11-9.1.2 |
| | SHALL BE DISPERSED AMONG THE VARIOUS CLASSES OF |
| | SLEEPING ACCOMMODATIONS AVAILABLE TO PATRONS OF THE |
| | PLACE OF TRANSIENT LODGING. THERE ARE NO TWO BEDROOM |
| | UNITS THAT ARE ACCESSIBLE. PLEASE SHOW COMPLIANCE. |
| | |
| | 4. SHT GN-2 PER SECTION 11-9.1.2 IN ALL BUILDINGS, |
| | STRUCTURES AND FACILITIES LICENSED AS A HOTEL, OR |
| | "RESORT CONDOMINIUM" PURSANT TO CHAPTER 509, FLORIDA |
| | STATUES, A NUMBER OF ROOMS EQUALING 5 PERCENT OF THE |
| | GUEST ROOMS MINIMUM THE NUMBER OF ACCESSIBLE ROOMS |
| | REQUIRED BY THE TABLE BELOW SHALL PROVIDE ADDITIONAL |
| | SPECIAL ACCESSIBLITY FEATURES OF SECTION 11-9.2.3. 3 |
| | UNITS ARE REQUIRED. PLEASE INDICATE THE ROOM NUMBERS OF |
| | THE 3 UNITS. |
| | |
| | 5. SHT GN-2 PLUMBING FIXTURE COUNT CALCULATIONS. |
| | INDICATE THE SQUARE FOOTAGE FOR ALL PUBLIC SPACES ON |
| | THE GROUND FLOOR AND SECOND FLOOR. INCLUDE THE AREAS |
| | FOR ALL BUSINESS, ASSEMBLY, STORAGE ETC. AREAS PER |
| | TABLE 403.1. |
| | |
| | 6. SHTS C-3 & C-6 ALL PLUMBING WORK WITHIN THE |
| | FOOTPRINT OF THE BUILDING SHALL BE INSTALLED BY A |
| | LICENSED PLUMBING CONTRACTOR WITH MATERIALS APPROVED IN |
| | TABLE 702.2 OF THE FBC-2004 PLUMBING CODE. PER FS 489 |
| | THIS IS NOT WITHIN THE SCOPE AND LICENSURE OF A UTILITY |
| | OR SITE CONTRACTOR. |
| | |
| | 7. SHT A2.02 OVERFLOW SCUPPERS INDICATE REFERENCE TO |
| | PLUMBING DRAWINGS. THESE WERE NOT LOCATED ON THE |
| | PLUMBING DRAWINGS NOR ARE THEY SHOWN ON THE BUILDING |
| | ELEVATIONS. (ONLY TWO WERE FOUND ON THE NORTH |
| | ELEVATION). PLEASE SUBMIT A DETAIL FOR ALL OVERFLOW |
| | SCUPPERS SHOWING THE HEIGHT, WIDTH AND INDICATE THE |
| | MEASUREMENT OFF THE ROOF TO THE FLOW LINE, MINIMUM 2" |
| | AND MAXIMUM 4"SECTIONS 106.1.2 & 1503.4.3. SHOW |
| | SCUPPERS ON ALL ELEVATIONS. |
| | |
| | 8. SHT A2.03 MAKES REFERENCE TO OVERFLOW SCUPPER AT THE |
| | SOUTH EAST CORNER OF THE ROOF. THE SCUPPERS WERE NOT |
| | LOCATED ON THE ELEVATIONS. PLEASE CLARIFY. SECTIONS |
| | 106.1.1 & 1503.4.3. |
| | |
| | 9. SHTS A2.05 & A2.06 MAKES REFERENCE TO OVERFLOW |
| | SCUPPERS. THE SCUPPERS WERE NOT LOCATED ON THE |
| | ELEVATIONS. PLEASE CLARIFY. SECTIONS 106.1.1 & |
| | 1503.4.3. |
| | |
| | 10. SHT A2.07 ROOM 709. CLARIFY THE NOTE WHICH STATES, |
| | UNIT J FLOORS 7-8 (HC ACCESSIBLE) AND ROOM 711 UNIT F |
| | FLOORS 7-9 (HC ACCESSIBLE). THIS DOES NOT CORRELATE |
| | WITH THE GUEST UNIT INFORMATION ON SHT GN-2. PLEASE |
| | CORRLEATE. SECTIONS 106.1.1 & 11-9.1.2. |
| | |
| | 11. SHT A2.08 PLEASE SUBMIT CALCULATIONS FOR EACH ROOF |
| | DRAIN. SHOW THE SQUARE FOOT AREA DRAINED BY EACH ROOF |
| | DRAIN ALONG WITH 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS ADDED TO THE AREA. |
| | |
| | 12. SHT A 2.08 THE ROOF FOR THE ELEVATORS AND THE ROOF |
| | FOR STAIR NUMBER 2 DO NOT SHOW THE REQUIRED SECONDARY |
| | ROOF DRAINS. PLEASE SHOW THE DRAINS REQUIRED BY |
| | SECTIONS 1107.1 & 1107.2. |
| | |
| | 13. SHT A14.06 DETAIL A5 THE CONTROLS SHALL BE LOCATED |
| | AS SHOWN IN FIGURE 11-34. |
| | |
| | 14. SHT A14.06 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___W/C |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C. |
| | C. 11-4-16-6 DISPENSERS |
| | ___LAV |
| | A. 11-4.19.2 HEIGHT & CLEARANCE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS |
| | |
| | 15. SHT A14.09 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___W/C |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C. |
| | C. 11-4-16-6 DISPENSERS |
| | ___LAV |
| | A. 11-4.19.2 HEIGHT & CLEARANCE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS |
| | |
| | 16. SHT A14.13 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___W/C |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C. |
| | C. 11-4-16-6 DISPENSERS |
| | ___LAV |
| | A. 11-4.19.2 HEIGHT & CLEARANCE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCET |
| | |
| | 17. SHT A14.14 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___W/C |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C. |
| | C. 11-4-16-6 DISPENSERS |
| | ___LAV |
| | A. 11-4.19.2 HEIGHT & CLEARANCE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS |
| | |
| | 18. SUBMIT A FINISH SCHEDULE FOR THE WALLS & FLOOR IN |
| | THE PUBLIC AND COMMON USE TOILET ROOMS TO SHOW |
| | COMPLIANCE WITH SECTION 1210. SECTION 106.1.2. |
| | |
| | 19. SHT A16.01 DETAILS A1, A4, E13, J6, J13,L6 & L10. |
| | SHOW THE GRAB BAR SIZE BEHIND THE WATER CLOSET AS 36 |
| | INCHES LONG AS REQUIRED IN SECTION 11-4.16.4 & FIGURE |
| | 28. SOME DETAILS SHOW THE GRAB BAR AS 24", SOME DETAILS |
| | SHOW THE GRAB AS 36" AND SOME SHOW NO MEASUREMENT. |
| | PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 20. SHT A16.01 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___LAV |
| | A. 11-4.19.2 CLEARANCE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | |
| | 21. SHT A16.02 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___W/C |
| | A. 11-4.16.4 GRAB BARS (36" REQD. BUT SHOWN AS 24" |
| | BEHIND THE W/C) |
| | |
| | ___LAV |
| | A. 11-4.19.2 CLEARANCE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | |
| | ___TOILET ROOMS |
| | A. 11-4.22.3 UNOBSTRUCTED TURNING AREA |
| | |
| | 21. SHT P1 SHOWS SUMP PUMPS FROM THE ELEVATORS |
| | CONNECTING DIRECTLY TO THE SANITARY. PER SECTION 301.6 |
| | THIS IS PROHIBITED. IF DRAINING TO THE SANITARY, AN |
| | INTERCEPTOR MAY BE REQUIRED. AN OUTLET TO PUMP CONTENTS |
| | INTO A RECEPTICLE AND PROPER DISPOSAL AS HAZARDOUS |
| | MATERIAL IS ACCEPTABLE. PLEASE INDICATE METHOD. SECTION |
| | 106.1.2. |
| | |
| | 22. SHTS P1, P2 & P3 SHOWS TRENCH DRAINS CONNECTING TO |
| | THE SANITARY. PLEASE INDICATE WHAT WILL DRAIN INTO THE |
| | TRENCH DRAIN. IF STORM WATER, THEN IT MUST CONNECT TO |
| | THE STORM SYSTEM AND THE AIR ADMITTENCE VALVE, (STUDOR |
| | VENT), IS NOT REQUIRED. ARTICLE III SECTION 90-124(6). |
| | IF SANITARY DRAINAGE THE AAV IS REQUIRED TO HAVE A |
| | RELIEF VENT PER SECTION 917.13.2. PLEASE CLARIFY. |
| | |
| | 23. SHT P7 DRAWING TITLE PLUMBING 7TH - PENTHOUSE PLAN |
| | SHOWS A 3/4 INCH HOT WATER RETURN. IS THIS TYPICAL FOR |
| | ALL FLOORS? IF NOT IT SHALL BE A SEPARATE SHEET OR BE |
| | INDICATED AS FOR WHATEVER FLOORS IT IS ON. IS SHT P6 |
| | (6TH FLOOR), DIFFERENT FROM THE 7TH THRU PENTHOUSE |
| | FLOORS? PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1. |
| | |
| | 24. SHT P8 PER SECTIONS 1107.1 1107.2 SECONDARY ROOF |
| | DRAINS OR EMERGENCY OVERFLOW SCUPPERS ARE REQUIRED. |
| | PLEASE INDICATE THE LOCATION OF THE REQUIRED SEPARATE |
| | SYSTEM. |
| | |
| | 25. SHT P8 SEE SHEET A2.08 WHEN MAKING CALCULATIONS FOR |
| | THE ROOF DRAINAGE, KEEP IN MIND THE RIDGE IS NOT IN THE |
| | CENTER OF THE ROOF SO MORE SQUARE FOOTAGE WILL BE |
| | DIRECTED TO THE DRAINS ON ONE SIDE OF THE ROOF THAN THE |
| | OTHER. TABLE 1106.3. |
| | |
| | 26. SHT P12 ENLARGED KITCHEN PLAN. ITEM 18, (DISH |
| | WASHER), SHALL NOT DISCHARGE INTO THE GREASE SYSTEM, |
| | AND IS REQUIRED TO DISCHARGE INTO THE SANITARY SYSTEM. |
| | ARTICLE III SECTION 90-124(7)(B). |
| | |
| | 27. SHT P12 ENLARGED KITCHEN PLAN. THE WATER FILTER |
| | SHALL MEET THE REQUIREMENTS OF NSF 42 PER SECTION |
| | 611.1. PLEASE SUBMIT MANUF. SPECIFICATIONS SHOWING |
| | COMPLIANCE. SECTION 106.1.2. |
| | |
| | 28. SHT P12 WATER PIPING DIAGRAM. A VACUUM RELIEF VALVE |
| | IS REQUIRED PER SECTION 504.2. PLEASE SHOW AT THE TOP |
| | OF THE COLD WATER SUPPLY DROP TO THE WATER HEATERS. |
| | |
| | 29. SHT P12 WATER HEATER PIPING DIAGRAM EXPANSION TANK. |
| | SUBMIT MANUF SPECIFICATIONS INDICATING MODEL NUMBER AND |
| | SUBMIT CALCULATIONS OR MANUF. CHART SHOWING THE CORRECT |
| | SIZE OF THE EXPANSION TANK. SECTION 607.3.2. |
| | |
| | 30. SHT P12 WATER HEATER PIPING DIAGRAM DOES NOT RELECT |
| | ENLARGED BOILER ROOM PIPING. THE DIAGRAM ON SHT P24 |
| | DOES REFLECT THE PIPING. PLEASE INDICATE WITH A NOTE |
| | DIRECTING ATTENTION TO THE RISER ON SHT P24 AS WELL, |
| | LIKE THE NOTE DIRECTING ATTENTION TO THE PIPING DIAGRAM |
| | AT THE BOILER ROOM. SECTIONS 106.1.1 & 601.1. |
| | |
| | 31. SHT P12 TYPICAL ENLARGED "UNIT S" PLAN. PLEASE |
| | INDICATE WHERE THE HOT WATER TO THE TUB CONNECTS TO THE |
| | WATER SUPPLY LINE OVERHEAD. THE WATER RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN AT THE RISER. PLEASE |
| | CORRELATE. SECTIONS 106.1.1, 106.1.2 & 607.4. |
| | |
| | 32. SHT P13 UNIT D SANITARY RISER DIAGRAM SHOWER IS NOT |
| | VENTED AND THE FLOOR PLAN SHOWS A TUB. UNIT D WATER |
| | RISER SHOWS A SHOWER AS WELL. PLEASE CORRELATE. |
| | SECTIONS 106.1.1, 701.1 & 901.2.1. |
| | |
| | 33. SHT P14 UNIT F/UNIT H WATER & SANITARY RISERS |
| | INDICATE A SHOWER IN UNIT H, BUT THE FLOOR PLAN SHOWS A |
| | TUB. PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 34. SHT P14 UNIT G SANITARY AND WATER RISER DIAGRAMS DO |
| | NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS |
| | 106.1.1, 601.1 & 701.1. |
| | |
| | 35. SHT P15 UNITS Q & R SANITARY & WATER RISER DIAGRAMS |
| | ARE REVERSE FROM THE FLOOR PLAN. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | |
| | 36. SHT P16 ALL SANITARY RISER DIAGRAMS. THE VENT |
| | STACKS SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK. |
| | THE VENT SHALL CONNECT TO THE STACK AT OR BELOW THE |
| | LOWEST HORIZONTAL BRANCH. SECTION 903.4. |
| | |
| | 37. SHT P16 TYPICAL RISER G SHOWS 9 FU FOR THE 5TH |
| | FLOOR BUT HAS THE SAME FIXTURES AS ALL THE OTHER FLOORS |
| | SHOWN AS 14 FU. PLEASE CLARIFY & CORRELATE. TABLE |
| | 710.1(2). |
| | |
| | 38. SHT P17 TYPICAL RISER B STARTS OUT WITH 1-1/4" COLD |
| | WATER THEN INCREASES TO 1-1/2" FOR THE NEXT FOUR |
| | FLOORS. PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1. |
| | |
| | 39. SHT P18 SHOWS SUMP PUMPS FROM THE ELEVATORS |
| | CONNECTING DIRECTLY TO THE SANITARY. PER SECTION 301.6 |
| | THIS IS PROHIBITED. IF DRAINING TO THE SANITARY, AN |
| | INTERCEPTOR MAY BE REQUIRED. AN OUTLET TO PUMP CONTENTS |
| | INTO A RECPTICLE AND PROPER DISPOSAL AS HAZARDOUS |
| | MATERIAL IS ACCEPTABLE. PLEASE INDICATE METHOD. SECTION |
| | 106.1.2. |
| | |
| | 40. SHT P18 FLOOR DRAINS IN THE TOILET ROOMS 130 & 131 |
| | ARE NOT VENTED AS SHOWN. SECTION 901.2.1. THE FLOOR |
| | DRAINS SHOULD DISCHARGE DOWNSTREAM OF THE VENTED LAVS. |
| | SECTION 901.2. |
| | |
| | 41. SHT P18 GREASE INTERCEPTORS SHALL BE SIZED BY THE |
| | UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| | COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY |
| | SUPERVISOR AT HER OFFICE, (561) 822-2271, BY FAX (561) |
| | 822-2279 OR BY E-MAIL [email protected]. A WRITTEN |
| | DETERMINATION IS REQUIRED FROM THE UTILITY DEPT. |
| | ARTICLE III SECTION 90-124(7)(F) AND SECTION 1003. |
| | |
| | 42. SHT SHT P18 PLEASE INDICATE WHAT WILL DRAIN INTO |
| | THE TRENCH DRAIN. IF STORM WATER, THEN IT MUST CONNECT |
| | TO THE STORM SYSTEM AND THE AIR ADMITTANCE VALVE, |
| | (STUDOR VENT), IS NOT REQUIRED. ARTICLE III SECTION |
| | 90-124(6). IF SANITARY DRAINAGE THE AAV IS REQUIRED TO |
| | HAVE A RELIEF VENT PER SECTION 917.13.2. PLEASE |
| | CLARIFY. |
| | |
| | 43. SHT P18 INDICATE WHERE THE CONTINUATION FOR THE |
| | SANITARY RISER A1 CAN BE LOCATED. SECTIONS 106.1.2 & |
| | 701.1. |
| | |
| | 44. SHT P19 3" FLOOR DRAIN WITH SEDIMENT BUCKET (2FU). |
| | INDICATE HOW THE STORM WATER WILL BE KEPT OUT OF THE |
| | SANITARY SYSTEM. (DRAIN NOT REQUIRED). ARTICLE III |
| | 90-124 (6). ALSO THE AIR ADMITTANCE VALVE, (STUDOR |
| | VENT), REQUIRES A RELIEF VENT PER SECTION 917.3.1. |
| | |
| | 45. SHT P19 CLEANOUTS ARE REQUIRED AT THE BASE OF ALL |
| | STACKS. SECTION 708.3.4. |
| | |
| | 46. SHT P25 SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR THE PERMIT: |
| | |
| | A. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | B. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. (FOR DRYERS) |
| | |
| | C. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. (MANUAL VALVE AND UNION |
| | NOT SHOWN). |
| | |
| | 47 SHT P25 THE GAS PIPING SHALL BE SIZED BY FBC-2004 |
| | FUEL GAS OR SUBMIT A COPY OF THE TABLE USED. THE SOURCE |
| | OF THE TABLE SHALL BE INDICATED ON THE TABLE. |
| | |
| | 48. SHT P26 PLUMBING RWL 2ND FLOOR. PLEASE INDICATE IF |
| | THE RISER ENDS ON THE 2ND FLOOR OR CONTINUES UP TO THE |
| | 3RD & 4TH FLOORS AS INDICATED ON THE RWL RISER DIAGRAM |
| | 1ST FLOOR GARAGE. CLARIFY. SECTIONS 106.1.1 & 1101.1. |
| | |
| | 49. SHT P26 VERIFY SQUARE FOOTAGE ON 8" 90785 SF AND |
| | ACCUMULATED BELOW. (SEE SHT P27). SECTIONS 106.1.1 & |
| | TABLE 1106.3. |
| | |
| | 50. SHT P27 RECHECK ADDITION ON 6" DOWNSTREAM OF 6" |
| | (2157 SF) ON RWL 4TH FLOOR GARAGE AND DOWNSTREAM. |
| | SECTION 106.1.1 & TABLE 1106.3. |
| | |
| | 51. SHT P27 RISER DIAGRAM 3RD FLOOR PLEASE INDICATE IF |
| | THE RISER ENDS ON THE 2ND FLOOR OR CONTINUES UP TO THE |
| | 3RD & 4TH FLOORS AS INDICATED ON THE RWL RISER DIAGRAM |
| | 1ST FLOOR GARAGE. CLARIFY. SECTIONS 106.1.1 & 1101.1. |
| | |
| | 52. SHT P29 SEE ATTACHED COPY OF THE CITY WPB UNITLIY |
| | DETAIL FOR GREASE INTERCEPTORS. GREASE INTERCEPTOR |
| | DETAIL SHALL BE APPROVED BY THE UTILITY DEPT. OR GREASE |
| | INTERCEPTOR DETAIL SHALL REFLECT APPROVED DETAIL. |
| | SECTION 1003.2. |
| | |
| | 53. SHT P30 SAFE WASTE DETAILS FCO & FD. PER SECTION |
| | 1002.1 DOUBLE TRAPING IS PROHIBITED. PLEASE CHANGE |
| | DETAILS. |
| | |
| | 54. SHT P30 ICE MACHINE DETAIL. THE WATER FILTER SHALL |
| | MEET THE REQUIREMENTS OF NSF 42. SECTION 611.1. |
| | |
| | 55. SUBMIT A CONDENSATE BUILDING ISOMETRIC RISER |
| | DIAGRAM AND CONDENSATE RISER DIAGRAMS SHOWING ALL PIPE |
| | SIZES, TRAPS, VENTS, AND INDICATE MATERIAL. SECTIONS |
| | 106.3.5.1.3 & 314.2.2. |
| | |
| | 56. CONDENSATE IS SHOWN TERMINATING AT THE CATCH BASINS |
| | IN THE FIRST FLOOR GARAGE. CONCERNS FOR THE POSSIBILITY |
| | OF THE EXHAUST FUMES ENTERING THE UNITS SHALL BE |
| | ADDRESSED. PLEASE INDICATE HOW THIS WILL BE ADDRESSED. |
| | SECTION 106.1.2 (MORE INFORMATION REQUIRED). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ******IMPORTANT****** PLEASE RESUBMIT PLUMBING PLANS |
| | WITH THE HIGHLIGHTED SHEETS TO HELP EXPEDITE FUTURE |
| | PLAN REVIEWS. THANK YOU |
| | |
| | REVIEW BY KEN STEVENS |