Plan Review Notes
Plan Review Notes For Permit 08120552
Permit Number 08120552
Review Stop P
Sequence Number 1
Notes
Date Text
2009-01-10 20:20:05DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
  
 **********PLAN REVIEW ONLY**********
  
 1. SHT GN-2 CODE DATA TO INCLUDE THE 2007 AMENDMENTS.
 SECTION 106.1.1.
  
 2. SHT GN-2 GUEST UNIT INFORMATION:
 SECTION 11-9.1.3, SLEEPING ACCOMMODATION FOR PERSONS
 WITH HEARING IMPAIRMENTS.
 IN ADDITION TO THOSE ACCESSIBLE SLEEPING ROOMS AND
 SUITES REQUIRED BY SECTION 11-9.1.2, SLEEPING ROOMS AND
 SUITES THAT COMPLY WITH SECTION 11-9.3 SHALL BE
 PROVIDED IN CONFORMANCE WITH THE FOLLOWING TABLE.
 NUMBER OF ELEMENTS =151 TO 200 / ACCESSIBLE ELEMENTS 6.
 PLEASE INDICATE WHERE THE SIX ELMENTS WILL BE LOCATED.
 INDICATE WITH ROOM NUMBERS IN THE GUEST INFORMATION.
  
 3. SHT GN-2 GUEST UNIT INFORMATION:
 SECTION 11-9.1.4 CLASSES OF SLEEPING ACCOMMODATIONS.
 (1) IN ORDER TO PROVIDE PERSONS WITH DISABILITIES A
 RANGE OF OPTIONS EQUIVALENT TO THOSE AVAILABLE TO OTHER
 PESONS SERVED BY THE FACILITY, SLEEPING ROOMS AND
 SUITES REQUIRED TO BE ACCESSIBLE BY SECTION 11-9.1.2
 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES OF
 SLEEPING ACCOMMODATIONS AVAILABLE TO PATRONS OF THE
 PLACE OF TRANSIENT LODGING. THERE ARE NO TWO BEDROOM
 UNITS THAT ARE ACCESSIBLE. PLEASE SHOW COMPLIANCE.
  
 4. SHT GN-2 PER SECTION 11-9.1.2 IN ALL BUILDINGS,
 STRUCTURES AND FACILITIES LICENSED AS A HOTEL, OR
 "RESORT CONDOMINIUM" PURSANT TO CHAPTER 509, FLORIDA
 STATUES, A NUMBER OF ROOMS EQUALING 5 PERCENT OF THE
 GUEST ROOMS MINIMUM THE NUMBER OF ACCESSIBLE ROOMS
 REQUIRED BY THE TABLE BELOW SHALL PROVIDE ADDITIONAL
 SPECIAL ACCESSIBLITY FEATURES OF SECTION 11-9.2.3. 3
 UNITS ARE REQUIRED. PLEASE INDICATE THE ROOM NUMBERS OF
 THE 3 UNITS.
  
 5. SHT GN-2 PLUMBING FIXTURE COUNT CALCULATIONS.
 INDICATE THE SQUARE FOOTAGE FOR ALL PUBLIC SPACES ON
 THE GROUND FLOOR AND SECOND FLOOR. INCLUDE THE AREAS
 FOR ALL BUSINESS, ASSEMBLY, STORAGE ETC. AREAS PER
 TABLE 403.1.
  
 6. SHTS C-3 & C-6 ALL PLUMBING WORK WITHIN THE
 FOOTPRINT OF THE BUILDING SHALL BE INSTALLED BY A
 LICENSED PLUMBING CONTRACTOR WITH MATERIALS APPROVED IN
 TABLE 702.2 OF THE FBC-2004 PLUMBING CODE. PER FS 489
 THIS IS NOT WITHIN THE SCOPE AND LICENSURE OF A UTILITY
 OR SITE CONTRACTOR.
  
 7. SHT A2.02 OVERFLOW SCUPPERS INDICATE REFERENCE TO
 PLUMBING DRAWINGS. THESE WERE NOT LOCATED ON THE
 PLUMBING DRAWINGS NOR ARE THEY SHOWN ON THE BUILDING
 ELEVATIONS. (ONLY TWO WERE FOUND ON THE NORTH
 ELEVATION). PLEASE SUBMIT A DETAIL FOR ALL OVERFLOW
 SCUPPERS SHOWING THE HEIGHT, WIDTH AND INDICATE THE
 MEASUREMENT OFF THE ROOF TO THE FLOW LINE, MINIMUM 2"
 AND MAXIMUM 4"SECTIONS 106.1.2 & 1503.4.3. SHOW
 SCUPPERS ON ALL ELEVATIONS.
  
 8. SHT A2.03 MAKES REFERENCE TO OVERFLOW SCUPPER AT THE
 SOUTH EAST CORNER OF THE ROOF. THE SCUPPERS WERE NOT
 LOCATED ON THE ELEVATIONS. PLEASE CLARIFY. SECTIONS
 106.1.1 & 1503.4.3.
  
 9. SHTS A2.05 & A2.06 MAKES REFERENCE TO OVERFLOW
 SCUPPERS. THE SCUPPERS WERE NOT LOCATED ON THE
 ELEVATIONS. PLEASE CLARIFY. SECTIONS 106.1.1 &
 1503.4.3.
  
 10. SHT A2.07 ROOM 709. CLARIFY THE NOTE WHICH STATES,
 UNIT J FLOORS 7-8 (HC ACCESSIBLE) AND ROOM 711 UNIT F
 FLOORS 7-9 (HC ACCESSIBLE). THIS DOES NOT CORRELATE
 WITH THE GUEST UNIT INFORMATION ON SHT GN-2. PLEASE
 CORRLEATE. SECTIONS 106.1.1 & 11-9.1.2.
  
 11. SHT A2.08 PLEASE SUBMIT CALCULATIONS FOR EACH ROOF
 DRAIN. SHOW THE SQUARE FOOT AREA DRAINED BY EACH ROOF
 DRAIN ALONG WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO THE AREA.
  
 12. SHT A 2.08 THE ROOF FOR THE ELEVATORS AND THE ROOF
 FOR STAIR NUMBER 2 DO NOT SHOW THE REQUIRED SECONDARY
 ROOF DRAINS. PLEASE SHOW THE DRAINS REQUIRED BY
 SECTIONS 1107.1 & 1107.2.
  
 13. SHT A14.06 DETAIL A5 THE CONTROLS SHALL BE LOCATED
 AS SHOWN IN FIGURE 11-34.
  
 14. SHT A14.06 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C.
 C. 11-4-16-6 DISPENSERS
 ___LAV
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 15. SHT A14.09 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C.
 C. 11-4-16-6 DISPENSERS
 ___LAV
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 16. SHT A14.13 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C.
 C. 11-4-16-6 DISPENSERS
 ___LAV
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCET
  
 17. SHT A14.14 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS, 36" REQUIRED BEHIND THE W/C.
 C. 11-4-16-6 DISPENSERS
 ___LAV
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 18. SUBMIT A FINISH SCHEDULE FOR THE WALLS & FLOOR IN
 THE PUBLIC AND COMMON USE TOILET ROOMS TO SHOW
 COMPLIANCE WITH SECTION 1210. SECTION 106.1.2.
  
 19. SHT A16.01 DETAILS A1, A4, E13, J6, J13,L6 & L10.
 SHOW THE GRAB BAR SIZE BEHIND THE WATER CLOSET AS 36
 INCHES LONG AS REQUIRED IN SECTION 11-4.16.4 & FIGURE
 28. SOME DETAILS SHOW THE GRAB BAR AS 24", SOME DETAILS
 SHOW THE GRAB AS 36" AND SOME SHOW NO MEASUREMENT.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 20. SHT A16.01 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___LAV
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 21. SHT A16.02 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C
 A. 11-4.16.4 GRAB BARS (36" REQD. BUT SHOWN AS 24"
 BEHIND THE W/C)
  
 ___LAV
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 ___TOILET ROOMS
 A. 11-4.22.3 UNOBSTRUCTED TURNING AREA
  
 21. SHT P1 SHOWS SUMP PUMPS FROM THE ELEVATORS
 CONNECTING DIRECTLY TO THE SANITARY. PER SECTION 301.6
 THIS IS PROHIBITED. IF DRAINING TO THE SANITARY, AN
 INTERCEPTOR MAY BE REQUIRED. AN OUTLET TO PUMP CONTENTS
 INTO A RECEPTICLE AND PROPER DISPOSAL AS HAZARDOUS
 MATERIAL IS ACCEPTABLE. PLEASE INDICATE METHOD. SECTION
 106.1.2.
  
 22. SHTS P1, P2 & P3 SHOWS TRENCH DRAINS CONNECTING TO
 THE SANITARY. PLEASE INDICATE WHAT WILL DRAIN INTO THE
 TRENCH DRAIN. IF STORM WATER, THEN IT MUST CONNECT TO
 THE STORM SYSTEM AND THE AIR ADMITTENCE VALVE, (STUDOR
 VENT), IS NOT REQUIRED. ARTICLE III SECTION 90-124(6).
 IF SANITARY DRAINAGE THE AAV IS REQUIRED TO HAVE A
 RELIEF VENT PER SECTION 917.13.2. PLEASE CLARIFY.
  
 23. SHT P7 DRAWING TITLE PLUMBING 7TH - PENTHOUSE PLAN
 SHOWS A 3/4 INCH HOT WATER RETURN. IS THIS TYPICAL FOR
 ALL FLOORS? IF NOT IT SHALL BE A SEPARATE SHEET OR BE
 INDICATED AS FOR WHATEVER FLOORS IT IS ON. IS SHT P6
 (6TH FLOOR), DIFFERENT FROM THE 7TH THRU PENTHOUSE
 FLOORS? PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1.
  
 24. SHT P8 PER SECTIONS 1107.1 1107.2 SECONDARY ROOF
 DRAINS OR EMERGENCY OVERFLOW SCUPPERS ARE REQUIRED.
 PLEASE INDICATE THE LOCATION OF THE REQUIRED SEPARATE
 SYSTEM.
  
 25. SHT P8 SEE SHEET A2.08 WHEN MAKING CALCULATIONS FOR
 THE ROOF DRAINAGE, KEEP IN MIND THE RIDGE IS NOT IN THE
 CENTER OF THE ROOF SO MORE SQUARE FOOTAGE WILL BE
 DIRECTED TO THE DRAINS ON ONE SIDE OF THE ROOF THAN THE
 OTHER. TABLE 1106.3.
  
 26. SHT P12 ENLARGED KITCHEN PLAN. ITEM 18, (DISH
 WASHER), SHALL NOT DISCHARGE INTO THE GREASE SYSTEM,
 AND IS REQUIRED TO DISCHARGE INTO THE SANITARY SYSTEM.
 ARTICLE III SECTION 90-124(7)(B).
  
 27. SHT P12 ENLARGED KITCHEN PLAN. THE WATER FILTER
 SHALL MEET THE REQUIREMENTS OF NSF 42 PER SECTION
 611.1. PLEASE SUBMIT MANUF. SPECIFICATIONS SHOWING
 COMPLIANCE. SECTION 106.1.2.
  
 28. SHT P12 WATER PIPING DIAGRAM. A VACUUM RELIEF VALVE
 IS REQUIRED PER SECTION 504.2. PLEASE SHOW AT THE TOP
 OF THE COLD WATER SUPPLY DROP TO THE WATER HEATERS.
  
 29. SHT P12 WATER HEATER PIPING DIAGRAM EXPANSION TANK.
 SUBMIT MANUF SPECIFICATIONS INDICATING MODEL NUMBER AND
 SUBMIT CALCULATIONS OR MANUF. CHART SHOWING THE CORRECT
 SIZE OF THE EXPANSION TANK. SECTION 607.3.2.
  
 30. SHT P12 WATER HEATER PIPING DIAGRAM DOES NOT RELECT
 ENLARGED BOILER ROOM PIPING. THE DIAGRAM ON SHT P24
 DOES REFLECT THE PIPING. PLEASE INDICATE WITH A NOTE
 DIRECTING ATTENTION TO THE RISER ON SHT P24 AS WELL,
 LIKE THE NOTE DIRECTING ATTENTION TO THE PIPING DIAGRAM
 AT THE BOILER ROOM. SECTIONS 106.1.1 & 601.1.
  
 31. SHT P12 TYPICAL ENLARGED "UNIT S" PLAN. PLEASE
 INDICATE WHERE THE HOT WATER TO THE TUB CONNECTS TO THE
 WATER SUPPLY LINE OVERHEAD. THE WATER RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN AT THE RISER. PLEASE
 CORRELATE. SECTIONS 106.1.1, 106.1.2 & 607.4.
  
 32. SHT P13 UNIT D SANITARY RISER DIAGRAM SHOWER IS NOT
 VENTED AND THE FLOOR PLAN SHOWS A TUB. UNIT D WATER
 RISER SHOWS A SHOWER AS WELL. PLEASE CORRELATE.
 SECTIONS 106.1.1, 701.1 & 901.2.1.
  
 33. SHT P14 UNIT F/UNIT H WATER & SANITARY RISERS
 INDICATE A SHOWER IN UNIT H, BUT THE FLOOR PLAN SHOWS A
 TUB. PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 34. SHT P14 UNIT G SANITARY AND WATER RISER DIAGRAMS DO
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS
 106.1.1, 601.1 & 701.1.
  
 35. SHT P15 UNITS Q & R SANITARY & WATER RISER DIAGRAMS
 ARE REVERSE FROM THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 36. SHT P16 ALL SANITARY RISER DIAGRAMS. THE VENT
 STACKS SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK.
 THE VENT SHALL CONNECT TO THE STACK AT OR BELOW THE
 LOWEST HORIZONTAL BRANCH. SECTION 903.4.
  
 37. SHT P16 TYPICAL RISER G SHOWS 9 FU FOR THE 5TH
 FLOOR BUT HAS THE SAME FIXTURES AS ALL THE OTHER FLOORS
 SHOWN AS 14 FU. PLEASE CLARIFY & CORRELATE. TABLE
 710.1(2).
  
 38. SHT P17 TYPICAL RISER B STARTS OUT WITH 1-1/4" COLD
 WATER THEN INCREASES TO 1-1/2" FOR THE NEXT FOUR
 FLOORS. PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1.
  
 39. SHT P18 SHOWS SUMP PUMPS FROM THE ELEVATORS
 CONNECTING DIRECTLY TO THE SANITARY. PER SECTION 301.6
 THIS IS PROHIBITED. IF DRAINING TO THE SANITARY, AN
 INTERCEPTOR MAY BE REQUIRED. AN OUTLET TO PUMP CONTENTS
 INTO A RECPTICLE AND PROPER DISPOSAL AS HAZARDOUS
 MATERIAL IS ACCEPTABLE. PLEASE INDICATE METHOD. SECTION
 106.1.2.
  
 40. SHT P18 FLOOR DRAINS IN THE TOILET ROOMS 130 & 131
 ARE NOT VENTED AS SHOWN. SECTION 901.2.1. THE FLOOR
 DRAINS SHOULD DISCHARGE DOWNSTREAM OF THE VENTED LAVS.
 SECTION 901.2.
  
 41. SHT P18 GREASE INTERCEPTORS SHALL BE SIZED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY
 SUPERVISOR AT HER OFFICE, (561) 822-2271, BY FAX (561)
 822-2279 OR BY E-MAIL [email protected]. A WRITTEN
 DETERMINATION IS REQUIRED FROM THE UTILITY DEPT.
 ARTICLE III SECTION 90-124(7)(F) AND SECTION 1003.
  
 42. SHT SHT P18 PLEASE INDICATE WHAT WILL DRAIN INTO
 THE TRENCH DRAIN. IF STORM WATER, THEN IT MUST CONNECT
 TO THE STORM SYSTEM AND THE AIR ADMITTANCE VALVE,
 (STUDOR VENT), IS NOT REQUIRED. ARTICLE III SECTION
 90-124(6). IF SANITARY DRAINAGE THE AAV IS REQUIRED TO
 HAVE A RELIEF VENT PER SECTION 917.13.2. PLEASE
 CLARIFY.
  
 43. SHT P18 INDICATE WHERE THE CONTINUATION FOR THE
 SANITARY RISER A1 CAN BE LOCATED. SECTIONS 106.1.2 &
 701.1.
  
 44. SHT P19 3" FLOOR DRAIN WITH SEDIMENT BUCKET (2FU).
 INDICATE HOW THE STORM WATER WILL BE KEPT OUT OF THE
 SANITARY SYSTEM. (DRAIN NOT REQUIRED). ARTICLE III
 90-124 (6). ALSO THE AIR ADMITTANCE VALVE, (STUDOR
 VENT), REQUIRES A RELIEF VENT PER SECTION 917.3.1.
  
 45. SHT P19 CLEANOUTS ARE REQUIRED AT THE BASE OF ALL
 STACKS. SECTION 708.3.4.
  
 46. SHT P25 SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE PERMIT:
  
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (FOR DRYERS)
  
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (MANUAL VALVE AND UNION
 NOT SHOWN).
  
 47 SHT P25 THE GAS PIPING SHALL BE SIZED BY FBC-2004
 FUEL GAS OR SUBMIT A COPY OF THE TABLE USED. THE SOURCE
 OF THE TABLE SHALL BE INDICATED ON THE TABLE.
  
 48. SHT P26 PLUMBING RWL 2ND FLOOR. PLEASE INDICATE IF
 THE RISER ENDS ON THE 2ND FLOOR OR CONTINUES UP TO THE
 3RD & 4TH FLOORS AS INDICATED ON THE RWL RISER DIAGRAM
 1ST FLOOR GARAGE. CLARIFY. SECTIONS 106.1.1 & 1101.1.
  
 49. SHT P26 VERIFY SQUARE FOOTAGE ON 8" 90785 SF AND
 ACCUMULATED BELOW. (SEE SHT P27). SECTIONS 106.1.1 &
 TABLE 1106.3.
  
 50. SHT P27 RECHECK ADDITION ON 6" DOWNSTREAM OF 6"
 (2157 SF) ON RWL 4TH FLOOR GARAGE AND DOWNSTREAM.
 SECTION 106.1.1 & TABLE 1106.3.
  
 51. SHT P27 RISER DIAGRAM 3RD FLOOR PLEASE INDICATE IF
 THE RISER ENDS ON THE 2ND FLOOR OR CONTINUES UP TO THE
 3RD & 4TH FLOORS AS INDICATED ON THE RWL RISER DIAGRAM
 1ST FLOOR GARAGE. CLARIFY. SECTIONS 106.1.1 & 1101.1.
  
 52. SHT P29 SEE ATTACHED COPY OF THE CITY WPB UNITLIY
 DETAIL FOR GREASE INTERCEPTORS. GREASE INTERCEPTOR
 DETAIL SHALL BE APPROVED BY THE UTILITY DEPT. OR GREASE
 INTERCEPTOR DETAIL SHALL REFLECT APPROVED DETAIL.
 SECTION 1003.2.
  
 53. SHT P30 SAFE WASTE DETAILS FCO & FD. PER SECTION
 1002.1 DOUBLE TRAPING IS PROHIBITED. PLEASE CHANGE
 DETAILS.
  
 54. SHT P30 ICE MACHINE DETAIL. THE WATER FILTER SHALL
 MEET THE REQUIREMENTS OF NSF 42. SECTION 611.1.
  
 55. SUBMIT A CONDENSATE BUILDING ISOMETRIC RISER
 DIAGRAM AND CONDENSATE RISER DIAGRAMS SHOWING ALL PIPE
 SIZES, TRAPS, VENTS, AND INDICATE MATERIAL. SECTIONS
 106.3.5.1.3 & 314.2.2.
  
 56. CONDENSATE IS SHOWN TERMINATING AT THE CATCH BASINS
 IN THE FIRST FLOOR GARAGE. CONCERNS FOR THE POSSIBILITY
 OF THE EXHAUST FUMES ENTERING THE UNITS SHALL BE
 ADDRESSED. PLEASE INDICATE HOW THIS WILL BE ADDRESSED.
 SECTION 106.1.2 (MORE INFORMATION REQUIRED).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ******IMPORTANT****** PLEASE RESUBMIT PLUMBING PLANS
 WITH THE HIGHLIGHTED SHEETS TO HELP EXPEDITE FUTURE
 PLAN REVIEWS. THANK YOU
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  