Plan Review Notes
Plan Review Notes For Permit 08120552
Permit Number 08120552
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-01-10 17:16:12*****DENIED*****
  
 01. THE STRUCTURE WILL BE CONSIDERED A HIGH-RISE AND
 SHALL COMPLY WITH THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 02. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04. THE PROJECT SITE ADDRESS SHALL BE IN THE TILTLE
 BLOCK OF EACH SUBMITTED PLAN SHEET, NONE SHOWN ON THE
 CIVIL AND LANDSCAPE SHEETS.
  
 05. IN ALL BUILDINGS OVER ONE STORY IN HEIGHT, AT LEAST
 ONE STAIRWAY SHALL BE PROVIDED IN AN USABLE CONDITION
 AT ALL TIMES.
  
 06. A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT. THE STANDPIPES SHALL BE PROVIDED WITH
 CONSPICUOUSLY MARKED AND READILY ACCESSIBLE FIRE
 DEPARTMENT CONNECTIONS ON THE OUTSIDE OF THE BUILDING
 AT THE STREET LEVEL AND HAVE AT LEAST ONE STANDARD HOSE
 OUTLET AT EACH FLOOR.
  
 07. WHERE/IF UNDERGROUND WATER MAINS AND FIRE HYDRANTS
 ARE TO BE PROVIDED, THEY SHALL BE INSTALLED,
 COMPLETEED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 08. THERE SHALL BE NO DELAY IN THE INSTALLATION OF FIRE
 PROTECTION EQUI;MENT.
  
 09. THE INSTALLATION OF THE SPRINKLER SYSTEM SHALL BE
 PLACED IN SERVICE AS SOON AS PRACTICABLE.
  
 10. THE PROJECT SITE ADDRESS SHALL BE TEMPORILY POSTED
 PRIOR TO, AND DURING CONSTRUCTION, OR UNTIL SUCH TIME
 THAT THE PERMANENT NUMERICAL ADDRESS IS DIPLAYED ON THE
 EXTERIOR ELEVATION WHICH FRONTS THE BUILDING.
  
 11. LANDSCAPE SHALL NOT INTERFERE OR HINDER
 ACCESSIBILITY TO FIRE HYDRANTS, FIRE DEPARTMENT
 CONNECTIONS, AND (OR) ANY OTHER LIFE/FIRE SAFETY
 SYSTEMS.
  
 12. ON THE LIFE SAFETY SHEETS, NOTE #13, AMEND TO
 REFLECT 2A:10BC RATED FIRE EXTINGUISHERS ARE TO BE USED
 AS PER LOCAL CODES.
  
 13. PLEASE EXPLAIN WHY THERE IS NO LIFE SAFETY PLAN FOR
 FLOORS ABOVE THE 5TH FLOOR.
  
 14. ON THE APPROPIATE EXTERIOR ELEVATION SHEET,
 SHOW/DISPLAY THE NUMERICAL ADDRESS FOR THE SITE. AS PER
 WEST PALM BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.
  
 15. SINCE THE BUILDING WILL BE EQUIPPED WITH FIRE ALARM
 AND FIRE SPRINKLER SYSTEMS, A ACCESS BOX (KNOX) FOR THE
 PREMISES SHALL BE REQUIRED. SHOW/DISPLAY THE LOCATION
 OF THE KNOX BOX ON THE APPROPIATE EXTERIOR ELEVATION
 SHEET. FOR KNOX APPLICATIONS CONTACT WEST PALM BEACH
 FIRE PREVENTION AT 561-804-4724.
  
 16. TRASH CHUTE SHALL COMPLY WITH NFPA 82. ADD COMMENT
 TO DRAWING A9.02 SHEET.
  
 17. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE
 SIGNS SHALL IDENTIFY STAIR NUMBER, FLOOR LEVEL,
 TERMINUS TOP AND BOTTOM.
  
 18. PROVIDE PRESCRIPTIVE STRENGHTS FOR STAIRS'
 HANDRAILS/GUARDRAILS.
  
 19. IN REFERENCE TO THE WIRE SECURITY PARTITION WITH
 DOOR (LEVEL 5, DOOR #45) SHOWN ON SHEET A10.02, CONTACT
 BATTALLION CHIEF (FIRE MARSHAL) MIKE CARSILLO AT
 561-804-4724 FOR FEASIBILITY OF THIS ARRANGEMENT.
  
 20. ON SHEET A11.01, EXPLAIN CRITERIA FOR THE LABELED
 RATING FOR SOME STORAGE DOORS WHILE OTHERS ARE NOT;
 LIST LABELED DOOR FIRE RATING FOR THE FIRE COMMAND
 CENTER - 126, DOMESTIC WATER PUMP - 143, STORAGE ROOM
 -144, ELEVATOR MACHINE ROOM - 205, MECHANICAL ROOM
 (302), POOL EQUIPMENT - 402, BOILER ROOM - 403.
 ELECTRICAL CLOSET - 524, ELECTRICAL CLOSET - 624.
  
 21. DOORS AND WINDOWS REQUIRED TO BE FIRE RATED SHALL
 COMPLY WITH NFPA 80.
  
 22. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE
 SELF-CLOSING AND SELF-LATCHING. ADD COMMENT TO DOOR
 NOTES - SHEET A11.01 - UNDER THE GUEST UNITS SECTION.
  
 23. THERE ARE TWO STAIR #2 SHOWN ON A15.03 & A15.07
 SHEETS. PLEASE EXPLAIN.
  
 24. ON THE LIFE SAFETY SHEETS, SHOW EXIT LIGHTS
 CORRELATING TO THE ELECTRICAL LIGHTING SHEETS.
  
 25. ON SHEET LS1 IN THE EXIT DISCHARGE CALCULATIONS FOR
 THE LOBBY ZONE, THERE ARE TWO EXIT #2'S. AMEND TO
 REFLECT 3 EXITS AS SHOWN ON THE DRAWING. SHEET LS2 THRU
 LS5, CALCULATIONS SHOULD BE FOR STAIR 2 & 3, NOT 1 & 2.
  
 26. IS ANY EMERGENCY LIGHTING (SEE SHEET E10) PROPOSED
 FOR STAIR #1?
  
 27. A FIRE ALARM SYSTEM USING AN APPROVED, EMERGENCY
 VOICE / ALARM COMMUNICATION SYSTEM SHALL BE INSTALLED
 IN ACCORDANCE WITH NFPA 72.
  
 28. INDICATE WHAT MESSAGE IS PLANNED FOR THE FIRE ALARM
 VOICE FEATURE OF THE FIRE ALARM SYSTEM.
  
 29. ON SHEET FA10, FIRE ALARM SEQUENCE OF OPERATIONS -
 D, AMEND TO REFLECT THAT SMOKE DUCT DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 30. AN APPROVED SINGLE-STATION SMOKE ALARM SHALL BE
 INSTALLED IN EVERY GUEST ROOM AND EVERY LIVING AREA AND
 SLEEPING ROOM WITHIN A GUEST SUITE. AMEND TO REFLECT AS
 SUCH ON THE APPROPIATE FA SHEETS, INCLUDING THE FIRE
 ALARM LEGEND (FA9) SHEET. BE ADVISED THAT SMOKE
 DETECTORS (SD) ARE TIED INTO THE BUILDING'S FIRE ALARM
 SYSTEM WHEREAS SMOKE ALARMS (SA) ALERT THE OCCUPANT(S)
 OF THE DWELLING UNIT ONLY.
  
 31. THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH NFPA 13; LISTED QUICK-RESPONSE OR
 RESIDENTIAL SPRINKLERS SHALL BE USED THROUGHOUT GUEST
 ROOMS AND GUEST ROOM SUITES.
  
 32. ALL AREAS OF THE BUILDING TO BE SPRINKLERED. WHY IS
 THERE NO SPRINKLER COVERAGE IN STORAGE ROOMS 125 & 125
 FOR EXAMPLE.
  
 33. KNOX LOCKING CAPS WILL REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. INCLUDE IN SCHEMATIC 3/FP9 ON
 SHEET FP9 DRAWING. FOR APPLICATIONS CONTACT WEST PALM
 BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
 34. IN ADDITION TO ELECTRONIC SWITCHES, CHAIN AND LOCK
 WILL BE REQUIRED ON THE DOUBLE DETECTOR CHECK VALVE
 ASSEMBLY. INCLUDE/SHOW IN SCHEMATIC 4/FP10 ON SHEET
 FP10 DRAWING.
  
 35. A FIRE SPRINKLER PIPE INSPECTION (CODE:603) SHALL
 BE REQUIRED AS PER WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT. REPLACE NOTE ON SHEET FP9 , PIPE
 AND FITTING SPECIFICATION (D) WHICH REFERENCES THE CITY
 OF COCONUT CREEK FLORIDA FIRE RESCUE.
  
 36. EMERGENCY GENERATORS PROVIDING POWER TO EMERGENCY
 LIGHTING SHALL BE INSTALLED, TESTED, AND MAINTAINED IN
 ACCORDANCE WITH NFPA 110.
  
 37. REQUIREMENTS FOR STANDBY POWER SHALL BE AS
 SPECIFIED IN 11.8.4.2 OF NFPA 101, LIFE SAFETY CODE.
  
 38. THE CENTRAL CONTROL STATION (FIRE COMMAND
 CENTER/ROOM) SHALL CONTAIN THE FOLLOWING AS LISTED IN
 11.8.5 OF NFPA 101, LIFE SAFETY CODE.
  
 39. ELEVATORS SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF ASME A17.1, SAFETY CODE FOR ELEVATORS
 AND ESCALATORS. ALL NEW ELEVATORS SHALL CONFORM TO THE
 FIREFIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS.
  
 40. IN HIGH-RISE BUILDINGS, ONE ELEVATOR SHALL BE
 PROVIDED WITH A POWER SUPPLY AND SHALL BE AVAILABLE FOR
 USE BY THE FIRE DEPARTMENT IN CASE OF EMERGENCY AND/OR
 PARAMEDICAL USE.
  
 41. A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR
 ARRANGEMENT, EXIT LOCATIONS, AND ROOM IDENTIFICATION
 SHALL BE POSTED IN AN AHJ APPROVED LOCATION, OR
 IMMEDIATELY ADJACENT TO, EVERY GUEST ROOM DOOR IN
 HOTELS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE COMMENTS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW