| 2009-01-01 16:42:52 | MARRIOTT RESIDENCE INN |
| | |
| | 455 HIBISCUS ST |
| | |
| | |
| | *** DENIED REVIEW ** |
| | |
| | |
| | ** IMPORTANT: |
| | IT IS VERY IMPORTANT TO UNDERSTAND THE REVIEW IS BASED |
| | ON THE PLANS SUBMITTED AT THIS TIME. AS THERE IS MANY |
| | ITEMS NOT YET COMPLETED OR SUBMITTED FOR REVIEW A |
| | COMPLETE REVIEW OF CODE COMPLIANCE DETERMINATION CAN |
| | NOT BE DONE AT THIS TIME. THERE MAY CERTAINLY BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW DUE TO CHANGES IN |
| | PLANS, SUBMITTED DOCUMENTS ETC WHICH IS NOT POSSIBLE TO |
| | BE MADE AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLANS HAVE BEEN SUBMITTED FOR * PLAN REVIEW* |
| | ONLY AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE |
| | KNOW ONCE PERMIT APPLICATION IS MADE ITEMS SUCH AS |
| | LICENSING OF CONTRACTOR, AND OTHER DESIGN PROFESSIONALS |
| | WILL ALL BE VERIFIED AT THAT TIME. PLAN REVIEW DOES NOT |
| | *LOCK* A PROJECT IN UNDER THE CODE IN EFFECT AT THE |
| | TIME OF THE REVIEW. ONLY PLANS SUBMITTED FOR PERMIT |
| | APPLICATION WITH LICENSED CONTRACTOR. THIS IS GIVEN FOR |
| | INFORMATION ONLY AS THE FLORIDA BUILDING CODE IS SET TO |
| | CHANGE ON MARCH 1ST, 2009. |
| | EVEN ONCE ALL ITEMS NOTED FOR CODE COMPLIANCE ARE |
| | ADDRESSED AND PERMIT APPLICATION HAS NOT BEEN MADE THE |
| | REVIEW STATUS WILL STILL REMAIN FAILED. |
| | |
| | 2) NOTE: THE INFORMATION OF THE PROJECT HAS BEEN ROUTED |
| | TO THE ADDRESSING REVIEWER. THE PROJECT WAS SUBMITTED |
| | UNDER AN ADDRESS OF 421 HIBISCUS ON THE PAPERWORK |
| | HOWEVER THE ADDRESS ON PLANS AND NOW IN OUR SYSTEM IS |
| | 455 HIBISCUS. PLEASE BE SURE TO CONFIRM THIS ADDRESS IS |
| | THE FINAL LOCATION. ALL PLANS AND OTHER SUPPORTING |
| | DOCUMENTATION ONCE SUBMITTED WILL NEED TO COORDINATE. |
| | THIS COMMENT IS FOR COORDINATION OF PLANS AND |
| | DOCUMENTS. |
| | |
| | 3) NOTE: THE CODES FOR THIS REVIEWER NEED TO BE STATED |
| | ON PLANS AS FOLLOWS. SOME OF THE CODES BELOW ARE LISTED |
| | AND ACCURATE HOWEVER SOME OTHERS LISTED ON PLANS ARE |
| | NOT CURRENTLY IN EFFECT. PLEASE BE SURE THE FOLLOWING |
| | IS NOTED ON THE ARCHITECTURAL SHEET GN2 AS WELL AS ON |
| | THE ELECTRICAL PLANS. |
| | |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 (NATIONAL ELECTRICAL CODE) |
| | 2003 NFPA-101 (LIFE SAFETY CODE) |
| | 2002 NFPA-72 (NATIONAL FIRE ALARM CODE) |
| | 2003 NFPA-20 ( STANDARD FOR STATIONARY FIRE PUMP) |
| | PLEASE ALSO BE SURE THE FP SHEETS CONTAIN THE REFERENCE |
| | TO NFPA-20 2003. |
| | |
| | ** THESE ARE NOTED FOR THIS REVIEWER. THERE MAY BE |
| | OTHERS NOTED BY OTHER TRADES. |
| | PLEASE SEE SOME NOTES BELOW AS THERE ARE SOME CODE |
| | REFERENCES TO CODES WHICH ARE NO LONGER ADOPTED IN THE |
| | STATE OF FLORIDA. |
| | |
| | 4) NOTE: THE PROJECT AS SUBMITTED IS NOTED AND SHOWN AS |
| | A HOTEL FOR TRANSIENT LODGING. THIS IS NOTED FOR |
| | INFORMATION ONLY. PLEASE BE AWARE OF HOUSE BILL 7121 |
| | WHICH AFFECTED NUMEROUS FLORIDA STATUTES WITH RESPECT |
| | TO RESIDENTIAL HIGH-RISE BUILDINGS. IF THERE IS ANY |
| | INTENT TO CHANGE THE OCCUPANCY OF THE BUILDING TO A |
| | CONDO AT A LATER DATE PLEASE BE AWARE OF SEVERAL |
| | ASPECTS OF THE STATUTES AND STATE LEGISLATION WHICH |
| | WOULD AFFECT DESIGN AS WELL AS CODE REQUIREMENTS. AS |
| | SUBMITTED THIS WOULD NOT AFFECT THE BUILDING AND IS |
| | NOTED FOR INFORMATION ONLY AS SOME OTHER HOTELS HAVE |
| | DONE THIS. |
| | |
| | 5) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 AND FLORIDA STATUTES 481.219. THE TITLE |
| | BLOCKS ON THE LANDSCAPE PLANS ARE MISSING INFORMATION |
| | AS REQUIRED. |
| | THE TITLE BLOCKS ARE MISSING PRINTED NAME AND LICENSE |
| | NUMBER OF THE LANDSCAPE DESIGNER. THE TITLE BLOCKS ARE |
| | ALSO MISSING THE REQUIRED CERTIFICATE OF AUTHORIZATION |
| | NUMBER. THIS REQUIRED ON ALL LANDSCAPE PLANS WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER TRADE REVIEWS. |
| | |
| | 6) NOTE: PLEASE BE SURE ALL RAISED SEALS ARE CLEAR AND |
| | VISIBLE. THE INFORMATION ON RAISED SEAL OF THE |
| | LANDSCAPE ARCHITECT IS NOT CLEAR AND VISIBLE AND COULD |
| | NOT BE READ. ON THE SET REVIEWED THE INFORMATION ON |
| | SEAL SUCH AS LICENSE NUMBER AND NAME COULD NOT BE READ |
| | EVEN USING LEAD RUB. THE VERIFICATION OF LICENSING OF |
| | SAID DESIGNER COULD NOT BE DONE. PLEASE SEE NOTE ABOVE |
| | WITH RESPECT TO PRINTED NAME AND LICENSE NUMBER OF |
| | DESIGNER AS REQUIRED. |
| | |
| | 7) NOTE: ALL EXTERIOR LIGHTING OUTSIDE THE PROPERTY |
| | LINE OR IN THE RIGHT OF WAY AREAS BEING INSTALLED OR |
| | REPLACED SHALL BE UNDER SEPARATE PERMITS. THESE ALSO |
| | MAY NOT BE FED FROM THE ELECTRICAL SERVICE IN THIS |
| | BUILDING. PLEASE CONTACT JONATHAN BRAMLEY OF ENGINEER |
| | SERVICES FOR INFORMATION ON RIGHT OF WAY LIGHTING |
| | SPECIFICS. HIS CONTACT INFORMATION IS [email protected] |
| | OR 561-494-1089. |
| | ALL EXTERIOR LIGHTING WITHIN THE PROPERTY BOUNDARIES |
| | MAY BE FED FROM THIS BUILDING. |
| | |
| | 8) NOTE: THE ELECTRICAL PLANS INDICATE LIGHTING INSIDE |
| | THE FPL VAULT. THIS IS NOT PERMITTED AS THIS IS AN |
| | EASEMENT ARE BELONGING TO FPL AND ALSO TO FPL VAULT |
| | STANDARDS. PLEASE BE SURE TO CONTACT THE FPL |
| | REPRESENTATIVE TO OBTAIN AN SPECIFICS REQUIRED BY FPL. |
| | THE ELECTRICAL LIGHTING ETC AS SHOWN ON PLANS WILL NOT |
| | BE PART OF THIS PERMITTED SCOPE OF WORK. ANY LIGHTING |
| | INSTALLED IN THE FPL VAULT EASEMENT AREA IS UNDER |
| | UTILITY JURISDICTION. |
| | PLANS ALSO IDENTIFY A SUMP PIT. IF THIS PIT CONTAINS |
| | ANY ELECTRICAL SUMP PUMP IT SHALL NOT BE FED FROM THE |
| | ELECTRICAL SERVICE OF THE BUILDING. THIS WOULD ALSO BE |
| | UNDER FPL UTILITY VAULT EASEMENT AREA. |
| | PLEASE BE SURE TO OBTAIN FPL VAULT CONSTRUCTION |
| | STANDARDS OF THE VAULT. IN ANY CASE THE NEC PROVIDES |
| | MINIMUM RATINGS WHICH MUST BE MET FOR WALLS, FLOORS, |
| | DOORS ETC. THESE SHALL BE 3HR MINIMUM AND CONSTRUCTED |
| | OF CONCRETE. IT IS NOT PERMITTED TO HAVE ANY OF THE |
| | CONSTRUCTION MATERIALS OF WALL BOARD AND THE LIKE. AS |
| | THE FPL VAULT WILL NOT CONTAIN SPRINKLERS IT IS NOT |
| | PERMITTED TO GO TO LESSER RATING. |
| | |
| | 9) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| | EGRESS PATHS. SOME WERE SUBMITTED AND SHOWN FOR GARAGE |
| | AREAS HOWEVER THESE ARE NOT ALL EGRESS PATHS. PLEASE BE |
| | SURE TO SEE NFPA-101 7.8.1.3, 7.9.1.2, 7.9.2.2, FBC |
| | 1006.2.1, .2.3. ALL EGRESS STAIRS SHALL CONTAIN A |
| | MINIMUM OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED |
| | TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. |
| | THIS IS BASED ON AN AVERAGE PER FORMULA STATED IN THE |
| | LIFE SAFETY CODE. |
| | ** IMPORTANT** |
| | IF THIS BUILDING IS GOING TO REMAIN OCCUPIED UNDER |
| | EMERGENCY POWER DURING OR AFTER AN EVEN SUCH AS A |
| | HURRICANE OR OTHER TIME WHEN NORMAL POWER IS LOST THE |
| | BUILDING SHALL CONTAIN BATTERY BACK UP LIGHTING IN ALL |
| | EGRESS PATHS TO MEET THE 1FT CANDLE AVERAGE. THE LIFE |
| | SAFETY CODE AS WELL AS CHAPTER 10 OF THE FLORIDA |
| | BUILDING CODE ADDRESSES THE REQUIRED EGRESS LIGHTING TO |
| | EXIT *ALL* OCCUPANTS OUT OF THE BUILDING IN EMERGENCY |
| | EVENT OR LOSS OF NORMAL POWER. |
| | WHEN A BUILDING IS OCCUPIED UNDER EMERGENCY POWER THE |
| | BACK UP SYSTEM OF THE PREVIOUS NORMAL POWER HAS NOW |
| | BECOME THE NORMAL POWER. A LOSS OF ONE BREAKER SUCH AS |
| | THE GENERATOR MAIN OR THE GENERATOR ITSELF GOING DOWN |
| | WOULD REMOVE ALL LIFE SAFETY BACK UP FOR LIGHTING AND |
| | EGRESS PATHS. |
| | PLEASE CALL TO GO OVER OTHER OPTIONS WHICH WOULD |
| | REQUIRE A LETTER THE OWNER WHICH WOULD BE REQUIRED TO |
| | EVACUATE ALL OCCUPANTS WHEN THE BUILDING GOES INTO |
| | EMERGENCY POWER BACK UP. THE WORDING TO THAT AFFECT |
| | WOULD BE GONE OVER AT A LATER DATE IF THAT IS THE |
| | OPTION. |
| | BASED ON THE PLANS SUBMITTED OTHER LOCATIONS WHICH WILL |
| | REQUIRE BATTERY BACK UP LIGHTING FIXTURES OF SOME TYPE |
| | WHETHER OR NOT BUILDING REMAINS OCCUPIED WILL BE THE |
| | STAIRS, EMERGENCY GENERATOR ROOM, FIRE PUMP ROOM, MAIN |
| | ELECTRICAL ROOM, ELEVATOR EQUIPMENT ROOMS AND FIRE |
| | COMMAND ROOM. THERE ARE AREAS OF THE PLANS WHICH DO NOT |
| | MEET THE WIRING REQUIREMENTS AND ARE ALSO REQUIRED TO |
| | CONTAIN BATTERY BACK UP FIXTURE FOR EGRESS LIGHTING. |
| | PLEASE SEE SECTIONS ABOVE AS WELL AS 700.12F, 700.16 |
| | ETC. |
| | ALL STAIRS BASED ON WIRING AS SHOWN ARE REQUIRED TO BE |
| | BATTERY BACK UP. BASED ON CIRCUITING AND SYMBOL LEGEND |
| | WHICH DOE NOT INDICATE THE FIXTURES AS BATTER Y BACK UP |
| | THE GENERATOR MAY NOT BE USED AS THE SOLE BACK UP FOR |
| | EGRESS LIGHTING. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| | FROM THE LIFE SAFETY CODE. 7.9.2.2 |
| | |
| | THE EMERGENCY LIGHTING SYSTEM SHALL BE ARRANGED TO |
| | PROVIDE THE REQUIRED ILLUMINATION AUTOMATICALLY IN THE |
| | EVENT OF ANY INTERRUPTION OF NORMAL LIGHTING DUE TO ANY |
| | OF THE FOLLOWING: |
| | (1) FAILURE OF A PUBLIC UTILITY OR OTHER OUTSIDE |
| | ELECTRICAL POWER SUPPLY |
| | (2) OPENING OF A CIRCUIT BREAKER OR FUSE |
| | (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A |
| | SWITCH CONTROLLING NORMAL LIGHTING FACILITIES |
| | |
| | THERE ARE NUMEROUS LOCATIONS ON PLANS IN WHICH THE |
| | OPENING OR TRIPPING OF SINGLE CIRCUIT BREAKER WILL |
| | LEAVE EGRESS AREAS IN TOTAL DARKNESS. THIS IS WHETHER |
| | OR NOT BUILDING IS OCCUPIED UNDER GENERATOR POWER. |
| | |
| | *** PLEASE SEE NOTES #24 AND #40 ON SHEET E-24 WHICH |
| | CONFLICTS WITH FIXTURES ON SYMBOL LEGEND AND ON PLANS. |
| | |
| | 10) NOTE: THE FIRST FLOOR POWER PLANS CONTAINS A NOTE |
| | FOR THE MAIN ELECTRICAL ROOM AND FIRE PUMP ROOM FOR |
| | SIGNAGE HOWEVER THESE ARE NOT THE ONLY TWO LOCATIONS. |
| | OTHER LOCATIONS SUCH AS THE FIRE COMMAND ROOM AND THE |
| | EMERGENCY GENERATOR ROOM WOULD ALSO REQUIRE SUCH |
| | SIGNAGE. ALL OF THESE ROOMS ARE ALSO REQUIRED TO |
| | CONTAIN PERMANENT MAPPING CONTAINING A LAYOUT OF THE |
| | BUILDING SHOWING THE LOCATIONS OF EACH OF THESE ROOMS |
| | CLEARLY IDENTIFIED. THIS WOULD BE REQUIRED IN ALL ROOMS |
| | NOTING EACH OF THE OTHERS. THIS COMMENT MAY BE ADDRESS |
| | BY NOTES ON PLANS. THIS WILL ONE OF THE REQUIRED ITEMS |
| | BY THE CONTRACTOR TO HAVE ALL SIGNAGE UP FOR ALL MAINS, |
| | ELECTRICAL SERVICES, FIRE PUMPS, FIRE COMMAND ROOM ETC |
| | BEFORE ANY RELEASE OF POWER. THIS IS NOT THE ONLY |
| | REQUIREMENT OTHERS WILL BE DIRECTED AT A LATER DATE BY |
| | THE INSPECTION STAFF. |
| | 230.2E, 700.8,701.9, ETC |
| | |
| | 11) NOTE: PLEASE BE SURE TO LIST ALL OF THE FOLLOWING |
| | ITEMS REQUIRED TO BE LOCATED IN THE FIRE COMMAND ROOM. |
| | NFPA-101 11.8.5 THESE ARE SYSTEMS AT A MINIMUM. PLEASE |
| | SEE NOTES FORM OTHER TRADES SUCH AS THE FIRE MARSHAL |
| | WHICH MAY ALSO NOTE OTHER ITEMS. |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER |
| | SECTION OF THIS CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) SPRINKLER VALVE AND WATER-FLOW ANNUNCIATORS |
| | (6) EMERGENCY GENERATOR STATUS INDICATORS |
| | (7) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | |
| | 12) NOTE: PLEASE BE SURE THE ELEVATION OF ALL EMERGENCY |
| | ELECTRICAL SYSTEMS SUCH AS THE GENERATOR, EQUIPMENT, |
| | FIRE PUMP ETC IS LISTED ON PLANS. THE ELEVATIONS ARE |
| | REQUIRED TO MEET ONE OF THE FOLLOWING; EITHER THE 100 |
| | YEAR STORM ELEVATION OR THE ELEVATION SET FORTH BY THE |
| | SLOSH (SEA, LAKE, OVERLAND SURGES BY HURRICANES) CHARTS |
| | BASED ON A CATEGORY 4 HURRICANE. |
| | AS THE PLANS ALREADY CONTAIN INFORMATION FOR SUMP PIT |
| | IN SOME LOCATIONS OTHER THAN THE ELEVATOR PITS THERE IS |
| | A CONCERN OF THE ELEVATIONS OF EQUIPMENT. |
| | PLEASE PROVIDE THIS INFORMATION. |
| | |
| | 13) NOTE: AS NOTED ABOVE FOR COMPLETE PHOTO-METRICS FOR |
| | EGRESS. PLEASE ALSO INCLUDE THE LIGHTING LEVELS IN THE |
| | EMERGENCY GENERATOR ROOM. PLEASE SEE NFPA-110 7.3.3. |
| | THE LIGHTING LEVELS IN THIS ROOM SHALL BE AT A MINIMUM |
| | OF 30FT CANDLES. |
| | |
| | 14) NOTE: PLEASE ALSO INCLUDE THE LIGHTING LEVELS FOR |
| | ELEVATOR PITS TO MEET THE MINIMUM OF 5 FT CANDLES. |
| | PLEASE SEE NEC 620.23 WHICH CONTAINS REFERENCE TO |
| | MINIMUM REQUIREMENTS. SEE HANDBOOK COMMENTARY; ASME |
| | A17.1-2004, SAFETY CODE FOR ELEVATORS AND ESCALATORS, |
| | REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) AT THE PIT |
| | FLOOR AND REQUIRES LUMINAIRES TO BE EXTERNALLY GUARDED |
| | TO PREVENT ACCIDENTAL BREAKAGE. |
| | THE POWER PLANS AS WELL AS THE LIGHTING PLANS CONTAIN A |
| | *J* WHICH IS NOTED AS A JUNCTION BOX ON THE SYMBOL |
| | LEGEND. AT THIS TIME NO REQUIRED LIGHTING IS SHOWN. |
| | |
| | 15) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS IN |
| | COMPLIANCE WITH ALL SECTIONS OF FLORIDA BUILDING CODE |
| | CHAPTER 13. |
| | PLEASE BE SURE TO SEE AREAS SUCH AS |
| | 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING |
| | PERFORMANCE LEVELS. PLEASE BE SURE TO SEE SECTION NOTES |
| | FOR ITEMS SUCH AS TRACK LIGHTING, HID LIGHTING ETC |
| | WHICH ARE NOT ALWAYS BASED ON BULB WATTAGE. |
| | THE COORDINATION OF ALL ITEMS ON THE INPUT DATA REPORT |
| | FOR *ALL* BUILDING COMPONENTS IS MOST IMPORTANT. THE |
| | LACK OF COORDINATION OF THE IDR WITH THE PLANS IS ONE |
| | OF THE KEY ITEMS IN THE DELAY OF ISSUANCE OF MANY |
| | BUILDING PERMITS. AS THIS PROJECT WAS ONLY SUBMITTED |
| | UNDER PLAN REVIEW THE NEW REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE BEING ADOPTED IN MARCH OF 2009 WILL |
| | GREATLY INCREASE THE STRINGENCY OF THIS CHAPTER OF THE |
| | FBC. |
| | AS NO ENERGY CALCULATIONS WERE SUBMITTED FOR REVIEW IT |
| | IS NOT POSSIBLE TO COMMENT ON CALCULATIONS AT THIS |
| | TIME. |
| | ** ONCE AGAIN WHEN SUBMITTING THE CALCULATIONS ALONG |
| | WITH THE IDR, PLEASE BE SURE ALL ITEMS ON PLANS |
| | COORDINATE WITH THE SUBMITTED CALCULATIONS. |
| | |
| | 16) NOTE: PLEASE SUBMIT LIGHTING PLANS IN COMPLIANCE |
| | WITH THE MINIMUM REQUIREMENTS OF FBC CHAPTER 13 FOR |
| | LIGHTING CONTROLS. PLEASE SEE 13-415.1.ABC.1 WHICH |
| | REQUIRES *ALL* LIGHTING IN ANY BUILDING GREATER THAN 5K |
| | SQ FT TO BE AUTOMATICALLY SHUT OFF WHEN ANY AREA OR |
| | BUILDING IS NOT OCCUPIED. THERE ARE SOME EXCEPTIONS TO |
| | THIS REQUIREMENT HOWEVER MANY AREAS OF THIS BUILDING IS |
| | NOT CONSIDERED 24HR OPERATION OR MEET THE DEFINITIONS |
| | OF PATIENT CARE. THERE WOULD BE SOME AREAS/ROOMS IN |
| | WHICH MAY BE CONSIDERED A HAZARD TO THE OCCUPANTS IF |
| | THE LIGHTING WAS AUTOMATICALLY SHUT OFF SUCH AS THE |
| | ELECTRICAL ROOMS. (SEE NEC 110.26 SECTION FOR |
| | ILLUMINATION) |
| | THERE ARE MANY LOCATIONS ON PLANS WHICH ONLY INDICATE A |
| | STANDARD SINGLE POLE SWITCH FOR THE LIGHTING CONTROLS |
| | WHICH IS NOT PERMITTED. SOME OF THE FOLLOWING LOCATIONS |
| | ARE NOTED FOR EXAMPLE LOCATIONS OF THIS AND IS NOT ALL |
| | LOCATIONS ON PLANS WHICH ARE NOT CODE COMPLIANT. |
| | SEE ROOMS: |
| | 120,121,124,125,123,135,134,133,130,131,107,106,105 ETC |
| | THESE ARE ONLY SOME ROOMS WHICH ARE NOTED FOR EXAMPLE. |
| | THERE ARE MANY OTHERS. |
| | |
| | A) PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 FOR |
| | ALL AREAS WHICH REQUIRE LIGHTING CONTROLS. THE PLANS |
| | CONTAIN A NOTE WHICH MENTIONS THE ENTIRE BUILDING IS |
| | UNDER ENERGY MANAGEMENT HOWEVER BASED ON THE ITEMS |
| | LISTED ABOVE, **ALL ** SEPARATE SPACES WHICH CONTAIN |
| | FLOOR TO CEILING HEIGHT PARTITIONS SUCH AS ROOMS AND |
| | AREAS REQUIRES AN OVER RIDE OF SUCH A SYSTEM OR MEET |
| | THE REQUIREMENTS FOR INDIVIDUAL SPACES. |
| | PLEASE ALSO SEE THE CONTROLS IN THE 13-415.1.ABC.1 (1) |
| | FOR ANY MORE THAN ONE LEVEL WHICH REQUIRES SEPARATE |
| | CONTROLS. |
| | PLEASE SEE FBC 1006.1.2 AND NFPA-10 17.8.1.2.2 FOR ANY |
| | DEVICES CONTROLLING EGRESS LIGHTING AS THESE SHALL BE |
| | *FAIL-SAFE ON* DEVICES. |
| | PLEASE SEE AREAS SUCH AS MULTI-GANG BATHROOMS WHICH |
| | WILL REQUIRE DUAL TECHNOLOGY DEVICES. IN THESE AREAS |
| | AND OTHER POSSIBLE AREAS IT WILL NOT BE PERMISSIBLE TO |
| | USE ONLY MOTION SENSOR TYPE DEVICES. |
| | |
| | B) PLEASE BE SURE TO SEE 13-415.1.ABC.1.4 FOR EXTERIOR |
| | LIGHTING CONTROLS REQUIRED. THERE ARE ONE OF TWO |
| | METHODS PERMITTED FOR CONTROLS. (BOTH MAY BE USED). |
| | IF USING AN ASTRONOMICAL TIME CLOCK PLEASE BE SURE TO |
| | LIST THE MINIMUM REQUIRED PROGRAMMING BATTERY BACK UP |
| | TIME. THE CODE REQUIRES 10HRS MINIMUM. |
| | |
| | C) PLEASE BE SURE TO SEE SECTION 13-415.1.ABC.1.3 AS |
| | NOTED ABOVE TO HOTEL AND MOTEL GUEST ROOMS. THESE SHALL |
| | CONTAIN CONTROLS TO TURN OFF ALL LIGHTING IN THE |
| | GUESTROOMS/SUITES WHEN THEY ARE NOT OCCUPIED. THIS |
| | INCLUDES ALL OUTLETS INCLUDING SWITCHED RECEPTACLES |
| | WHICH MAY CONTAIN LIGHTING FIXTURES WHICH MAY BE OF THE |
| | PLUG-IN TYPE. THE USE OF STANDARD SINGLE POLE OR 3-POLE |
| | SWITCHES IS NOT PERMITTED. THESE DO NOT MEET ANY |
| | AUTOMATED CONTROLS. |
| | |
| | D) PLEASE SEE THERE IS LIGHTING ON PLANS WHICH DO NOT |
| | SHOW ANY LIGHTING CONTROLS AT ALL INCLUDING NO |
| | CIRCUITING ETC. |
| | |
| | E) PLEASE BE SURE TO SEE SOME ROOMS SUCH AS CONFERENCE |
| | ROOMS, EMPLOYEE BREAK ROOMS ETC AS LISTED IN |
| | 13-415.1.ABC.1.2 REQUIRE OCCUPANCY SENSORS WHETHER OR |
| | NOT PART OF ANY BUILDING AUTOMATION SYSTEM. |
| | |
| | F) PLEASE SEE NOTE #31 ON SHEET E24 WHICH CONFLICTS |
| | WITH THE LIGHTING CONTROLS ON PLANS AND INFORMATION |
| | SHOWN/SUBMITTED. |
| | |
| | THE INTENT OF THE ENERGY CODE AND THE MINIMUM FEDERALLY |
| | ADOPTED REQUIREMENTS IS THAT LIGHTING IS TURNED OFF TO |
| | CONSERVE ENERGY WHEN THE ROOM(S) AND AREAS ARE NOT |
| | OCCUPIED. IN JULY OF 2004 THE FEDERAL MANDATES ADOPTED |
| | 1999 ASHRAE 90.1. ALL STATES IN THE US WERE REQUIRED TO |
| | ADOPTED THIS MINIMUM STANDARD OR EQUIVALENT BY THEIR |
| | NEXT CODE CYCLE. THE FEDERAL MANDATES HAVE HAD |
| | ADJUSTMENTS SINCE THAT DATE. THE STATE OF FLORIDA |
| | ADOPTED THE FLORIDA ENERGY EFFICIENCY CODE (CHAPTER 13) |
| | IN THE 2001 FBC CODE CYCLE AND WAS SUBSTANTIALLY |
| | CHANGED IN THE ADOPTION OF THE 2004 FBC OCT 1ST, 2005. |
| | THERE HAVE BEEN SEVERAL REVISIONS TO THE 2004 FBC WHICH |
| | HAVE AFFECT CHAPTER 13 AND MORE SPECIFICALLY LIGHTING |
| | CONTROLS. |
| | ** THIS NOTE GIVES SECTIONS FOR LIGHTING CONTROLS WHICH |
| | ARE REQUIRED TO MEET A *MINIMUM*. THERE ARE MANY |
| | SYSTEMS ON THE MARKET WHICH MEET THE MINIMUM AND MANY |
| | WHICH MEET THE MINIMUM AND ABOVE. THIS OFFICE/REVIEWER |
| | ONLY REQUIRES THE MINIMUM MEETING THE FLORIDA BUILDING |
| | CODE. ANY SYSTEMS CHOSEN BY THE DESIGN TEAM WHICH GO |
| | ABOVE THE MINIMUM REQUIREMENTS OF THE CODE WILL NOT BE |
| | REJECTED AS THEY MOST CERTAINLY MEET THE MINIMUM. |
| | |
| | IF ANY OF THESE ITEMS NEED TO BE GONE OVER IT IS BEING |
| | NOTED TO CALL AND GO OVER ANY QUESTIONS OR COMMENTS. |
| | AS THERE ARE MANY ASPECTS OF THE PLANS WHICH DO NOT |
| | SHOW THE MINIMUM AT THIS TIME THERE MAY BE NEW COMMENTS |
| | ON THE FOLLOWING REVIEW ONCE INFORMATION IS SUBMITTED |
| | OR SHOWN. |
| | PLEASE BE SURE CHECK LISTING PER 110.3 OF ANY PROPOSED |
| | SYSTEMS AND PLEASE SUBMIT COMPLETE SYSTEMS PROPOSAL FOR |
| | ANY BUILDING MANAGEMENT SYSTEM. |
| | |
| | 17) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE FOLLOWING ITEMS. |
| | THE GENERATOR. |
| | FIRE PUMP. |
| | FIRE PUMP CONTROLLER. |
| | ATS (AUTOMATIC TRANSFER SWITCH). |
| | FUEL TANK. THE FUEL TANK WILL BE REVIEWED BY OTHERS) |
| | |
| | MINIMUM EQUIPMENT MEETING THE CODE AT THIS TIME MUST BE |
| | VERIFIED. EVEN IF THE EQUIPMENT IS NOT FINALIZED |
| | EQUIPMENT WILL NEED TO BE CHOSEN AT THIS TIME. THE |
| | MANUFACTURE OR BRAND OF EQUIPMENT MAY ALWAYS BE CHANGED |
| | AT A LATE DATE. |
| | 90.7,110.3, NFPA_20, NFPA-101, NFPA-70, NFPA-110. |
| | FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | 18) NOTE: PLEASE PROVIDE ALL SHUT DOWN OF ALL EQUIPMENT |
| | IN IT ROOM INCLUDING A/C UNIT. THE PLANS DO NOT SHOW |
| | ANY EPO (EMERGENCY POWER OFF) BUTTON AS REQUIRED PER |
| | 645.10. THE PANEL SCHEDULE FEEDING THE IT PANEL AND THE |
| | IT PANEL SCHEDULE ALSO DOES NOT LIST ANY SHUNT TRIP |
| | BREAKERS. PLEASE SEE 645.10 FOR DISCONNECTING |
| | REQUIREMENTS. |
| | PLEASE SEE NEC 645.4 REQUIREMENTS OF AN IT ROOM. WHEN |
| | ANY PROPOSED ROOM DOES MEETS ALL ITEMS LISTED PER 645.4 |
| | THE WIRING METHODS WHICH ARE LESS STRINGENT IN THIS |
| | CODE SECTION MAY NOT BE USED. |
| | PLEASE MEET ALL OF 645.4 OR PLEASE CHANGE DESIGNATION |
| | AND PROVIDE NOTE FOR WIRING METHODS OF CHAPTERS 1-4 |
| | MUST BE USED. IT MAY BE HELPFUL TO CONTACT IT PERSONNEL |
| | FOR MARRIOTT TO CONFIRM WIRING METHODS TO BE USED. |
| | THE FOLLOWING IS EXTRACTED FROM THE NEC FOR EASE OF |
| | CODE SECTIONS: |
| | |
| | |
| | THIS ARTICLE SHALL APPLY, PROVIDED ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) DISCONNECTING MEANS COMPLYING WITH 645.10 ARE |
| | PROVIDED. |
| | (2) A SEPARATE HEATING/VENTILATING/AIR-CONDITIONING |
| | (HVAC) SYSTEM IS PROVIDED THAT IS DEDICATED FOR |
| | INFORMATION TECHNOLOGY EQUIPMENT USE AND IS SEPARATED |
| | FROM OTHER AREAS OF OCCUPANCY. ANY HVAC SYSTEM THAT |
| | SERVES OTHER OCCUPANCIES SHALL BE PERMITTED TO ALSO |
| | SERVE THE INFORMATION TECHNOLOGY EQUIPMENT ROOM IF |
| | FIRE/SMOKE DAMPERS ARE PROVIDED AT THE POINT OF |
| | PENETRATION OF THE ROOM BOUNDARY. SUCH DAMPERS SHALL |
| | OPERATE ON ACTIVATION OF SMOKE DETECTORS AND ALSO BY |
| | OPERATION OF THE DISCONNECTING MEANS REQUIRED BY |
| | 645.10. |
| | FPN: FOR FURTHER INFORMATION, SEE NFPA 75-2003, |
| | STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY |
| | EQUIPMENT, CHAPTER 10, 10.1, 10.1.1, 10.1.2, AND |
| | 10.1.3. |
| | (3) LISTED INFORMATION TECHNOLOGY EQUIPMENT IS |
| | INSTALLED. |
| | (4) THE ROOM IS OCCUPIED ONLY BY THOSE PERSONNEL NEEDED |
| | FOR THE MAINTENANCE AND FUNCTIONAL OPERATION OF THE |
| | INSTALLED INFORMATION TECHNOLOGY EQUIPMENT. |
| | (5) THE ROOM IS SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTANT-RATED WALLS, FLOORS, AND CEILINGS WITH |
| | PROTECTED OPENINGS. |
| | FPN: FOR FURTHER INFORMATION ON ROOM CONSTRUCTION |
| | REQUIREMENTS, SEE NFPA 75-2003, STANDARD FOR THE |
| | PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT, CHAPTER |
| | 5. |
| | |
| | ALL ITEMS ABOVE WITH THE EXCEPTION OF # 1 ABOVE ARE |
| | SHOWN ON PLANS. |
| | |
| | 19) NOTE: PLEASE SEE 110.26 AS THE MAIN ELECTRICAL ROOM |
| | WHICH REQUIRES THE DOORS TO SWING OUTWARD. THE DOORS |
| | SHALL ALSO BE EQUIPMENT WITH PANIC HARDWARE, PRESSURE |
| | PLATES OR OTHER TYPES OF LOCKING MECHANISMS WHICH DOES |
| | NOT IMPEDED THE EGRESS OF ANY PERSONNEL IN THE ROOM IN |
| | THE EVENT OF AN EMERGENCY. AN OCCUPANT WHICH HAS HAD A |
| | FLASH, BURN OR OTHER INJURY NEEDS TO EXIT THE ROOM |
| | WITHOUT HAVING USE HANDS, EYES ETC TO EXIT. THERE ARE |
| | MANY DOCUMENTED CASES IN WHICH THIS IS SUCH A HAZARD. |
| | |
| | 20) NOTE: PLEASE PLACE NOTES ON PLANS FOR SIGNAGE |
| | REQUIRED FOR ARC FLASH OF ALL EQUIPMENT MEETING 110.16 |
| | |
| | 21) NOTE: PLEASE SEE 210.8B2 AS ALL 15 AND 20 AMP 120V |
| | RECEPTACLES IN KITCHEN AND BUFFET AREA WILL BE REQUIRED |
| | TO BE GFI OR GFI PROTECTED. THIS DOE NOT MATTER IF |
| | THESE RECEPTACLES ARE SERVING COUNTER SPACES. |
| | |
| | 22) NOTE: PLEASE SEE 210.63, 210.8B3,4,AND 5. THERE ARE |
| | LOCATIONS ON PLANS IN WHICH REMOTE AIR CONDITIONING OR |
| | REFRIGERATION EQUIPMENT IS NOTED HOWEVER NO RECEPTACLE |
| | FOR SERVICING COULD BE LOCATED ON PLANS. |
| | PLEASE BE SURE ALL LOCATIONS OF OUTSIDE OR ROOF TOP |
| | EQUIPMENT CONTAIN THESE DEVICES FOR SERVICING AS WELL |
| | AS PROTECTION. |
| | |
| | 23) NOTE: PLEASE SEE FBC 3006.2 FOR REQUIRED |
| | CONDITIONING/VENTILATION OF ELEVATOR EQUIPMENT ROOMS. |
| | THE ELECTRICAL PLANS DO SHOW ELECTRICAL FOR ELEVATOR |
| | EQUIPMENT HOWEVER ANY EQUIPMENT ON MECHANICAL PLANS |
| | WHICH ARE BEING INSTALLED TO MEET THIS CODE SECTION |
| | NEEDS OT BE SHOWN ON ELECTRICAL PLANS. |
| | |
| | 24) NOTE: PLEASE SEE 620.23 AS NOTED ABOVE FOR ELEVATOR |
| | PIT AREAS FOR LIGHTING LEVELS. THIS SAME SECTION |
| | REQUIRES THE LIGHTING AS WELL AS RECEPTACLES IN THESE |
| | EQUIPMENT ROOMS TO BE ON DEDICATED CIRCUITS. BASED ON |
| | SHEET E11 WHICH SHOWS THE LIGHTING IN THE ELEVATOR |
| | EQUIPMENT ROOM CIRCUITED TO LIGHTING OF OTHER AREAS |
| | THIS DOES NOT MEET THE CODE SECTION GIVEN. |
| | |
| | 25) NOTE: THE POWER PLANS ARE INCOMPLETE AS THERE NO |
| | ELECTRICAL EQUIPMENT OR POWER SHOWN FOR THE POOL |
| | EQUIPMENT ROOM. |
| | 680,310,240 ETC |
| | FBC106.1.1, 106.1.2 FOR CLARITY, COORDINATION, AND |
| | ADDITIONAL INFORMATION NEEDED ON RECORD PLANS. |
| | |
| | 26) NOTE: PLEASE OBTAIN PHOTO-METRIC LEVELS FOR |
| | SWIMMING POOL AREA FOR ANY NIGHT TIME SWIMMING PER PALM |
| | BEACH COUNTY HEALTH DEPARTMENT. ALL PHOTO-METRICS FOR |
| | ANY SWIMMING AFTER DUSK OR BEFORE DAWN SHALL BE STAMPED |
| | BY THE HEALTH DEPARTMENT. |
| | THIS IS NOT A CITY OF WEST PALM BEACH ADOPTED LEVEL OF |
| | LIGHTING HOWEVER UNLESS PLANS ARE STAMPED PERMIT MAY |
| | NOT BE ISSUED. PLEASE ALSO KEEP IN MIND IF THERE IS NOT |
| | GOING TO BE ANY SWIMMING OUTSIDE OF THE DAYLIGHTS HOURS |
| | PER THE HEALTH DEPARTMENT PLEASE PLACE NOTES ON PLANS |
| | ACCORDINGLY. |
| | |
| | 27) NOTE: ANY PROPOSED LIGHTNING PROTECTION SYSTEM IS |
| | GOING TO BE REQUIRED TO BE UNDER SEPARATE PERMIT. |
| | HOWEVER PLEASE PLACE NOTES ON PLANS THAT ANY PROPOSED |
| | LIGHTNING PROTECTION SYSTEM SHALL MEET NFPA-780. (OR |
| | WORDS TO THAT AFFECT). |
| | THERE ARE MANY SYSTEMS ON THE MARKET WHICH DO NOT MEET |
| | ANY ACCEPTABLE STANDARD AND ARE NOT LISTED TO MEET |
| | NFPA-780. |
| | |
| | 28) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS |
| | PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE |
| | SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE |
| | LIFE SAFETY PLANS. |
| | * TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633, FLORIDA STATUTES* |
| | |
| | 29) NOTE: PLEASE SEE FA PLANS. THERE ARE CODE REFERENCE |
| | TO ADA REQUIREMENTS WHICH ARE NOT PART OF THE CURRENT |
| | ADOPTED CHAPTER 11 OF THE FBC. PLEASE SEE FBC |
| | 11-4.28.1, .2 AND .3 FOR REFERENCES AND PLEASE BE SURE |
| | TO REFLECT THESE CODES. |
| | PLEASE ALSO SEE THERE ARE SEVERAL REFERENCES TO THE |
| | 2002 NATIONAL ELECTRICAL CODE ON FA SHEETS. PROJECT IS |
| | CURRENTLY SUBMITTED FOR REVIEW UNDER THE 2005 NFPA-70/ |
| | NEC. |
| | PLEASE ADJUST NOTES AND REFERENCES ON PLANS. |
| | PLEASE BE SURE ALL HEIGHTS, LOCATIONS AND LEVELS ARE |
| | PER SECTIONS NOTED ABOVE. |
| | |
| | 30) NOTE: PLEASE COORDINATE THE FLOOR PLANS FOR THE |
| | FIRE PUMP ROOM. PLEASE SEE SHEET FP -10 WHICH CONTAINS |
| | A DIFFERENT ROOM LAYOUT INCLUDING DOORS WHICH ARE NOT |
| | THE SAME AS THE REST OF THE PLANS SUBMITTED. |
| | THERE ARE MANY ASPECTS OF NFPA-20 FOR FIRE PUMP ROOMS |
| | WHICH ARE REVIEWED INCLUDING FLOOR DRAINAGE REQUIRED. |
| | COORDINATION OF ALL OF THESE ITEMS IS IMPERATIVE. |
| | NEC 695, NFPA-20 |
| | |
| | 31) NOTE: PLEASE PROVIDE INFORMATION ON FUEL |
| | CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP |
| | AND ALL EMERGENCY SYSTEMS PER 700 AND 701. |
| | PLEASE BE SURE TO INCLUDE 5% FOR SUMP AND 5% FOR |
| | EXPANSION. |
| | PLEASE SEE NFPA-110, NFPA-20 9.6.2.2 |
| | |
| | 32) NOTE: THE FIRE PUMP SERVICE ENTRANCE CONDUCTORS ARE |
| | ALONG WITH OTHER ELECTRICAL SERVICE ENTRANCE CONDUCTORS |
| | ARE NOT PERMITTED TO HAVE MORE THAN 8FT OF UNPROTECTED |
| | CONDUCTORS INSIDE THE BUILDING. 230.70,230.71 PLEASE |
| | SEE NEC FOR CONDUCTORS TO BE CONSIDERED OUTSIDE THE |
| | BUILDING BY DEFINITION (SEE SAME SECTION 695.6 |
| | INCLUDING 230.6) FOR THESE REQUIREMENTS. |
| | THE RISER SHOWS SE CONDUCTORS TO GUTTERS AND THEN TO |
| | THE MAIN SERVICE EQUIPMENT. MOST CERTAINLY THIS WOULD |
| | BE MORE THAN 8 FT OF TOTAL LENGTH OF UNPROTECTED |
| | CONDUCTORS. AS THE NEC DOES NOT PROVIDE THE 8 FT LENGTH |
| | MANY JURISDICTIONS USED TO CONTAIN LOCAL TECHNICAL |
| | AMENDMENTS ALLOWING UP TO 8 FT AND SOME NOT ALLOWING |
| | ANY INSIDE WITHOUT PROTECTION. AS THE TECHNICAL |
| | AMENDMENTS WENT AWAY IN THE 2001 CODE CYCLE THIS AHJ |
| | DOES STILL ALLOW UP TO 8 FT HOWEVER NOT ANY GREATER. |
| | THE NEC IS NO SPECIFIC AND A AHJ COULD PERMIT LESS. |
| | PLEASE ADJUST RISER WITH THE CONDUCTORS AS SHOWN. |
| | |
| | 33) NOTE: THE RISER IS SHOWING *EQUIPMENT GROUNDING |
| | CONDUCTORS* BEFORE THE FIRST MEANS OF SERVICE |
| | DISCONNECT FOR ALL PROPOSED SERVICES INCLUDING THE FIRE |
| | PUMP WHICH IS NOT PERMITTED. AS THE CODE REQUIRES THE |
| | NEUTRAL (GROUNDED) CONDUCTOR TO BE BONDED AT THE FIRST |
| | MEANS OF DISCONNECT IF AN EQUIPMENT GROUND IS INSTALLED |
| | THIS WOULD PARALLEL THE NEUTRAL. THIS WOULD CREATE |
| | OBJECTIONABLE CURRENTS PER 250.6 AND IS NOT PERMITTED. |
| | PLEASE REMOVE AND ADJUST RISER. |
| | 250.6,250.24 ETC. |
| | |
| | 34) NOTE: EMERGENCY EQUIPMENT MAINS AND FIRE PUMP MAINS |
| | NEED TO BE LABELED AS SUCH. FOR EXAMPLE: THE FIRE PUMP |
| | AS SHOWN IS A SEPARATE SERVICE FROM FPL AS REQUIRED. |
| | THE RISER NOTES THIS IS MAIN FOUR OF FIVE HOWEVER THIS |
| | IS THE FIRE PUMP MAIN. |
| | A SECOND EXAMPLE IS THE EMERGENCY MAIN AS SHOWN ON |
| | RISER. THIS IS NOTED AS MAIN 3 OF 3 YET THIS IS |
| | ACTUALLY THE EMERGENCY MAIN ONE OF ONE. |
| | EACH MAIN IN EACH PERMITTED SERVICE NEEDS TO BE |
| | LABELED. |
| | 230.2, 701.9,700.8 AS NOTED ABOVE. |
| | PLEASE ADJUST LABELING. |
| | |
| | 35) NOTE: RISER NOTES THE FIRE PUMP CONTROLLER AS |
| | SERVICE ENTRANCE RATE HOWEVER NO INDICATE OF THIS UNIT |
| | CONTAINING THE BUILT IN TRANSFER SWITCH IS NOTED. |
| | PLEASE SEE NOTES ABOVE AND EXPANDED ON THE FIRE PUMP |
| | CONTROLLER INFORMATION. |
| | 695.4 |
| | PLEASE BE SURE TO SEE NOTES ON TRANSFER SWITCHES. |
| | |
| | 36) NOTE: PLEASE SEE 230.95,240.13 ETC. THE CODE |
| | REQUIRES GROUND FAULT PROTECTION FOR ANY SYSTEMS 150V |
| | OR MORE TO GROUND AND 100AMPS OR OVER. THE RISER |
| | INDICATES GFI PROTECTION WHICH IS CLASS A PROTECTION |
| | FOR PERSONNEL. THIS IS NOT THE SAME KING OF PROTECTION |
| | WHICH IS GFP WHICH IS WHAT IS REQUIRED IN THE SECTIONS |
| | GIVEN. PLEASE PROVIDE INFORMATION ON THE TRANSFER |
| | SWITCHES AND PLEASE SEE THE FOLLOWING COMMENT WHICH MAY |
| | AFFECT THE USE OF 3-POLE OR 4-POLE TRANSFER SWITCHES. |
| | |
| | 37) NOTE: PLEASE SEE NEC |
| | ,250.20,250.30,250.66,240.13.230.95, 700.7D AND 700.26. |
| | GFP PROTECTION IS REQUIRED ON THE NORMAL SIDE OF THE |
| | SERVICE HOWEVER ONLY GROUND FAULT SENSING IS REQUIRED |
| | TO BE ON THE SECONDARY SIDE. THE CODE ACTUALLY DOES NOT |
| | REQUIRE NOR DOES IT RECOMMEND GFP ON THE EMERGENCY |
| | EQUIPMENT. |
| | PLEASE SEVERAL WHITE PAPERS WHICH HAVE NOTES ON THE |
| | ABOVE SITUATION WHEN GROUND FAULT PROTECTION IS |
| | TRIGGERED BY THE CODE. MANY OF THESE IN FACT NOTE A |
| | COORDINATION LOSS OF EQUIPMENT WHEN THE USE OF 3-POLE |
| | ATS SWITCHES IS USED. |
| | PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL |
| | CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING |
| | CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND |
| | THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY |
| | GROUNDED TO ACHIEVE GROUND-FAULT SENSING. |
| | PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM *ASCO* |
| | WHITE PAPERS: |
| | |
| | WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE CODE |
| | AND AN ALTERNATE POWER SUPPLY IS INCLUDED, SWITCHING OF |
| | THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT SHOWN ABOVE |
| | ILLUSTRATES SUCH A CIRCUMSTANCE. THE SERVICE IS LARGER |
| | THAN 1,000 AMPS. CONSEQUENTLY, GROUND FAULT PROTECTION |
| | IS REQUIRED AT THE MAIN SERVICE DISCONNECT AT A |
| | MINIMUM. IF IT IS INSTALLED THERE AND THE GENERATOR |
| | NEUTRAL GROUNDING WAS THROUGH A SOLID CONNECTION TO THE |
| | MAIN SERVICE NEUTRAL, A GROUND FAULT WHEN THE GENERATOR |
| | IS FEEDING THE LOAD WILL CAUSE THE MAIN SERVICE |
| | DISCONNECT TO OPEN. THIS WILL NOT DISCONNECT THE ARCING |
| | FAULT FROM THE GENERATOR. COORDINATION IS THUS LOST." |
| | |
| | THIS HAS BEEN READ AND NOTED BY OTHER MANUFACTURES. |
| | PLEASE OBTAIN AND VERIFY COORDINATION FROM THE PROPOSED |
| | MANUFACTURE AND ADJUST PLANS. |
| | AS THE PLANS DO NOT INDICATE THE USE OF 3 OR 4 POLE |
| | DEVICES AT THIS TIME FINAL COMMENT CAN NOT BE MADE. |
| | PLEASE ALSO SEE GENERATOR GROUNDING DETAIL MAYBE BE |
| | REQUIRED TO BE REVISED. |
| | |
| | 38) NOTE: PLEASE SEE 700.9 OF THE NEC ALONG WITH |
| | EXHIBITS IN 700.1 ETC. |
| | THE RISER INDICATES EMERGENCY/LIFE SAFETY SYSTEMS BEING |
| | WIRED IN WITH LEGALLY REQUIRED SYSTEMS WHICH ARE NOT |
| | PERMITTED. PLEASE ADJUST RISER. PLEASE ALSO KNOW THERE |
| | MAY BE NEW COMMENTS AS SEVERAL ITEMS WILL NEED TO BE |
| | PROVIDED. |
| | *** IMPORTANT** |
| | PLEASE SEE NEC 700 AND 701 DEFINITIONS AND OTHER |
| | ADOPTED CODES AS NOT ALL SYSTEMS, FEEDERS, BRANCH |
| | CIRCUITS ETC AS SHOWN ON RISER AND PANEL SCHEDULES ARE |
| | LIFE SAFETY/EMERGENCY SYSTEMS AS SOME ARE CONSIDERED |
| | LEGALLY REQUIRED. THIS WOULD REQUIRE SEPARATION. |
| | THIS CAN BE GONE OVER. |
| | AN EXAMPLE IS THE ELEVATOR IS THIS OCCUPANCY IS |
| | CONSIDERED LEGALLY REQUIRE AND NOT LIFE SAFETY. THIS IS |
| | A BACK UP REQUIRED TO COME ON IN 60SECONDS INSTEAD OF |
| | THE REQUIRED 10 SECONDS LISTED IN 700 SYSTEMS. |
| | AN ELEVATOR IN A HOSPITAL WOULD BE DIFFERENT AND WOULD |
| | BE CONSIDERED LIFE SAFETY. |
| | THIS COMMENT WILL ALL TIE INTO THE COMMENTS ABOVE WITH |
| | RESPECT TO THE LIGHTING AND BACK UP OF THE EGRESS |
| | LIGHTS. IF ALL MEET THE BATTERY BACK UP THEN THIS WOULD |
| | ONLY BE ONE LEGALLY REQUIRED (701) SYSTEM. THIS WOULD |
| | CHANGE MANY ASPECTS OF THE DESIGN INCLUDING NEXT |
| | COMMENT. |
| | PLEASE BE AWARE OF ANY PHONE SYSTEMS BEING PROPOSED |
| | WHICH WOULD BE REQUIRED TO CONTAIN UPS FOR BACK AS |
| | EMERGENCY COMMUNICATIONS IS REQUIRED TO CONTAIN BACK UP |
| | WHICH MAY THEN BE PART OF THE GENERATOR WHICH IS 10, 60 |
| | SECOND BACK UP. NO DELAY IN PHONE SYSTEM IS PERMITTED. |
| | |
| | 39) NOTE: PLEASE SUBMIT A COMPLETE COORDINATION STUDY |
| | FOR ALL LIFE SAFETY/EMERGENCY SERVICE EQUIPMENT AND |
| | BREAKERS. PLEASE SEE 240.12, 700.27 AND 701.18. THIS |
| | REQUIRES ALL BREAKERS AND EQUIPMENT TO BE COORDINATE. |
| | |
| | 40) NOTE: PLEASE PROVIDE NOTE FOR SUPPORT OF VERTICAL |
| | CONDUCTORS PER 300.19. |
| | |
| | 41) NOTE: PLEASE INDICATE AIC RATING FOR ALL SERVICE |
| | EQUIPMENT INCLUDING RATINGS OF ALL PANELS. 110.9. COULD |
| | NOT LOCATE ALL REQUIRED. |
| | |
| | 42) NOTE: EVEN AS THE SWIMMING POOL IS UNDER A SEPARATE |
| | PERMIT PLEASE SEE 2005 NEC WHICH REQUIRES AN EQUAL |
| | POTENTIAL BOND. |
| | PLEASE PROVIDE DETAIL ON PLANS AS THIS MAY BE PART OF |
| | THE STRUCTURAL ELEMENTS OF THE PROPOSED STRUCTURE AND |
| | POOL AREA. |
| | |
| | 43) NOTE: PLEASE PROVIDE THROUGH WALL AND FLOORS |
| | PENETRATION DETAILS PER 300.21. THE SPREAD OF FIRE IS |
| | REQUIRED TO BE CONTAINED PER SEVERAL ADOPTED REFERENCES |
| | AND STANDARDS. |
| | PLEASE SEE THE HANDBOOK COMMENTARY WHICH PROVIDES THE |
| | REFERENCES SUCH AS NFPA-221,251, ASTM AND ANSI |
| | REQUIREMENTS. |
| | |
| | 44) NOTE: PLEASE COORDINATE ALL ITEMS ON RISER AND |
| | PANEL SCHEDULES. PLEASE SUBMIT COMPLETE PLANS FOR FULL |
| | REVIEW. THERE ARE SEVERAL ASPECTS OF RISER AND PANELS |
| | WHICH ARE NOT COMPLETED. AN EXAMPLE LIST WILL BE GIVEN |
| | OF SOME OF THESE ITEMS. THIS IS NOT A COMPLETE LIST. AS |
| | THERE ARE MANY ITEMS NOT YET COMPLETE OR SUBMITTED |
| | THESE CAN SIMPLY NOT BE REVIEWED. |
| | |
| | A) EXAMPLE: |
| | |
| | B) EXAMPLE: RISER INDICATES MDPLEM AS A MCB( MAIN |
| | CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS |
| | THIS AS MLO (MAIN LUG ONLY). |
| | |
| | C) EXAMPLE: RISER INDICATES MDPHEM AS A MCB( MAIN |
| | CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS |
| | THIS AS MLO (MAIN LUG ONLY). |
| | |
| | D) EXAMPLE: RISER INDICATES MDPL AS A MCB ( MAIN |
| | CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS |
| | THIS AS MLO (MAIN LUG ONLY). |
| | |
| | E) EXAMPLE: RISER INDICATES MDPH AS A MCB( MAIN CIRCUIT |
| | BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS THIS AS MLO |
| | (MAIN LUG ONLY). |
| | |
| | 45) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| | FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED |
| | THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES |
| | A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END |
| | DEVICE ON A CIRCUIT. THIS MAY GREATLY AFFECT FEEDERS OR |
| | BRANCH CIRCUIT CONDUCTORS. |
| | PLEASE SEE 13-413.1ABC.1. |
| | |
| | 46) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER |
| | 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN |
| | THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH FLORIDA |
| | BUILDING COMMISSION/DCA. |
| | |
| | 47) NOTE: PLEASE INCLUDE EFFICIENCY RATINGS OF MOTORS |
| | WHICH SHALL MEET 13-414.1.ABC.1.1. |
| | |
| | 48) NOTE: PLEASE INCLUDE LOAD CALCULATIONS FOR ALL |
| | PANELS AND SERVICES. SOME INFORMATION IS SHOWN ON PLANS |
| | HOWEVER MOST IS NOT COMPLETE AT THIS TIME. |
| | PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%. |
| | 230.42,215.5. |
| | 220. |
| | P |
| | PLEASE SEE SECTIONS SUCH AS 220.12,220.14,220.42, |
| | 220.44 AND OTHERS SUCH AS 220.43 FOR TRACK LIGHTING. |
| | THERE ARE SEVERAL ASPECTS OF THE LOAD CALCULATIONS AND |
| | HOW LOADS WERE DERIVED WHICH NEED TO BE SHOWN |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2 FOR ADDITIONAL |
| | INFORMATION, CLARITY AND COORDINATION. |
| | |
| | 49) NOTE: PLEASE COMPLETE ALL PANELS WITH THE CONDUCTOR |
| | SIZES PER 310.16, 240.4 ETC |
| | MANY ARE NOTED AND SHOWN HOWEVER DUE TO SOME PANELS NOT |
| | BEING COMPLETE AT THIS TIME THIS NOTE REMAINS. |
| | |
| | 50) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND |
| | PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS |
| | AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR |
| | EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM |
| | COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT* |
| | ETC IS NOT ACCEPTABLE. THIS INCLUDES ALL SUITES/ROOMS. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 51) NOTE: THE RISER LENDS TO EACH PANEL FOR UNITS AS |
| | FEED THROUGH HOWEVER THE PANEL SCHEDULES DO NOT |
| | INDICATE ANY FEED THRU NOTES, LUGS ETC. |
| | 240, 215 ETC |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 52) NOTE: PLEASE SEE 210.12 FOR REQUIRED ARC FAULT |
| | PROTECTION FOR UNIT OUTLETS. THIS INCLUDES PROTECTIONS |
| | OF ALL OUTLETS INCLUDING LIGHTS, FANS AND RECEPTACLES. |
| | ** PLEASE BE AWARE OF ANY LIGHTING CONTROL SYSTEMS FOR |
| | DESIGN WHICH MAY BE AFFECTED BY THE REQUIREMENT OF AFCI |
| | PROTECTION. |
| | |
| | 53) NOTE: PLEASE SEE 210.60 OF THE NEC. WHEN A GUEST |
| | ROOM/SUITE FALLS UNDER THE DEFINITION WITH PERMANENT |
| | MEANS OF COOKING ALL THE REQUIREMENTS OF 210.52 MUST BE |
| | MET. |
| | THIS INCLUDES MANY OF FOLLOWING WHICH WILL GREATLY |
| | AFFECT THE PLANS, WIRING, THE LOADS, THE PANEL |
| | SCHEDULES ETC AS SUBMITTED. THE PLANS AT THIS DO NOT |
| | MEET THE CODE WITH RESPECT TO MANY ITEMS. PLEASE SEE |
| | THE FOLLOWING EXAMPLES: |
| | |
| | A) PLEASE SEE 210.52C1-5 FOR RECEPTACLES ALONG KITCHEN |
| | COUNTER SPACES WHICH SHALL MEET SPACING. |
| | THIS INCLUDES PENINSULAR AREAS. |
| | THIS ALSO INCLUDES OTHER SPACING AS THERE ARE UNITS |
| | SUCH AS UNIT *B* WHICH SHOWS MORE THAN FOUR FT BETWEEN |
| | COUNTER TOP RECEPTACLES WHICH IS NOT PERMITTED. |
| | THERE ARE OTHER UNITS ALSO NOT JUST UNIT *B*. SEE UNIT |
| | *S* AS AN EXAMPLE WHICH SHOWS COUNTER SPACE OF 12 |
| | INCHES OR MORE YET NO RECEPTACLE IS SHOWN. |
| | GFCI PROTECTION PER 210.8A6 |
| | |
| | B) PLEASE SEE 210.52B1 FOR THE REQUIRED CIRCUITING |
| | WHICH REQUIRES MINIMUM OF TWO SMALL APPLIANCE CIRCUITS. |
| | EACH CIRCUIT IS REQUIRED TO BE FIGURED PER 220.53 WHICH |
| | REQUIRES 1500VA PER EACH. |
| | SEE ANY AREAS SUCH AS DINING, BREAKFAST AREAS OF THE |
| | LIKE WHICH WILL BE AFFECTED. THE PLANS DO NOT INDICATE |
| | THE DINING, BREAKFAST OR EATING AREA OF THE LIKE. THE |
| | PLANS DO SHOW THE RECEPTACLES IN THE AREAS WHICH WOULD |
| | BE CONSIDERED ONE OF THESE AS ON THE GENERAL LIGHTING |
| | AND RECEPTACLES CIRCUIT WHICH IS NOT PERMITTED. AN AREA |
| | NEEDS TO BE DESIGNATED AND RECEPTACLE WIRING NEEDS TO |
| | BE ADJUSTED. |
| | |
| | C) PLANS DO NOT SHOW ANY RECEPTACLE FOR DISHWASHER. |
| | PLEASE BE SURE TO SEE 210.4 FOR ANY DEVICES SUCH A |
| | SINGLE YOKE BEING FED FROM A TWO BREAKERS WHICH SHALL |
| | MEET DISCONNECTING REQUIREMENTS. |
| | |
| | D) NOTE: PLEASE SEE 210.52D, 210.11C3 AS THE BATHROOM |
| | WIRING SHALL NOT FEED ANY OTHER ROOMS, DEVICES, OUTLETS |
| | ETC. THIS NEEDS TO BE SPECIFIED AS THE DEDICATED |
| | BATHROOM CIRCUIT AS NOTED ABOVE PER 408.4. |
| | |
| | 54) NOTE: PLEASE SEE FBC 1019.1.25 AS NO OTHER SYSTEMS |
| | ARE PERMITTED IN THE VERTICAL EGRESS STAIRS WITH THE |
| | EXCEPTION OF THOSE SYSTEMS REQUIRED TO BE PART OF THE |
| | STAIRS. SHEET E-16 INDICATES A SWITCH FOR A LIGHT |
| | FIXTURE ON THE ROOF TOP. THE SWITCH IN THIS LOCATION IS |
| | NOT PERMITTED. |
| | PLEASE ALSO PROVIDE LIGHTING PER EGRESS OF ROOF AREAS |
| | INCLUDING MEETING LIGHTING CONTROLS PER FBC |
| | 13-415.1.ABC.1.4. |
| | |
| | 55) NOTE: PLEASE BE SURE TO SHOW/IDENTIFY THE REQUIRED |
| | SMOKE ALARMS, DETECTORS, AND CARBON MONOXIDE DETECTORS |
| | ON UNIT ROOM LAYOUT FOR ELECTRICAL PLANS AS THE FIRE |
| | ALARM WILL BE UNDER SEPARATE PERMIT. |
| | |
| | 56) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCE FOR |
| | ELECTRICAL PANELS. SOME SHOW FURNITURE IN FRONT OF |
| | PANELS. LOCATION NEEDS TO MEET 110.26. |
| | PLEASE ALSO PROVIDE A LAYOUT OF ALL ELECTRICAL, FIRE |
| | PUMP ROOMS ETC SO COMPLIANCE FOR MINIMUM CLEARANCES |
| | AREA REVIEWED. |
| | PLEASE SEE NOTES ABOVE WITH RESPECT TO PERMITTED |
| | SYSTEMS SUCH AS 700 AND 701 IN THE SAME LOCATIONS. |
| | NFPA-110 SECTION 7.2.2 AS EPSS EQUIPMENT SHALL NOT BE |
| | INSTALLED IN THE SAME ROOM WHERE THE NORMAL ELECTRICAL |
| | SERVICE EQUIPMENT IS INSTALLED. THE CODE; SECTION |
| | 7.2.2.1 DOES PERMIT TRANSFER SWITCHES TO BE INSTALLED |
| | IN THE NORMAL ELECTRICAL SERVICE ROOM ONLY WHERE TWICE |
| | THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF NFPA 70, |
| | NATIONAL ELECTRICAL CODE, EXISTS BETWEEN EQUIPMENT |
| | ENCLOSURES. |
| | EMERGENCY EQUIPMENT ROOMS WITH THE 2HR RATING AS |
| | REQUIRED PER 7.2.1.1 PROVIDES THE SAFE LOCATION SO ANY |
| | FIRE IN THE MAIN SWITCH GEAR BY AN EXPLOSION ETC WOULD |
| | NOT DAMAGE THE LIFE SAFETY OR LEGALLY REQUIRED SYSTEMS. |
| | PLEASE SEE LOCATION WHERE THE GENERATOR IS RUNNING AT |
| | FULL SPEED CAN ALSO BE DISTRACTING FOR ANY EMERGENCY |
| | PERSONNEL WHEN ATTEMPTING TO SHUT DOWN ANY SPECIFIC |
| | SYSTEMS. MEETING THE SECTION ABOVE FOR SEPARATION AND |
| | CLEARANCE REQUIREMENTS NEEDS TO BE ADDRESSED. |
| | LOCATIONS OF ALL ELECTRICAL EQUIPMENT NEED TO BE |
| | VERIFIED. |
| | |
| | PLEASE COMPLETE PLANS WITH ALL FURNITURE AS PROPOSED. |
| | |
| | 57) NOTE: PLEASE SEE 210.8B3,4 AND 5 OF THE 2005 NEC |
| | WHICH REQUIRES ALL RECEPTACLES OUTSIDE EVEN IF FOR |
| | DEDICATE EQUIPMENT SUCH AS DRINKING FOUNTAINS TO BE |
| | GFI/ GFI PROTECTED. PLEASE SEE FOUNTAIN ON ROOF TOP |
| | PLANS WHICH NEEDS TO MEET THIS. |
| | CIR 567L-13 |
| | |
| | 58) NOTE: PLEASE SUBMIT A COMPLETE FIXTURE LEGEND FOR |
| | ALL SPECIFIC FIXTURES. THERE ARE SEVERAL ITEMS FOR FBC |
| | CHAPTER 13 AS NOTED ABOVE ALONG WITH OTHER ITEMS SUCH |
| | AS POOL AREA LIGHTS WHICH NEED TO BE REVIEWED. |
| | PLEASE SEE 411.4B, 680.22 AND 680.23 WHICH WILL GREATLY |
| | AFFECT THE REVIEW FOR TYPES OF FIXTURES PERMITTED. |
| | PLEASE PLACE NOTE ON LIGHTING PLANS FOR POOL AREA WHICH |
| | DOES NOT PERMIT ANY LOW VOLTAGE LIGHTING SYSTEMS WITHIN |
| | 10FT OF THE WATERS EDGE. |
| | FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION, CLARITY |
| | AND COORDINATION. |
| | |
| | 59) NOTE: PLEASE KEEP IN MIND TO INDICATE THE REQUIRED |
| | WIND LOAD RATINGS FOR ANY ROOF-TOP OR OUTSIDE POLE |
| | LIGHT PER SECTION 1609 OF THE FBC. THE CALCULATIONS |
| | WHICH NEED TO BE SUBMITTED WILL NEED TO SHOW THE EPA |
| | (EFFECTIVE PROJECTED AREA) OF ANY PROPOSED LIGHT |
| | FIXTURE. THE CALCULATIONS WILL BE PART OF THE |
| | STRUCTURAL REVIEW ONCE SHOWN AND SUBMITTED. |
| | ELECTRICAL PLANS MUST SHOW MINIMUM WIND LOAD DESIGNS. |
| | |
| | 60) NOTE: IF A GUTTER IS STILL GOING TO BE PART OF THE |
| | FUTURE SERVICE PROPOSED DESIGN; PLEASE INCLUDE |
| | DIMENSIONS. NEC 366 |
| | THIS INCLUDES ANY OTHER PROPOSED GUTTERS IF THEY ARE |
| | STILL PART OF THE DESIGN. |
| | PLEASE KEEP IN MIND PREVIOUS COMMENTS ABOVE WITH |
| | RESPECT TO NO MORE THAN 8FT OF TOTAL LENGTH OF |
| | UNPROTECTED CONDUCTORS. |
| | |
| | 61) NOTE: THE RISER CONTAINS NOTES AND DETAIL FOR THE |
| | GROUNDING ELECTRODE SYSTEM HOWEVER THIS SEEMS TO BE |
| | MISSING THE REQUIRED FOUNDATION/FOOTER STEEL PER |
| | 250.50. THE NOTE ON RISER MENTIONS *BUILDING STEEL* |
| | HOWEVER THIS BY DEFINITION THIS WOULD BE PART OF THE |
| | STRUCTURAL STEEL FOR THE BUILDING. THE |
| | FOUNDATION/FOOTER STEEL WOULD BE AT THE LOWEST POINT OF |
| | THE BOTTOM OF SUCH FOUNDATION. |
| | THIS MAY HAVE BEEN WHAT WAS MEANT BY NOTE HOWEVER THERE |
| | MAY BE SOME BUILDING STEEL EVEN IF POST TENSION CABLES |
| | SEEMS TO BE THE CONSTRUCTION SYSTEM. |
| | PLEASE ADJUST NOTE TO ALLEVIATE ANY CONFUSION. |
| | |
| | 62) NOTE: PLEASE SEE SHEET E1 WHICH INDICATES A PANEL |
| | FP, YET THIS IS NOT ON RISER AND NO PANEL SCHEDULE |
| | COULD BE LOCATED. |
| | IF THIS IS PART OF THE FIRE PUMP, OR CONTROLLER PLEASE |
| | SEE NOTES ABOVE WITH RESPECT TO MORE INFORMATION |
| | NEEDED. |
| | 695,408,215.5 ETC |
| | |
| | 63) NOTE: PLEASE PLACE NOTE ON PLANS FOR COLOR CODING |
| | FOR 277/480V SYSTEMS AS FOLLOWS: |
| | BROWN, PURPLED, AND YELLOW. |
| | PLEASE KNOW AS THE NEC DOES NOT PROVIDE COLOR CODING OF |
| | ALL SYSTEMS AND ORANGE IS FOR OPEN DELTA HIGH LEG |
| | SYSTEMS THE CITY OF WEST PALM BEACH USED TO HAVE |
| | TECHNICAL AMENDMENTS FOR THIS ITEM. THE LOCAL TECHNICAL |
| | AMENDMENTS ARE NO LONGER IN EFFECT HOWEVER IN KEEPING |
| | WITH THE UNIFORMITY WITH ALL OTHER BUILDING SYSTEMS |
| | WITHIN THIS JURISDICTION AND IN THE INTEREST OF LIFE |
| | SAFETY AND FIRE HAZARD THE ABOVE COLOR CODING IS |
| | REQUIRED PER 90.4. |
| | |
| | 64) NOTE: PLEASE INDICATE THE REQUIRED SIGN CIRCUIT PER |
| | 600.5. |
| | |
| | 65) NOTE: PLEASE CHECK WITH THE LOCAL FAA AUTHORITY FOR |
| | REQUIREMENTS OF ANY AIRCRAFT WARNING LIGHTS WHICH MAY |
| | BE REQUIRED. PLEASE CHECK WITH THE FAA WEBSITE OR |
| | CONTACT THE LOCAL AIRPORT AUTHORITY. |
| | THIS WILL AFFECT ELECTRICAL ON PLANS IF SO REQUIRED. |
| | ( OTHER HIGH-RISE BUILDINGS IN AREA DO CONTAIN |
| | LIGHTING). |
| | |
| | |
| | |
| | ** PLEASE BE SURE TO SUBMIT THE ABOVE INFORMATION AS |
| | WELL AS INFORMATION NOT YET SUBMITTED. |
| | PLEASE CALL TO GO OVER ANY COMMENTS WHICH MAY NOT BE |
| | CLEAR IN ANY MANNER. CONTACT INFORMATION IS BELOW. IF |
| | VOICE MAIL IS CONTACTED PLEASE BE SURE TO LISTEN TO |
| | MESSAGE AS I MAY NOT BE IN THE OFFICE. |
| | PLEASE LEAVE A MESSAGE WHEN CALLING AND THE CALL WILL |
| | BE RETURNED AS SOON AS POSSIBLE. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |