2009-01-01 16:42:52MARRIOTT RESIDENCE INN
  
 455 HIBISCUS ST
  
  
 *** DENIED REVIEW **
  
  
 ** IMPORTANT:
 IT IS VERY IMPORTANT TO UNDERSTAND THE REVIEW IS BASED
 ON THE PLANS SUBMITTED AT THIS TIME. AS THERE IS MANY
 ITEMS NOT YET COMPLETED OR SUBMITTED FOR REVIEW A
 COMPLETE REVIEW OF CODE COMPLIANCE DETERMINATION CAN
 NOT BE DONE AT THIS TIME. THERE MAY CERTAINLY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW DUE TO CHANGES IN
 PLANS, SUBMITTED DOCUMENTS ETC WHICH IS NOT POSSIBLE TO
 BE MADE AT THIS TIME.
  
  
 1) NOTE: PLANS HAVE BEEN SUBMITTED FOR * PLAN REVIEW*
 ONLY AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE
 KNOW ONCE PERMIT APPLICATION IS MADE ITEMS SUCH AS
 LICENSING OF CONTRACTOR, AND OTHER DESIGN PROFESSIONALS
 WILL ALL BE VERIFIED AT THAT TIME. PLAN REVIEW DOES NOT
 *LOCK* A PROJECT IN UNDER THE CODE IN EFFECT AT THE
 TIME OF THE REVIEW. ONLY PLANS SUBMITTED FOR PERMIT
 APPLICATION WITH LICENSED CONTRACTOR. THIS IS GIVEN FOR
 INFORMATION ONLY AS THE FLORIDA BUILDING CODE IS SET TO
 CHANGE ON MARCH 1ST, 2009.
 EVEN ONCE ALL ITEMS NOTED FOR CODE COMPLIANCE ARE
 ADDRESSED AND PERMIT APPLICATION HAS NOT BEEN MADE THE
 REVIEW STATUS WILL STILL REMAIN FAILED.
  
 2) NOTE: THE INFORMATION OF THE PROJECT HAS BEEN ROUTED
 TO THE ADDRESSING REVIEWER. THE PROJECT WAS SUBMITTED
 UNDER AN ADDRESS OF 421 HIBISCUS ON THE PAPERWORK
 HOWEVER THE ADDRESS ON PLANS AND NOW IN OUR SYSTEM IS
 455 HIBISCUS. PLEASE BE SURE TO CONFIRM THIS ADDRESS IS
 THE FINAL LOCATION. ALL PLANS AND OTHER SUPPORTING
 DOCUMENTATION ONCE SUBMITTED WILL NEED TO COORDINATE.
 THIS COMMENT IS FOR COORDINATION OF PLANS AND
 DOCUMENTS.
  
 3) NOTE: THE CODES FOR THIS REVIEWER NEED TO BE STATED
 ON PLANS AS FOLLOWS. SOME OF THE CODES BELOW ARE LISTED
 AND ACCURATE HOWEVER SOME OTHERS LISTED ON PLANS ARE
 NOT CURRENTLY IN EFFECT. PLEASE BE SURE THE FOLLOWING
 IS NOTED ON THE ARCHITECTURAL SHEET GN2 AS WELL AS ON
 THE ELECTRICAL PLANS.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70 (NATIONAL ELECTRICAL CODE)
 2003 NFPA-101 (LIFE SAFETY CODE)
 2002 NFPA-72 (NATIONAL FIRE ALARM CODE)
 2003 NFPA-20 ( STANDARD FOR STATIONARY FIRE PUMP)
 PLEASE ALSO BE SURE THE FP SHEETS CONTAIN THE REFERENCE
 TO NFPA-20 2003.
  
 ** THESE ARE NOTED FOR THIS REVIEWER. THERE MAY BE
 OTHERS NOTED BY OTHER TRADES.
 PLEASE SEE SOME NOTES BELOW AS THERE ARE SOME CODE
 REFERENCES TO CODES WHICH ARE NO LONGER ADOPTED IN THE
 STATE OF FLORIDA.
  
 4) NOTE: THE PROJECT AS SUBMITTED IS NOTED AND SHOWN AS
 A HOTEL FOR TRANSIENT LODGING. THIS IS NOTED FOR
 INFORMATION ONLY. PLEASE BE AWARE OF HOUSE BILL 7121
 WHICH AFFECTED NUMEROUS FLORIDA STATUTES WITH RESPECT
 TO RESIDENTIAL HIGH-RISE BUILDINGS. IF THERE IS ANY
 INTENT TO CHANGE THE OCCUPANCY OF THE BUILDING TO A
 CONDO AT A LATER DATE PLEASE BE AWARE OF SEVERAL
 ASPECTS OF THE STATUTES AND STATE LEGISLATION WHICH
 WOULD AFFECT DESIGN AS WELL AS CODE REQUIREMENTS. AS
 SUBMITTED THIS WOULD NOT AFFECT THE BUILDING AND IS
 NOTED FOR INFORMATION ONLY AS SOME OTHER HOTELS HAVE
 DONE THIS.
  
 5) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUTES 481.219. THE TITLE
 BLOCKS ON THE LANDSCAPE PLANS ARE MISSING INFORMATION
 AS REQUIRED.
 THE TITLE BLOCKS ARE MISSING PRINTED NAME AND LICENSE
 NUMBER OF THE LANDSCAPE DESIGNER. THE TITLE BLOCKS ARE
 ALSO MISSING THE REQUIRED CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS REQUIRED ON ALL LANDSCAPE PLANS WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADE REVIEWS.
  
 6) NOTE: PLEASE BE SURE ALL RAISED SEALS ARE CLEAR AND
 VISIBLE. THE INFORMATION ON RAISED SEAL OF THE
 LANDSCAPE ARCHITECT IS NOT CLEAR AND VISIBLE AND COULD
 NOT BE READ. ON THE SET REVIEWED THE INFORMATION ON
 SEAL SUCH AS LICENSE NUMBER AND NAME COULD NOT BE READ
 EVEN USING LEAD RUB. THE VERIFICATION OF LICENSING OF
 SAID DESIGNER COULD NOT BE DONE. PLEASE SEE NOTE ABOVE
 WITH RESPECT TO PRINTED NAME AND LICENSE NUMBER OF
 DESIGNER AS REQUIRED.
  
 7) NOTE: ALL EXTERIOR LIGHTING OUTSIDE THE PROPERTY
 LINE OR IN THE RIGHT OF WAY AREAS BEING INSTALLED OR
 REPLACED SHALL BE UNDER SEPARATE PERMITS. THESE ALSO
 MAY NOT BE FED FROM THE ELECTRICAL SERVICE IN THIS
 BUILDING. PLEASE CONTACT JONATHAN BRAMLEY OF ENGINEER
 SERVICES FOR INFORMATION ON RIGHT OF WAY LIGHTING
 SPECIFICS. HIS CONTACT INFORMATION IS [email protected]
 OR 561-494-1089.
 ALL EXTERIOR LIGHTING WITHIN THE PROPERTY BOUNDARIES
 MAY BE FED FROM THIS BUILDING.
  
 8) NOTE: THE ELECTRICAL PLANS INDICATE LIGHTING INSIDE
 THE FPL VAULT. THIS IS NOT PERMITTED AS THIS IS AN
 EASEMENT ARE BELONGING TO FPL AND ALSO TO FPL VAULT
 STANDARDS. PLEASE BE SURE TO CONTACT THE FPL
 REPRESENTATIVE TO OBTAIN AN SPECIFICS REQUIRED BY FPL.
 THE ELECTRICAL LIGHTING ETC AS SHOWN ON PLANS WILL NOT
 BE PART OF THIS PERMITTED SCOPE OF WORK. ANY LIGHTING
 INSTALLED IN THE FPL VAULT EASEMENT AREA IS UNDER
 UTILITY JURISDICTION.
 PLANS ALSO IDENTIFY A SUMP PIT. IF THIS PIT CONTAINS
 ANY ELECTRICAL SUMP PUMP IT SHALL NOT BE FED FROM THE
 ELECTRICAL SERVICE OF THE BUILDING. THIS WOULD ALSO BE
 UNDER FPL UTILITY VAULT EASEMENT AREA.
 PLEASE BE SURE TO OBTAIN FPL VAULT CONSTRUCTION
 STANDARDS OF THE VAULT. IN ANY CASE THE NEC PROVIDES
 MINIMUM RATINGS WHICH MUST BE MET FOR WALLS, FLOORS,
 DOORS ETC. THESE SHALL BE 3HR MINIMUM AND CONSTRUCTED
 OF CONCRETE. IT IS NOT PERMITTED TO HAVE ANY OF THE
 CONSTRUCTION MATERIALS OF WALL BOARD AND THE LIKE. AS
 THE FPL VAULT WILL NOT CONTAIN SPRINKLERS IT IS NOT
 PERMITTED TO GO TO LESSER RATING.
  
 9) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS. SOME WERE SUBMITTED AND SHOWN FOR GARAGE
 AREAS HOWEVER THESE ARE NOT ALL EGRESS PATHS. PLEASE BE
 SURE TO SEE NFPA-101 7.8.1.3, 7.9.1.2, 7.9.2.2, FBC
 1006.2.1, .2.3. ALL EGRESS STAIRS SHALL CONTAIN A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED
 TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 THIS IS BASED ON AN AVERAGE PER FORMULA STATED IN THE
 LIFE SAFETY CODE.
 ** IMPORTANT**
 IF THIS BUILDING IS GOING TO REMAIN OCCUPIED UNDER
 EMERGENCY POWER DURING OR AFTER AN EVEN SUCH AS A
 HURRICANE OR OTHER TIME WHEN NORMAL POWER IS LOST THE
 BUILDING SHALL CONTAIN BATTERY BACK UP LIGHTING IN ALL
 EGRESS PATHS TO MEET THE 1FT CANDLE AVERAGE. THE LIFE
 SAFETY CODE AS WELL AS CHAPTER 10 OF THE FLORIDA
 BUILDING CODE ADDRESSES THE REQUIRED EGRESS LIGHTING TO
 EXIT *ALL* OCCUPANTS OUT OF THE BUILDING IN EMERGENCY
 EVENT OR LOSS OF NORMAL POWER.
 WHEN A BUILDING IS OCCUPIED UNDER EMERGENCY POWER THE
 BACK UP SYSTEM OF THE PREVIOUS NORMAL POWER HAS NOW
 BECOME THE NORMAL POWER. A LOSS OF ONE BREAKER SUCH AS
 THE GENERATOR MAIN OR THE GENERATOR ITSELF GOING DOWN
 WOULD REMOVE ALL LIFE SAFETY BACK UP FOR LIGHTING AND
 EGRESS PATHS.
 PLEASE CALL TO GO OVER OTHER OPTIONS WHICH WOULD
 REQUIRE A LETTER THE OWNER WHICH WOULD BE REQUIRED TO
 EVACUATE ALL OCCUPANTS WHEN THE BUILDING GOES INTO
 EMERGENCY POWER BACK UP. THE WORDING TO THAT AFFECT
 WOULD BE GONE OVER AT A LATER DATE IF THAT IS THE
 OPTION.
 BASED ON THE PLANS SUBMITTED OTHER LOCATIONS WHICH WILL
 REQUIRE BATTERY BACK UP LIGHTING FIXTURES OF SOME TYPE
 WHETHER OR NOT BUILDING REMAINS OCCUPIED WILL BE THE
 STAIRS, EMERGENCY GENERATOR ROOM, FIRE PUMP ROOM, MAIN
 ELECTRICAL ROOM, ELEVATOR EQUIPMENT ROOMS AND FIRE
 COMMAND ROOM. THERE ARE AREAS OF THE PLANS WHICH DO NOT
 MEET THE WIRING REQUIREMENTS AND ARE ALSO REQUIRED TO
 CONTAIN BATTERY BACK UP FIXTURE FOR EGRESS LIGHTING.
 PLEASE SEE SECTIONS ABOVE AS WELL AS 700.12F, 700.16
 ETC.
 ALL STAIRS BASED ON WIRING AS SHOWN ARE REQUIRED TO BE
 BATTERY BACK UP. BASED ON CIRCUITING AND SYMBOL LEGEND
 WHICH DOE NOT INDICATE THE FIXTURES AS BATTER Y BACK UP
 THE GENERATOR MAY NOT BE USED AS THE SOLE BACK UP FOR
 EGRESS LIGHTING.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE LIFE SAFETY CODE. 7.9.2.2
  
 THE EMERGENCY LIGHTING SYSTEM SHALL BE ARRANGED TO
 PROVIDE THE REQUIRED ILLUMINATION AUTOMATICALLY IN THE
 EVENT OF ANY INTERRUPTION OF NORMAL LIGHTING DUE TO ANY
 OF THE FOLLOWING:
 (1) FAILURE OF A PUBLIC UTILITY OR OTHER OUTSIDE
 ELECTRICAL POWER SUPPLY
 (2) OPENING OF A CIRCUIT BREAKER OR FUSE
 (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A
 SWITCH CONTROLLING NORMAL LIGHTING FACILITIES
  
 THERE ARE NUMEROUS LOCATIONS ON PLANS IN WHICH THE
 OPENING OR TRIPPING OF SINGLE CIRCUIT BREAKER WILL
 LEAVE EGRESS AREAS IN TOTAL DARKNESS. THIS IS WHETHER
 OR NOT BUILDING IS OCCUPIED UNDER GENERATOR POWER.
  
 *** PLEASE SEE NOTES #24 AND #40 ON SHEET E-24 WHICH
 CONFLICTS WITH FIXTURES ON SYMBOL LEGEND AND ON PLANS.
  
 10) NOTE: THE FIRST FLOOR POWER PLANS CONTAINS A NOTE
 FOR THE MAIN ELECTRICAL ROOM AND FIRE PUMP ROOM FOR
 SIGNAGE HOWEVER THESE ARE NOT THE ONLY TWO LOCATIONS.
 OTHER LOCATIONS SUCH AS THE FIRE COMMAND ROOM AND THE
 EMERGENCY GENERATOR ROOM WOULD ALSO REQUIRE SUCH
 SIGNAGE. ALL OF THESE ROOMS ARE ALSO REQUIRED TO
 CONTAIN PERMANENT MAPPING CONTAINING A LAYOUT OF THE
 BUILDING SHOWING THE LOCATIONS OF EACH OF THESE ROOMS
 CLEARLY IDENTIFIED. THIS WOULD BE REQUIRED IN ALL ROOMS
 NOTING EACH OF THE OTHERS. THIS COMMENT MAY BE ADDRESS
 BY NOTES ON PLANS. THIS WILL ONE OF THE REQUIRED ITEMS
 BY THE CONTRACTOR TO HAVE ALL SIGNAGE UP FOR ALL MAINS,
 ELECTRICAL SERVICES, FIRE PUMPS, FIRE COMMAND ROOM ETC
 BEFORE ANY RELEASE OF POWER. THIS IS NOT THE ONLY
 REQUIREMENT OTHERS WILL BE DIRECTED AT A LATER DATE BY
 THE INSPECTION STAFF.
 230.2E, 700.8,701.9, ETC
  
 11) NOTE: PLEASE BE SURE TO LIST ALL OF THE FOLLOWING
 ITEMS REQUIRED TO BE LOCATED IN THE FIRE COMMAND ROOM.
 NFPA-101 11.8.5 THESE ARE SYSTEMS AT A MINIMUM. PLEASE
 SEE NOTES FORM OTHER TRADES SUCH AS THE FIRE MARSHAL
 WHICH MAY ALSO NOTE OTHER ITEMS.
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER
 SECTION OF THIS CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) SPRINKLER VALVE AND WATER-FLOW ANNUNCIATORS
 (6) EMERGENCY GENERATOR STATUS INDICATORS
 (7) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (8) FIRE PUMP STATUS INDICATORS
 (9) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
  
 12) NOTE: PLEASE BE SURE THE ELEVATION OF ALL EMERGENCY
 ELECTRICAL SYSTEMS SUCH AS THE GENERATOR, EQUIPMENT,
 FIRE PUMP ETC IS LISTED ON PLANS. THE ELEVATIONS ARE
 REQUIRED TO MEET ONE OF THE FOLLOWING; EITHER THE 100
 YEAR STORM ELEVATION OR THE ELEVATION SET FORTH BY THE
 SLOSH (SEA, LAKE, OVERLAND SURGES BY HURRICANES) CHARTS
 BASED ON A CATEGORY 4 HURRICANE.
 AS THE PLANS ALREADY CONTAIN INFORMATION FOR SUMP PIT
 IN SOME LOCATIONS OTHER THAN THE ELEVATOR PITS THERE IS
 A CONCERN OF THE ELEVATIONS OF EQUIPMENT.
 PLEASE PROVIDE THIS INFORMATION.
  
 13) NOTE: AS NOTED ABOVE FOR COMPLETE PHOTO-METRICS FOR
 EGRESS. PLEASE ALSO INCLUDE THE LIGHTING LEVELS IN THE
 EMERGENCY GENERATOR ROOM. PLEASE SEE NFPA-110 7.3.3.
 THE LIGHTING LEVELS IN THIS ROOM SHALL BE AT A MINIMUM
 OF 30FT CANDLES.
  
 14) NOTE: PLEASE ALSO INCLUDE THE LIGHTING LEVELS FOR
 ELEVATOR PITS TO MEET THE MINIMUM OF 5 FT CANDLES.
 PLEASE SEE NEC 620.23 WHICH CONTAINS REFERENCE TO
 MINIMUM REQUIREMENTS. SEE HANDBOOK COMMENTARY; ASME
 A17.1-2004, SAFETY CODE FOR ELEVATORS AND ESCALATORS,
 REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) AT THE PIT
 FLOOR AND REQUIRES LUMINAIRES TO BE EXTERNALLY GUARDED
 TO PREVENT ACCIDENTAL BREAKAGE.
 THE POWER PLANS AS WELL AS THE LIGHTING PLANS CONTAIN A
 *J* WHICH IS NOTED AS A JUNCTION BOX ON THE SYMBOL
 LEGEND. AT THIS TIME NO REQUIRED LIGHTING IS SHOWN.
  
 15) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS IN
 COMPLIANCE WITH ALL SECTIONS OF FLORIDA BUILDING CODE
 CHAPTER 13.
 PLEASE BE SURE TO SEE AREAS SUCH AS
 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING
 PERFORMANCE LEVELS. PLEASE BE SURE TO SEE SECTION NOTES
 FOR ITEMS SUCH AS TRACK LIGHTING, HID LIGHTING ETC
 WHICH ARE NOT ALWAYS BASED ON BULB WATTAGE.
 THE COORDINATION OF ALL ITEMS ON THE INPUT DATA REPORT
 FOR *ALL* BUILDING COMPONENTS IS MOST IMPORTANT. THE
 LACK OF COORDINATION OF THE IDR WITH THE PLANS IS ONE
 OF THE KEY ITEMS IN THE DELAY OF ISSUANCE OF MANY
 BUILDING PERMITS. AS THIS PROJECT WAS ONLY SUBMITTED
 UNDER PLAN REVIEW THE NEW REQUIREMENTS OF THE FLORIDA
 BUILDING CODE BEING ADOPTED IN MARCH OF 2009 WILL
 GREATLY INCREASE THE STRINGENCY OF THIS CHAPTER OF THE
 FBC.
 AS NO ENERGY CALCULATIONS WERE SUBMITTED FOR REVIEW IT
 IS NOT POSSIBLE TO COMMENT ON CALCULATIONS AT THIS
 TIME.
 ** ONCE AGAIN WHEN SUBMITTING THE CALCULATIONS ALONG
 WITH THE IDR, PLEASE BE SURE ALL ITEMS ON PLANS
 COORDINATE WITH THE SUBMITTED CALCULATIONS.
  
 16) NOTE: PLEASE SUBMIT LIGHTING PLANS IN COMPLIANCE
 WITH THE MINIMUM REQUIREMENTS OF FBC CHAPTER 13 FOR
 LIGHTING CONTROLS. PLEASE SEE 13-415.1.ABC.1 WHICH
 REQUIRES *ALL* LIGHTING IN ANY BUILDING GREATER THAN 5K
 SQ FT TO BE AUTOMATICALLY SHUT OFF WHEN ANY AREA OR
 BUILDING IS NOT OCCUPIED. THERE ARE SOME EXCEPTIONS TO
 THIS REQUIREMENT HOWEVER MANY AREAS OF THIS BUILDING IS
 NOT CONSIDERED 24HR OPERATION OR MEET THE DEFINITIONS
 OF PATIENT CARE. THERE WOULD BE SOME AREAS/ROOMS IN
 WHICH MAY BE CONSIDERED A HAZARD TO THE OCCUPANTS IF
 THE LIGHTING WAS AUTOMATICALLY SHUT OFF SUCH AS THE
 ELECTRICAL ROOMS. (SEE NEC 110.26 SECTION FOR
 ILLUMINATION)
 THERE ARE MANY LOCATIONS ON PLANS WHICH ONLY INDICATE A
 STANDARD SINGLE POLE SWITCH FOR THE LIGHTING CONTROLS
 WHICH IS NOT PERMITTED. SOME OF THE FOLLOWING LOCATIONS
 ARE NOTED FOR EXAMPLE LOCATIONS OF THIS AND IS NOT ALL
 LOCATIONS ON PLANS WHICH ARE NOT CODE COMPLIANT.
 SEE ROOMS:
 120,121,124,125,123,135,134,133,130,131,107,106,105 ETC
 THESE ARE ONLY SOME ROOMS WHICH ARE NOTED FOR EXAMPLE.
 THERE ARE MANY OTHERS.
  
 A) PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 FOR
 ALL AREAS WHICH REQUIRE LIGHTING CONTROLS. THE PLANS
 CONTAIN A NOTE WHICH MENTIONS THE ENTIRE BUILDING IS
 UNDER ENERGY MANAGEMENT HOWEVER BASED ON THE ITEMS
 LISTED ABOVE, **ALL ** SEPARATE SPACES WHICH CONTAIN
 FLOOR TO CEILING HEIGHT PARTITIONS SUCH AS ROOMS AND
 AREAS REQUIRES AN OVER RIDE OF SUCH A SYSTEM OR MEET
 THE REQUIREMENTS FOR INDIVIDUAL SPACES.
 PLEASE ALSO SEE THE CONTROLS IN THE 13-415.1.ABC.1 (1)
 FOR ANY MORE THAN ONE LEVEL WHICH REQUIRES SEPARATE
 CONTROLS.
 PLEASE SEE FBC 1006.1.2 AND NFPA-10 17.8.1.2.2 FOR ANY
 DEVICES CONTROLLING EGRESS LIGHTING AS THESE SHALL BE
 *FAIL-SAFE ON* DEVICES.
 PLEASE SEE AREAS SUCH AS MULTI-GANG BATHROOMS WHICH
 WILL REQUIRE DUAL TECHNOLOGY DEVICES. IN THESE AREAS
 AND OTHER POSSIBLE AREAS IT WILL NOT BE PERMISSIBLE TO
 USE ONLY MOTION SENSOR TYPE DEVICES.
  
 B) PLEASE BE SURE TO SEE 13-415.1.ABC.1.4 FOR EXTERIOR
 LIGHTING CONTROLS REQUIRED. THERE ARE ONE OF TWO
 METHODS PERMITTED FOR CONTROLS. (BOTH MAY BE USED).
 IF USING AN ASTRONOMICAL TIME CLOCK PLEASE BE SURE TO
 LIST THE MINIMUM REQUIRED PROGRAMMING BATTERY BACK UP
 TIME. THE CODE REQUIRES 10HRS MINIMUM.
  
 C) PLEASE BE SURE TO SEE SECTION 13-415.1.ABC.1.3 AS
 NOTED ABOVE TO HOTEL AND MOTEL GUEST ROOMS. THESE SHALL
 CONTAIN CONTROLS TO TURN OFF ALL LIGHTING IN THE
 GUESTROOMS/SUITES WHEN THEY ARE NOT OCCUPIED. THIS
 INCLUDES ALL OUTLETS INCLUDING SWITCHED RECEPTACLES
 WHICH MAY CONTAIN LIGHTING FIXTURES WHICH MAY BE OF THE
 PLUG-IN TYPE. THE USE OF STANDARD SINGLE POLE OR 3-POLE
 SWITCHES IS NOT PERMITTED. THESE DO NOT MEET ANY
 AUTOMATED CONTROLS.
  
 D) PLEASE SEE THERE IS LIGHTING ON PLANS WHICH DO NOT
 SHOW ANY LIGHTING CONTROLS AT ALL INCLUDING NO
 CIRCUITING ETC.
  
 E) PLEASE BE SURE TO SEE SOME ROOMS SUCH AS CONFERENCE
 ROOMS, EMPLOYEE BREAK ROOMS ETC AS LISTED IN
 13-415.1.ABC.1.2 REQUIRE OCCUPANCY SENSORS WHETHER OR
 NOT PART OF ANY BUILDING AUTOMATION SYSTEM.
  
 F) PLEASE SEE NOTE #31 ON SHEET E24 WHICH CONFLICTS
 WITH THE LIGHTING CONTROLS ON PLANS AND INFORMATION
 SHOWN/SUBMITTED.
  
 THE INTENT OF THE ENERGY CODE AND THE MINIMUM FEDERALLY
 ADOPTED REQUIREMENTS IS THAT LIGHTING IS TURNED OFF TO
 CONSERVE ENERGY WHEN THE ROOM(S) AND AREAS ARE NOT
 OCCUPIED. IN JULY OF 2004 THE FEDERAL MANDATES ADOPTED
 1999 ASHRAE 90.1. ALL STATES IN THE US WERE REQUIRED TO
 ADOPTED THIS MINIMUM STANDARD OR EQUIVALENT BY THEIR
 NEXT CODE CYCLE. THE FEDERAL MANDATES HAVE HAD
 ADJUSTMENTS SINCE THAT DATE. THE STATE OF FLORIDA
 ADOPTED THE FLORIDA ENERGY EFFICIENCY CODE (CHAPTER 13)
 IN THE 2001 FBC CODE CYCLE AND WAS SUBSTANTIALLY
 CHANGED IN THE ADOPTION OF THE 2004 FBC OCT 1ST, 2005.
 THERE HAVE BEEN SEVERAL REVISIONS TO THE 2004 FBC WHICH
 HAVE AFFECT CHAPTER 13 AND MORE SPECIFICALLY LIGHTING
 CONTROLS.
 ** THIS NOTE GIVES SECTIONS FOR LIGHTING CONTROLS WHICH
 ARE REQUIRED TO MEET A *MINIMUM*. THERE ARE MANY
 SYSTEMS ON THE MARKET WHICH MEET THE MINIMUM AND MANY
 WHICH MEET THE MINIMUM AND ABOVE. THIS OFFICE/REVIEWER
 ONLY REQUIRES THE MINIMUM MEETING THE FLORIDA BUILDING
 CODE. ANY SYSTEMS CHOSEN BY THE DESIGN TEAM WHICH GO
 ABOVE THE MINIMUM REQUIREMENTS OF THE CODE WILL NOT BE
 REJECTED AS THEY MOST CERTAINLY MEET THE MINIMUM.
  
 IF ANY OF THESE ITEMS NEED TO BE GONE OVER IT IS BEING
 NOTED TO CALL AND GO OVER ANY QUESTIONS OR COMMENTS.
 AS THERE ARE MANY ASPECTS OF THE PLANS WHICH DO NOT
 SHOW THE MINIMUM AT THIS TIME THERE MAY BE NEW COMMENTS
 ON THE FOLLOWING REVIEW ONCE INFORMATION IS SUBMITTED
 OR SHOWN.
 PLEASE BE SURE CHECK LISTING PER 110.3 OF ANY PROPOSED
 SYSTEMS AND PLEASE SUBMIT COMPLETE SYSTEMS PROPOSAL FOR
 ANY BUILDING MANAGEMENT SYSTEM.
  
 17) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING ITEMS.
 THE GENERATOR.
 FIRE PUMP.
 FIRE PUMP CONTROLLER.
 ATS (AUTOMATIC TRANSFER SWITCH).
 FUEL TANK. THE FUEL TANK WILL BE REVIEWED BY OTHERS)
  
 MINIMUM EQUIPMENT MEETING THE CODE AT THIS TIME MUST BE
 VERIFIED. EVEN IF THE EQUIPMENT IS NOT FINALIZED
 EQUIPMENT WILL NEED TO BE CHOSEN AT THIS TIME. THE
 MANUFACTURE OR BRAND OF EQUIPMENT MAY ALWAYS BE CHANGED
 AT A LATE DATE.
 90.7,110.3, NFPA_20, NFPA-101, NFPA-70, NFPA-110.
 FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 18) NOTE: PLEASE PROVIDE ALL SHUT DOWN OF ALL EQUIPMENT
 IN IT ROOM INCLUDING A/C UNIT. THE PLANS DO NOT SHOW
 ANY EPO (EMERGENCY POWER OFF) BUTTON AS REQUIRED PER
 645.10. THE PANEL SCHEDULE FEEDING THE IT PANEL AND THE
 IT PANEL SCHEDULE ALSO DOES NOT LIST ANY SHUNT TRIP
 BREAKERS. PLEASE SEE 645.10 FOR DISCONNECTING
 REQUIREMENTS.
 PLEASE SEE NEC 645.4 REQUIREMENTS OF AN IT ROOM. WHEN
 ANY PROPOSED ROOM DOES MEETS ALL ITEMS LISTED PER 645.4
 THE WIRING METHODS WHICH ARE LESS STRINGENT IN THIS
 CODE SECTION MAY NOT BE USED.
 PLEASE MEET ALL OF 645.4 OR PLEASE CHANGE DESIGNATION
 AND PROVIDE NOTE FOR WIRING METHODS OF CHAPTERS 1-4
 MUST BE USED. IT MAY BE HELPFUL TO CONTACT IT PERSONNEL
 FOR MARRIOTT TO CONFIRM WIRING METHODS TO BE USED.
 THE FOLLOWING IS EXTRACTED FROM THE NEC FOR EASE OF
 CODE SECTIONS:
  
  
 THIS ARTICLE SHALL APPLY, PROVIDED ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) DISCONNECTING MEANS COMPLYING WITH 645.10 ARE
 PROVIDED.
 (2) A SEPARATE HEATING/VENTILATING/AIR-CONDITIONING
 (HVAC) SYSTEM IS PROVIDED THAT IS DEDICATED FOR
 INFORMATION TECHNOLOGY EQUIPMENT USE AND IS SEPARATED
 FROM OTHER AREAS OF OCCUPANCY. ANY HVAC SYSTEM THAT
 SERVES OTHER OCCUPANCIES SHALL BE PERMITTED TO ALSO
 SERVE THE INFORMATION TECHNOLOGY EQUIPMENT ROOM IF
 FIRE/SMOKE DAMPERS ARE PROVIDED AT THE POINT OF
 PENETRATION OF THE ROOM BOUNDARY. SUCH DAMPERS SHALL
 OPERATE ON ACTIVATION OF SMOKE DETECTORS AND ALSO BY
 OPERATION OF THE DISCONNECTING MEANS REQUIRED BY
 645.10.
 FPN: FOR FURTHER INFORMATION, SEE NFPA 75-2003,
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT, CHAPTER 10, 10.1, 10.1.1, 10.1.2, AND
 10.1.3.
 (3) LISTED INFORMATION TECHNOLOGY EQUIPMENT IS
 INSTALLED.
 (4) THE ROOM IS OCCUPIED ONLY BY THOSE PERSONNEL NEEDED
 FOR THE MAINTENANCE AND FUNCTIONAL OPERATION OF THE
 INSTALLED INFORMATION TECHNOLOGY EQUIPMENT.
 (5) THE ROOM IS SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTANT-RATED WALLS, FLOORS, AND CEILINGS WITH
 PROTECTED OPENINGS.
 FPN: FOR FURTHER INFORMATION ON ROOM CONSTRUCTION
 REQUIREMENTS, SEE NFPA 75-2003, STANDARD FOR THE
 PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT, CHAPTER
 5.
  
 ALL ITEMS ABOVE WITH THE EXCEPTION OF # 1 ABOVE ARE
 SHOWN ON PLANS.
  
 19) NOTE: PLEASE SEE 110.26 AS THE MAIN ELECTRICAL ROOM
 WHICH REQUIRES THE DOORS TO SWING OUTWARD. THE DOORS
 SHALL ALSO BE EQUIPMENT WITH PANIC HARDWARE, PRESSURE
 PLATES OR OTHER TYPES OF LOCKING MECHANISMS WHICH DOES
 NOT IMPEDED THE EGRESS OF ANY PERSONNEL IN THE ROOM IN
 THE EVENT OF AN EMERGENCY. AN OCCUPANT WHICH HAS HAD A
 FLASH, BURN OR OTHER INJURY NEEDS TO EXIT THE ROOM
 WITHOUT HAVING USE HANDS, EYES ETC TO EXIT. THERE ARE
 MANY DOCUMENTED CASES IN WHICH THIS IS SUCH A HAZARD.
  
 20) NOTE: PLEASE PLACE NOTES ON PLANS FOR SIGNAGE
 REQUIRED FOR ARC FLASH OF ALL EQUIPMENT MEETING 110.16
  
 21) NOTE: PLEASE SEE 210.8B2 AS ALL 15 AND 20 AMP 120V
 RECEPTACLES IN KITCHEN AND BUFFET AREA WILL BE REQUIRED
 TO BE GFI OR GFI PROTECTED. THIS DOE NOT MATTER IF
 THESE RECEPTACLES ARE SERVING COUNTER SPACES.
  
 22) NOTE: PLEASE SEE 210.63, 210.8B3,4,AND 5. THERE ARE
 LOCATIONS ON PLANS IN WHICH REMOTE AIR CONDITIONING OR
 REFRIGERATION EQUIPMENT IS NOTED HOWEVER NO RECEPTACLE
 FOR SERVICING COULD BE LOCATED ON PLANS.
 PLEASE BE SURE ALL LOCATIONS OF OUTSIDE OR ROOF TOP
 EQUIPMENT CONTAIN THESE DEVICES FOR SERVICING AS WELL
 AS PROTECTION.
  
 23) NOTE: PLEASE SEE FBC 3006.2 FOR REQUIRED
 CONDITIONING/VENTILATION OF ELEVATOR EQUIPMENT ROOMS.
 THE ELECTRICAL PLANS DO SHOW ELECTRICAL FOR ELEVATOR
 EQUIPMENT HOWEVER ANY EQUIPMENT ON MECHANICAL PLANS
 WHICH ARE BEING INSTALLED TO MEET THIS CODE SECTION
 NEEDS OT BE SHOWN ON ELECTRICAL PLANS.
  
 24) NOTE: PLEASE SEE 620.23 AS NOTED ABOVE FOR ELEVATOR
 PIT AREAS FOR LIGHTING LEVELS. THIS SAME SECTION
 REQUIRES THE LIGHTING AS WELL AS RECEPTACLES IN THESE
 EQUIPMENT ROOMS TO BE ON DEDICATED CIRCUITS. BASED ON
 SHEET E11 WHICH SHOWS THE LIGHTING IN THE ELEVATOR
 EQUIPMENT ROOM CIRCUITED TO LIGHTING OF OTHER AREAS
 THIS DOES NOT MEET THE CODE SECTION GIVEN.
  
 25) NOTE: THE POWER PLANS ARE INCOMPLETE AS THERE NO
 ELECTRICAL EQUIPMENT OR POWER SHOWN FOR THE POOL
 EQUIPMENT ROOM.
 680,310,240 ETC
 FBC106.1.1, 106.1.2 FOR CLARITY, COORDINATION, AND
 ADDITIONAL INFORMATION NEEDED ON RECORD PLANS.
  
 26) NOTE: PLEASE OBTAIN PHOTO-METRIC LEVELS FOR
 SWIMMING POOL AREA FOR ANY NIGHT TIME SWIMMING PER PALM
 BEACH COUNTY HEALTH DEPARTMENT. ALL PHOTO-METRICS FOR
 ANY SWIMMING AFTER DUSK OR BEFORE DAWN SHALL BE STAMPED
 BY THE HEALTH DEPARTMENT.
 THIS IS NOT A CITY OF WEST PALM BEACH ADOPTED LEVEL OF
 LIGHTING HOWEVER UNLESS PLANS ARE STAMPED PERMIT MAY
 NOT BE ISSUED. PLEASE ALSO KEEP IN MIND IF THERE IS NOT
 GOING TO BE ANY SWIMMING OUTSIDE OF THE DAYLIGHTS HOURS
 PER THE HEALTH DEPARTMENT PLEASE PLACE NOTES ON PLANS
 ACCORDINGLY.
  
 27) NOTE: ANY PROPOSED LIGHTNING PROTECTION SYSTEM IS
 GOING TO BE REQUIRED TO BE UNDER SEPARATE PERMIT.
 HOWEVER PLEASE PLACE NOTES ON PLANS THAT ANY PROPOSED
 LIGHTNING PROTECTION SYSTEM SHALL MEET NFPA-780. (OR
 WORDS TO THAT AFFECT).
 THERE ARE MANY SYSTEMS ON THE MARKET WHICH DO NOT MEET
 ANY ACCEPTABLE STANDARD AND ARE NOT LISTED TO MEET
 NFPA-780.
  
 28) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS
 PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE
 SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE
 LIFE SAFETY PLANS.
 * TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633, FLORIDA STATUTES*
  
 29) NOTE: PLEASE SEE FA PLANS. THERE ARE CODE REFERENCE
 TO ADA REQUIREMENTS WHICH ARE NOT PART OF THE CURRENT
 ADOPTED CHAPTER 11 OF THE FBC. PLEASE SEE FBC
 11-4.28.1, .2 AND .3 FOR REFERENCES AND PLEASE BE SURE
 TO REFLECT THESE CODES.
 PLEASE ALSO SEE THERE ARE SEVERAL REFERENCES TO THE
 2002 NATIONAL ELECTRICAL CODE ON FA SHEETS. PROJECT IS
 CURRENTLY SUBMITTED FOR REVIEW UNDER THE 2005 NFPA-70/
 NEC.
 PLEASE ADJUST NOTES AND REFERENCES ON PLANS.
 PLEASE BE SURE ALL HEIGHTS, LOCATIONS AND LEVELS ARE
 PER SECTIONS NOTED ABOVE.
  
 30) NOTE: PLEASE COORDINATE THE FLOOR PLANS FOR THE
 FIRE PUMP ROOM. PLEASE SEE SHEET FP -10 WHICH CONTAINS
 A DIFFERENT ROOM LAYOUT INCLUDING DOORS WHICH ARE NOT
 THE SAME AS THE REST OF THE PLANS SUBMITTED.
 THERE ARE MANY ASPECTS OF NFPA-20 FOR FIRE PUMP ROOMS
 WHICH ARE REVIEWED INCLUDING FLOOR DRAINAGE REQUIRED.
 COORDINATION OF ALL OF THESE ITEMS IS IMPERATIVE.
 NEC 695, NFPA-20
  
 31) NOTE: PLEASE PROVIDE INFORMATION ON FUEL
 CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP
 AND ALL EMERGENCY SYSTEMS PER 700 AND 701.
 PLEASE BE SURE TO INCLUDE 5% FOR SUMP AND 5% FOR
 EXPANSION.
 PLEASE SEE NFPA-110, NFPA-20 9.6.2.2
  
 32) NOTE: THE FIRE PUMP SERVICE ENTRANCE CONDUCTORS ARE
 ALONG WITH OTHER ELECTRICAL SERVICE ENTRANCE CONDUCTORS
 ARE NOT PERMITTED TO HAVE MORE THAN 8FT OF UNPROTECTED
 CONDUCTORS INSIDE THE BUILDING. 230.70,230.71 PLEASE
 SEE NEC FOR CONDUCTORS TO BE CONSIDERED OUTSIDE THE
 BUILDING BY DEFINITION (SEE SAME SECTION 695.6
 INCLUDING 230.6) FOR THESE REQUIREMENTS.
 THE RISER SHOWS SE CONDUCTORS TO GUTTERS AND THEN TO
 THE MAIN SERVICE EQUIPMENT. MOST CERTAINLY THIS WOULD
 BE MORE THAN 8 FT OF TOTAL LENGTH OF UNPROTECTED
 CONDUCTORS. AS THE NEC DOES NOT PROVIDE THE 8 FT LENGTH
 MANY JURISDICTIONS USED TO CONTAIN LOCAL TECHNICAL
 AMENDMENTS ALLOWING UP TO 8 FT AND SOME NOT ALLOWING
 ANY INSIDE WITHOUT PROTECTION. AS THE TECHNICAL
 AMENDMENTS WENT AWAY IN THE 2001 CODE CYCLE THIS AHJ
 DOES STILL ALLOW UP TO 8 FT HOWEVER NOT ANY GREATER.
 THE NEC IS NO SPECIFIC AND A AHJ COULD PERMIT LESS.
 PLEASE ADJUST RISER WITH THE CONDUCTORS AS SHOWN.
  
 33) NOTE: THE RISER IS SHOWING *EQUIPMENT GROUNDING
 CONDUCTORS* BEFORE THE FIRST MEANS OF SERVICE
 DISCONNECT FOR ALL PROPOSED SERVICES INCLUDING THE FIRE
 PUMP WHICH IS NOT PERMITTED. AS THE CODE REQUIRES THE
 NEUTRAL (GROUNDED) CONDUCTOR TO BE BONDED AT THE FIRST
 MEANS OF DISCONNECT IF AN EQUIPMENT GROUND IS INSTALLED
 THIS WOULD PARALLEL THE NEUTRAL. THIS WOULD CREATE
 OBJECTIONABLE CURRENTS PER 250.6 AND IS NOT PERMITTED.
 PLEASE REMOVE AND ADJUST RISER.
 250.6,250.24 ETC.
  
 34) NOTE: EMERGENCY EQUIPMENT MAINS AND FIRE PUMP MAINS
 NEED TO BE LABELED AS SUCH. FOR EXAMPLE: THE FIRE PUMP
 AS SHOWN IS A SEPARATE SERVICE FROM FPL AS REQUIRED.
 THE RISER NOTES THIS IS MAIN FOUR OF FIVE HOWEVER THIS
 IS THE FIRE PUMP MAIN.
 A SECOND EXAMPLE IS THE EMERGENCY MAIN AS SHOWN ON
 RISER. THIS IS NOTED AS MAIN 3 OF 3 YET THIS IS
 ACTUALLY THE EMERGENCY MAIN ONE OF ONE.
 EACH MAIN IN EACH PERMITTED SERVICE NEEDS TO BE
 LABELED.
 230.2, 701.9,700.8 AS NOTED ABOVE.
 PLEASE ADJUST LABELING.
  
 35) NOTE: RISER NOTES THE FIRE PUMP CONTROLLER AS
 SERVICE ENTRANCE RATE HOWEVER NO INDICATE OF THIS UNIT
 CONTAINING THE BUILT IN TRANSFER SWITCH IS NOTED.
 PLEASE SEE NOTES ABOVE AND EXPANDED ON THE FIRE PUMP
 CONTROLLER INFORMATION.
 695.4
 PLEASE BE SURE TO SEE NOTES ON TRANSFER SWITCHES.
  
 36) NOTE: PLEASE SEE 230.95,240.13 ETC. THE CODE
 REQUIRES GROUND FAULT PROTECTION FOR ANY SYSTEMS 150V
 OR MORE TO GROUND AND 100AMPS OR OVER. THE RISER
 INDICATES GFI PROTECTION WHICH IS CLASS A PROTECTION
 FOR PERSONNEL. THIS IS NOT THE SAME KING OF PROTECTION
 WHICH IS GFP WHICH IS WHAT IS REQUIRED IN THE SECTIONS
 GIVEN. PLEASE PROVIDE INFORMATION ON THE TRANSFER
 SWITCHES AND PLEASE SEE THE FOLLOWING COMMENT WHICH MAY
 AFFECT THE USE OF 3-POLE OR 4-POLE TRANSFER SWITCHES.
  
 37) NOTE: PLEASE SEE NEC
 ,250.20,250.30,250.66,240.13.230.95, 700.7D AND 700.26.
 GFP PROTECTION IS REQUIRED ON THE NORMAL SIDE OF THE
 SERVICE HOWEVER ONLY GROUND FAULT SENSING IS REQUIRED
 TO BE ON THE SECONDARY SIDE. THE CODE ACTUALLY DOES NOT
 REQUIRE NOR DOES IT RECOMMEND GFP ON THE EMERGENCY
 EQUIPMENT.
 PLEASE SEVERAL WHITE PAPERS WHICH HAVE NOTES ON THE
 ABOVE SITUATION WHEN GROUND FAULT PROTECTION IS
 TRIGGERED BY THE CODE. MANY OF THESE IN FACT NOTE A
 COORDINATION LOSS OF EQUIPMENT WHEN THE USE OF 3-POLE
 ATS SWITCHES IS USED.
 PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL
 CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING
 CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND
 THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM *ASCO*
 WHITE PAPERS:
  
 WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE CODE
 AND AN ALTERNATE POWER SUPPLY IS INCLUDED, SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT SHOWN ABOVE
 ILLUSTRATES SUCH A CIRCUMSTANCE. THE SERVICE IS LARGER
 THAN 1,000 AMPS. CONSEQUENTLY, GROUND FAULT PROTECTION
 IS REQUIRED AT THE MAIN SERVICE DISCONNECT AT A
 MINIMUM. IF IT IS INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID CONNECTION TO THE
 MAIN SERVICE NEUTRAL, A GROUND FAULT WHEN THE GENERATOR
 IS FEEDING THE LOAD WILL CAUSE THE MAIN SERVICE
 DISCONNECT TO OPEN. THIS WILL NOT DISCONNECT THE ARCING
 FAULT FROM THE GENERATOR. COORDINATION IS THUS LOST."
  
 THIS HAS BEEN READ AND NOTED BY OTHER MANUFACTURES.
 PLEASE OBTAIN AND VERIFY COORDINATION FROM THE PROPOSED
 MANUFACTURE AND ADJUST PLANS.
 AS THE PLANS DO NOT INDICATE THE USE OF 3 OR 4 POLE
 DEVICES AT THIS TIME FINAL COMMENT CAN NOT BE MADE.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL MAYBE BE
 REQUIRED TO BE REVISED.
  
 38) NOTE: PLEASE SEE 700.9 OF THE NEC ALONG WITH
 EXHIBITS IN 700.1 ETC.
 THE RISER INDICATES EMERGENCY/LIFE SAFETY SYSTEMS BEING
 WIRED IN WITH LEGALLY REQUIRED SYSTEMS WHICH ARE NOT
 PERMITTED. PLEASE ADJUST RISER. PLEASE ALSO KNOW THERE
 MAY BE NEW COMMENTS AS SEVERAL ITEMS WILL NEED TO BE
 PROVIDED.
 *** IMPORTANT**
 PLEASE SEE NEC 700 AND 701 DEFINITIONS AND OTHER
 ADOPTED CODES AS NOT ALL SYSTEMS, FEEDERS, BRANCH
 CIRCUITS ETC AS SHOWN ON RISER AND PANEL SCHEDULES ARE
 LIFE SAFETY/EMERGENCY SYSTEMS AS SOME ARE CONSIDERED
 LEGALLY REQUIRED. THIS WOULD REQUIRE SEPARATION.
 THIS CAN BE GONE OVER.
 AN EXAMPLE IS THE ELEVATOR IS THIS OCCUPANCY IS
 CONSIDERED LEGALLY REQUIRE AND NOT LIFE SAFETY. THIS IS
 A BACK UP REQUIRED TO COME ON IN 60SECONDS INSTEAD OF
 THE REQUIRED 10 SECONDS LISTED IN 700 SYSTEMS.
 AN ELEVATOR IN A HOSPITAL WOULD BE DIFFERENT AND WOULD
 BE CONSIDERED LIFE SAFETY.
 THIS COMMENT WILL ALL TIE INTO THE COMMENTS ABOVE WITH
 RESPECT TO THE LIGHTING AND BACK UP OF THE EGRESS
 LIGHTS. IF ALL MEET THE BATTERY BACK UP THEN THIS WOULD
 ONLY BE ONE LEGALLY REQUIRED (701) SYSTEM. THIS WOULD
 CHANGE MANY ASPECTS OF THE DESIGN INCLUDING NEXT
 COMMENT.
 PLEASE BE AWARE OF ANY PHONE SYSTEMS BEING PROPOSED
 WHICH WOULD BE REQUIRED TO CONTAIN UPS FOR BACK AS
 EMERGENCY COMMUNICATIONS IS REQUIRED TO CONTAIN BACK UP
 WHICH MAY THEN BE PART OF THE GENERATOR WHICH IS 10, 60
 SECOND BACK UP. NO DELAY IN PHONE SYSTEM IS PERMITTED.
  
 39) NOTE: PLEASE SUBMIT A COMPLETE COORDINATION STUDY
 FOR ALL LIFE SAFETY/EMERGENCY SERVICE EQUIPMENT AND
 BREAKERS. PLEASE SEE 240.12, 700.27 AND 701.18. THIS
 REQUIRES ALL BREAKERS AND EQUIPMENT TO BE COORDINATE.
  
 40) NOTE: PLEASE PROVIDE NOTE FOR SUPPORT OF VERTICAL
 CONDUCTORS PER 300.19.
  
 41) NOTE: PLEASE INDICATE AIC RATING FOR ALL SERVICE
 EQUIPMENT INCLUDING RATINGS OF ALL PANELS. 110.9. COULD
 NOT LOCATE ALL REQUIRED.
  
 42) NOTE: EVEN AS THE SWIMMING POOL IS UNDER A SEPARATE
 PERMIT PLEASE SEE 2005 NEC WHICH REQUIRES AN EQUAL
 POTENTIAL BOND.
 PLEASE PROVIDE DETAIL ON PLANS AS THIS MAY BE PART OF
 THE STRUCTURAL ELEMENTS OF THE PROPOSED STRUCTURE AND
 POOL AREA.
  
 43) NOTE: PLEASE PROVIDE THROUGH WALL AND FLOORS
 PENETRATION DETAILS PER 300.21. THE SPREAD OF FIRE IS
 REQUIRED TO BE CONTAINED PER SEVERAL ADOPTED REFERENCES
 AND STANDARDS.
 PLEASE SEE THE HANDBOOK COMMENTARY WHICH PROVIDES THE
 REFERENCES SUCH AS NFPA-221,251, ASTM AND ANSI
 REQUIREMENTS.
  
 44) NOTE: PLEASE COORDINATE ALL ITEMS ON RISER AND
 PANEL SCHEDULES. PLEASE SUBMIT COMPLETE PLANS FOR FULL
 REVIEW. THERE ARE SEVERAL ASPECTS OF RISER AND PANELS
 WHICH ARE NOT COMPLETED. AN EXAMPLE LIST WILL BE GIVEN
 OF SOME OF THESE ITEMS. THIS IS NOT A COMPLETE LIST. AS
 THERE ARE MANY ITEMS NOT YET COMPLETE OR SUBMITTED
 THESE CAN SIMPLY NOT BE REVIEWED.
  
 A) EXAMPLE:
  
 B) EXAMPLE: RISER INDICATES MDPLEM AS A MCB( MAIN
 CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS
 THIS AS MLO (MAIN LUG ONLY).
  
 C) EXAMPLE: RISER INDICATES MDPHEM AS A MCB( MAIN
 CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS
 THIS AS MLO (MAIN LUG ONLY).
  
 D) EXAMPLE: RISER INDICATES MDPL AS A MCB ( MAIN
 CIRCUIT BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS
 THIS AS MLO (MAIN LUG ONLY).
  
 E) EXAMPLE: RISER INDICATES MDPH AS A MCB( MAIN CIRCUIT
 BREAKER) PANEL YET THE PANEL SCHEDULE SHOWS THIS AS MLO
 (MAIN LUG ONLY).
  
 45) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE KEEP IN MIND THIS NEEDS TO SHOW THE ENTIRE FEED
 THRU FROM THE SOURCE TO THE END USE. THE CODE REQUIRES
 A MAXIMUM ON THE ENTIRE RUN NOT FROM A PANEL TO THE END
 DEVICE ON A CIRCUIT. THIS MAY GREATLY AFFECT FEEDERS OR
 BRANCH CIRCUIT CONDUCTORS.
 PLEASE SEE 13-413.1ABC.1.
  
 46) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER
 13-413.ABC.2, .2.1 AND .2.2. THE WORDING AS STATED IN
 THE FBC IS ACCEPTABLE. THIS WAS CONFIRMED WITH FLORIDA
 BUILDING COMMISSION/DCA.
  
 47) NOTE: PLEASE INCLUDE EFFICIENCY RATINGS OF MOTORS
 WHICH SHALL MEET 13-414.1.ABC.1.1.
  
 48) NOTE: PLEASE INCLUDE LOAD CALCULATIONS FOR ALL
 PANELS AND SERVICES. SOME INFORMATION IS SHOWN ON PLANS
 HOWEVER MOST IS NOT COMPLETE AT THIS TIME.
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%.
 230.42,215.5.
 220.
 P
 PLEASE SEE SECTIONS SUCH AS 220.12,220.14,220.42,
 220.44 AND OTHERS SUCH AS 220.43 FOR TRACK LIGHTING.
 THERE ARE SEVERAL ASPECTS OF THE LOAD CALCULATIONS AND
 HOW LOADS WERE DERIVED WHICH NEED TO BE SHOWN
 FBC 106.1.1, 106.1.2, 106.3.5.1.2 FOR ADDITIONAL
 INFORMATION, CLARITY AND COORDINATION.
  
 49) NOTE: PLEASE COMPLETE ALL PANELS WITH THE CONDUCTOR
 SIZES PER 310.16, 240.4 ETC
 MANY ARE NOTED AND SHOWN HOWEVER DUE TO SOME PANELS NOT
 BEING COMPLETE AT THIS TIME THIS NOTE REMAINS.
  
 50) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM
 COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT*
 ETC IS NOT ACCEPTABLE. THIS INCLUDES ALL SUITES/ROOMS.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 51) NOTE: THE RISER LENDS TO EACH PANEL FOR UNITS AS
 FEED THROUGH HOWEVER THE PANEL SCHEDULES DO NOT
 INDICATE ANY FEED THRU NOTES, LUGS ETC.
 240, 215 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 52) NOTE: PLEASE SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION FOR UNIT OUTLETS. THIS INCLUDES PROTECTIONS
 OF ALL OUTLETS INCLUDING LIGHTS, FANS AND RECEPTACLES.
 ** PLEASE BE AWARE OF ANY LIGHTING CONTROL SYSTEMS FOR
 DESIGN WHICH MAY BE AFFECTED BY THE REQUIREMENT OF AFCI
 PROTECTION.
  
 53) NOTE: PLEASE SEE 210.60 OF THE NEC. WHEN A GUEST
 ROOM/SUITE FALLS UNDER THE DEFINITION WITH PERMANENT
 MEANS OF COOKING ALL THE REQUIREMENTS OF 210.52 MUST BE
 MET.
 THIS INCLUDES MANY OF FOLLOWING WHICH WILL GREATLY
 AFFECT THE PLANS, WIRING, THE LOADS, THE PANEL
 SCHEDULES ETC AS SUBMITTED. THE PLANS AT THIS DO NOT
 MEET THE CODE WITH RESPECT TO MANY ITEMS. PLEASE SEE
 THE FOLLOWING EXAMPLES:
  
 A) PLEASE SEE 210.52C1-5 FOR RECEPTACLES ALONG KITCHEN
 COUNTER SPACES WHICH SHALL MEET SPACING.
 THIS INCLUDES PENINSULAR AREAS.
 THIS ALSO INCLUDES OTHER SPACING AS THERE ARE UNITS
 SUCH AS UNIT *B* WHICH SHOWS MORE THAN FOUR FT BETWEEN
 COUNTER TOP RECEPTACLES WHICH IS NOT PERMITTED.
 THERE ARE OTHER UNITS ALSO NOT JUST UNIT *B*. SEE UNIT
 *S* AS AN EXAMPLE WHICH SHOWS COUNTER SPACE OF 12
 INCHES OR MORE YET NO RECEPTACLE IS SHOWN.
 GFCI PROTECTION PER 210.8A6
  
 B) PLEASE SEE 210.52B1 FOR THE REQUIRED CIRCUITING
 WHICH REQUIRES MINIMUM OF TWO SMALL APPLIANCE CIRCUITS.
 EACH CIRCUIT IS REQUIRED TO BE FIGURED PER 220.53 WHICH
 REQUIRES 1500VA PER EACH.
 SEE ANY AREAS SUCH AS DINING, BREAKFAST AREAS OF THE
 LIKE WHICH WILL BE AFFECTED. THE PLANS DO NOT INDICATE
 THE DINING, BREAKFAST OR EATING AREA OF THE LIKE. THE
 PLANS DO SHOW THE RECEPTACLES IN THE AREAS WHICH WOULD
 BE CONSIDERED ONE OF THESE AS ON THE GENERAL LIGHTING
 AND RECEPTACLES CIRCUIT WHICH IS NOT PERMITTED. AN AREA
 NEEDS TO BE DESIGNATED AND RECEPTACLE WIRING NEEDS TO
 BE ADJUSTED.
  
 C) PLANS DO NOT SHOW ANY RECEPTACLE FOR DISHWASHER.
 PLEASE BE SURE TO SEE 210.4 FOR ANY DEVICES SUCH A
 SINGLE YOKE BEING FED FROM A TWO BREAKERS WHICH SHALL
 MEET DISCONNECTING REQUIREMENTS.
  
 D) NOTE: PLEASE SEE 210.52D, 210.11C3 AS THE BATHROOM
 WIRING SHALL NOT FEED ANY OTHER ROOMS, DEVICES, OUTLETS
 ETC. THIS NEEDS TO BE SPECIFIED AS THE DEDICATED
 BATHROOM CIRCUIT AS NOTED ABOVE PER 408.4.
  
 54) NOTE: PLEASE SEE FBC 1019.1.25 AS NO OTHER SYSTEMS
 ARE PERMITTED IN THE VERTICAL EGRESS STAIRS WITH THE
 EXCEPTION OF THOSE SYSTEMS REQUIRED TO BE PART OF THE
 STAIRS. SHEET E-16 INDICATES A SWITCH FOR A LIGHT
 FIXTURE ON THE ROOF TOP. THE SWITCH IN THIS LOCATION IS
 NOT PERMITTED.
 PLEASE ALSO PROVIDE LIGHTING PER EGRESS OF ROOF AREAS
 INCLUDING MEETING LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.4.
  
 55) NOTE: PLEASE BE SURE TO SHOW/IDENTIFY THE REQUIRED
 SMOKE ALARMS, DETECTORS, AND CARBON MONOXIDE DETECTORS
 ON UNIT ROOM LAYOUT FOR ELECTRICAL PLANS AS THE FIRE
 ALARM WILL BE UNDER SEPARATE PERMIT.
  
 56) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCE FOR
 ELECTRICAL PANELS. SOME SHOW FURNITURE IN FRONT OF
 PANELS. LOCATION NEEDS TO MEET 110.26.
 PLEASE ALSO PROVIDE A LAYOUT OF ALL ELECTRICAL, FIRE
 PUMP ROOMS ETC SO COMPLIANCE FOR MINIMUM CLEARANCES
 AREA REVIEWED.
 PLEASE SEE NOTES ABOVE WITH RESPECT TO PERMITTED
 SYSTEMS SUCH AS 700 AND 701 IN THE SAME LOCATIONS.
 NFPA-110 SECTION 7.2.2 AS EPSS EQUIPMENT SHALL NOT BE
 INSTALLED IN THE SAME ROOM WHERE THE NORMAL ELECTRICAL
 SERVICE EQUIPMENT IS INSTALLED. THE CODE; SECTION
 7.2.2.1 DOES PERMIT TRANSFER SWITCHES TO BE INSTALLED
 IN THE NORMAL ELECTRICAL SERVICE ROOM ONLY WHERE TWICE
 THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF NFPA 70,
 NATIONAL ELECTRICAL CODE, EXISTS BETWEEN EQUIPMENT
 ENCLOSURES.
 EMERGENCY EQUIPMENT ROOMS WITH THE 2HR RATING AS
 REQUIRED PER 7.2.1.1 PROVIDES THE SAFE LOCATION SO ANY
 FIRE IN THE MAIN SWITCH GEAR BY AN EXPLOSION ETC WOULD
 NOT DAMAGE THE LIFE SAFETY OR LEGALLY REQUIRED SYSTEMS.
 PLEASE SEE LOCATION WHERE THE GENERATOR IS RUNNING AT
 FULL SPEED CAN ALSO BE DISTRACTING FOR ANY EMERGENCY
 PERSONNEL WHEN ATTEMPTING TO SHUT DOWN ANY SPECIFIC
 SYSTEMS. MEETING THE SECTION ABOVE FOR SEPARATION AND
 CLEARANCE REQUIREMENTS NEEDS TO BE ADDRESSED.
 LOCATIONS OF ALL ELECTRICAL EQUIPMENT NEED TO BE
 VERIFIED.
  
 PLEASE COMPLETE PLANS WITH ALL FURNITURE AS PROPOSED.
  
 57) NOTE: PLEASE SEE 210.8B3,4 AND 5 OF THE 2005 NEC
 WHICH REQUIRES ALL RECEPTACLES OUTSIDE EVEN IF FOR
 DEDICATE EQUIPMENT SUCH AS DRINKING FOUNTAINS TO BE
 GFI/ GFI PROTECTED. PLEASE SEE FOUNTAIN ON ROOF TOP
 PLANS WHICH NEEDS TO MEET THIS.
 CIR 567L-13
  
 58) NOTE: PLEASE SUBMIT A COMPLETE FIXTURE LEGEND FOR
 ALL SPECIFIC FIXTURES. THERE ARE SEVERAL ITEMS FOR FBC
 CHAPTER 13 AS NOTED ABOVE ALONG WITH OTHER ITEMS SUCH
 AS POOL AREA LIGHTS WHICH NEED TO BE REVIEWED.
 PLEASE SEE 411.4B, 680.22 AND 680.23 WHICH WILL GREATLY
 AFFECT THE REVIEW FOR TYPES OF FIXTURES PERMITTED.
 PLEASE PLACE NOTE ON LIGHTING PLANS FOR POOL AREA WHICH
 DOES NOT PERMIT ANY LOW VOLTAGE LIGHTING SYSTEMS WITHIN
 10FT OF THE WATERS EDGE.
 FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION, CLARITY
 AND COORDINATION.
  
 59) NOTE: PLEASE KEEP IN MIND TO INDICATE THE REQUIRED
 WIND LOAD RATINGS FOR ANY ROOF-TOP OR OUTSIDE POLE
 LIGHT PER SECTION 1609 OF THE FBC. THE CALCULATIONS
 WHICH NEED TO BE SUBMITTED WILL NEED TO SHOW THE EPA
 (EFFECTIVE PROJECTED AREA) OF ANY PROPOSED LIGHT
 FIXTURE. THE CALCULATIONS WILL BE PART OF THE
 STRUCTURAL REVIEW ONCE SHOWN AND SUBMITTED.
 ELECTRICAL PLANS MUST SHOW MINIMUM WIND LOAD DESIGNS.
  
 60) NOTE: IF A GUTTER IS STILL GOING TO BE PART OF THE
 FUTURE SERVICE PROPOSED DESIGN; PLEASE INCLUDE
 DIMENSIONS. NEC 366
 THIS INCLUDES ANY OTHER PROPOSED GUTTERS IF THEY ARE
 STILL PART OF THE DESIGN.
 PLEASE KEEP IN MIND PREVIOUS COMMENTS ABOVE WITH
 RESPECT TO NO MORE THAN 8FT OF TOTAL LENGTH OF
 UNPROTECTED CONDUCTORS.
  
 61) NOTE: THE RISER CONTAINS NOTES AND DETAIL FOR THE
 GROUNDING ELECTRODE SYSTEM HOWEVER THIS SEEMS TO BE
 MISSING THE REQUIRED FOUNDATION/FOOTER STEEL PER
 250.50. THE NOTE ON RISER MENTIONS *BUILDING STEEL*
 HOWEVER THIS BY DEFINITION THIS WOULD BE PART OF THE
 STRUCTURAL STEEL FOR THE BUILDING. THE
 FOUNDATION/FOOTER STEEL WOULD BE AT THE LOWEST POINT OF
 THE BOTTOM OF SUCH FOUNDATION.
 THIS MAY HAVE BEEN WHAT WAS MEANT BY NOTE HOWEVER THERE
 MAY BE SOME BUILDING STEEL EVEN IF POST TENSION CABLES
 SEEMS TO BE THE CONSTRUCTION SYSTEM.
 PLEASE ADJUST NOTE TO ALLEVIATE ANY CONFUSION.
  
 62) NOTE: PLEASE SEE SHEET E1 WHICH INDICATES A PANEL
 FP, YET THIS IS NOT ON RISER AND NO PANEL SCHEDULE
 COULD BE LOCATED.
 IF THIS IS PART OF THE FIRE PUMP, OR CONTROLLER PLEASE
 SEE NOTES ABOVE WITH RESPECT TO MORE INFORMATION
 NEEDED.
 695,408,215.5 ETC
  
 63) NOTE: PLEASE PLACE NOTE ON PLANS FOR COLOR CODING
 FOR 277/480V SYSTEMS AS FOLLOWS:
 BROWN, PURPLED, AND YELLOW.
 PLEASE KNOW AS THE NEC DOES NOT PROVIDE COLOR CODING OF
 ALL SYSTEMS AND ORANGE IS FOR OPEN DELTA HIGH LEG
 SYSTEMS THE CITY OF WEST PALM BEACH USED TO HAVE
 TECHNICAL AMENDMENTS FOR THIS ITEM. THE LOCAL TECHNICAL
 AMENDMENTS ARE NO LONGER IN EFFECT HOWEVER IN KEEPING
 WITH THE UNIFORMITY WITH ALL OTHER BUILDING SYSTEMS
 WITHIN THIS JURISDICTION AND IN THE INTEREST OF LIFE
 SAFETY AND FIRE HAZARD THE ABOVE COLOR CODING IS
 REQUIRED PER 90.4.
  
 64) NOTE: PLEASE INDICATE THE REQUIRED SIGN CIRCUIT PER
 600.5.
  
 65) NOTE: PLEASE CHECK WITH THE LOCAL FAA AUTHORITY FOR
 REQUIREMENTS OF ANY AIRCRAFT WARNING LIGHTS WHICH MAY
 BE REQUIRED. PLEASE CHECK WITH THE FAA WEBSITE OR
 CONTACT THE LOCAL AIRPORT AUTHORITY.
 THIS WILL AFFECT ELECTRICAL ON PLANS IF SO REQUIRED.
 ( OTHER HIGH-RISE BUILDINGS IN AREA DO CONTAIN
 LIGHTING).
  
  
  
 ** PLEASE BE SURE TO SUBMIT THE ABOVE INFORMATION AS
 WELL AS INFORMATION NOT YET SUBMITTED.
 PLEASE CALL TO GO OVER ANY COMMENTS WHICH MAY NOT BE
 CLEAR IN ANY MANNER. CONTACT INFORMATION IS BELOW. IF
 VOICE MAIL IS CONTACTED PLEASE BE SURE TO LISTEN TO
 MESSAGE AS I MAY NOT BE IN THE OFFICE.
 PLEASE LEAVE A MESSAGE WHEN CALLING AND THE CALL WILL
 BE RETURNED AS SOON AS POSSIBLE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  