Plan Review Notes
Plan Review Notes For Permit 08120552
Permit Number 08120552
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-30 20:02:35BUILDING PLAN REVIEW
 PERMIT: 08120552
 ADD: 455 HIBISCUS STREET
 CONT: "PLAN REVIEW"
 TEL: (561)239-6986 JOE SULLIVAN
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: DONALD T. YOSHINO, AIA
 STRUCTURAL ENGINEER: JOEL MIDDLEBROOKS, P.E.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 1E) INFORMATIONAL: PLANS ARE CURRENTLY BROUGHT IN AS A
 PLAN REVIEW OR MAJOR WORKING DRAWING REVIEW, AND ARE
 REVIEWED UNDER THE 2004 FBC BASE CODE WITH 2007
 SUPPLEMENTS. EFFECTIVE MARCH 1ST, 2009 THE 2007FBC BASE
 CODE WILL BE ENACTED. IF THIS PROJECT HAS NOT BEEN
 CONVERTED OVER TO A PERMIT APPLICATION, BEFORE MARCH
 1ST, 2009 THE
 PLANS ON THE NEXT REVIEW WILL BE REVIEWED UNDER THE
 2007 FBC AS THE BASE CODE.
  
 1F) PLEASE PROVIDE A UNITY OF TITLE FOR THREE LOTS THE
 HIGH RISE WILL BE BUILT ON. TABLE 602. WILL REQUIRE 3
 HR RATED WALLS THROUGH BUILDING WHERE RATED LOT LINES
 OCCURWITH NO UNITY OF TITLE.
  
 2) SOILS REPORT WAS NOT SUBMITTED, NO COPIES. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002 ENGINEERS
  
 SHEET S0.02 AUGER-CAST PILES INDICATES THERE WERE TEST
 COMPLETED BY ARDAMAN & ASSOC. REPORT# 08-2021DATED
 02-23-08.
  
 3) THRESHOLD BUILDING REQUIREMENTS:
  
 3A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 3B)THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 3C) INFORMATIONAL:
 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 4) INFORMATIONAL; 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) INFORMATIONAL: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 6) FBC 13-103.0 ENERGY CODE COMPLIANCE SHALL BE
 DEMONSTRATED BY SUBMITTAL OF APPROPRIATE CODE
 COMPLIANCE FORMS, NO ENERGY FORMS NOR INPUT DATA
 REPORTS WERE SUBMITTED.
  
 7) SHEET LS1 PLANS FAIL TO INDICATE THE FOLLOWING
 INFORMATION.110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6 & TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004. PLANS INDICATE ROUNDING
 DOWN NOT ROUNDING UP TO THE
 NEXT WHOLE NUMBER OR PERSON.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) NUMBER OF UNITS
 I ) NUMBER OF FLOORS
 J ) NUMBER OF BEDROOMS
 J) SQ. FT.( FOOTPRINT)
 K) SQ. FT. A/C SPACE PER FLOOR
  
 8) SHEET LS1 EXIT DOOR# 1, THE PLANS INDICATE THAT THE
 FULL 91? IS TAKEN FOR MEANS OF EGRESS, WHERE AS SHEET
 A11.01 INDICATES THAT THERE ARE (2) SIDE LIGHTS THAT
 ARE EACH 2?-1? PLEASE REVIEW SECTION 1008.1.1 MINIMUM
 CLEAR WIDTH FOR A DOORWAY IS 32? TO BE CONSIDERED IN A
 MEANS OF EGRESS.
  
 9) SHEET LS1 EXIT DOOR2 & 3, THE PLANS HAVE TAKEN THE
 FULL WIDTH OF THE DOOR OPENING, NOT SUBTRACTING THE
 DOOR WIDTH OF 2? OR A CLEAR OPENING OF 34? AND OCCUPANT
 LOAD OF 170 NOT 180. SECTION 1008.1.1.
  
 10) SHEET A2.01 DOOR# 101C IS WITHIN A 2 HR WALL BUT
 THE DOOR SCHEDULE ON SHEET A11.01 INDICATES A 45 MINUTE
 DOOR. SEE TABLE 715.3 OPENING PROTECTIVES. THE DOOR
 SCHEDULE ALSO INDICATES THE DOOR FRAME AND DOOR
 MATERIALS ARE CONSTRUCTED OF ALUMINUM. SHOW COMPLIANCE
 WITH SECTION 715.3.
  
 11) SHEET A2.1 ROOM 108 IT ROOM REQUIRES 1 HR RATED
 WALLS AND 20 MINUTE OPENING PROTECTION, SEE NFPA 645.2
 AND TABLE 715.3.
  
 12) SHEET A2.1 DOOR # 1123 C&D BOTH ARE LOCATED WITHIN
 A 2 HR FIRE RATED WALL THE DOOR SCHEDULE INDICATES 20
 MINUTE PLEASE REVIEW TABLE 715.3.
  
 13) SHEET A2.1 FOUR WINDOWS INDICATED AS (HH) ON SHEET
 A 12.01 AS 45MINUTE SHOULD READ 1 ? HR OPENING
 PROTECTION SEE TABLE 715.3, 2HR RATED WALL.
  
 14) SHEET A2.1 STAIR TOWER# 2THE INTERIOR WALL THAT
 BACKS UP AGAINST THE COMPUTER ALCOVE IS INDICATED AS A
 WALL TYPE ?1C? OR ONE HOUR WALL, PLEASE REVIEW SECTION
 1019.1.
  
 15) SHEET A2.1 STAIR TOWER # 2 EXTERIOR WALL IS MISSING
 THE WALL IDENTIFICATION TAG ALL TOGETHER, TABLE 602.
  
 16) SHEET A2.1 THERE ARE AREAS OF CONCERN WHERE THE
 FLOOR RATING WILL BE OF CONCERN:
 16A) THE FPL VAULT THE FLOOR RATING OF THE 2ND FLOOR
 OVER THE VAULT IS TO BE THE SAME RATING AS THE WALLS.
  
 17) SHEET A2.1 ROOM # 135 LINEN ROOM ALSO INDICATES A
 LAUNDRY CHUTE, THE LAUNDRY CHUTE DOES NOT PROVIDE A 2HR
 SHAFT ENCLOSURE PLANS INDICATE A WALL TYPE ELEVEN ON
 TWO SIDES OF THE ENCLOSURE SEE SECTION 707.13.1.
  
 18) SHEET A2.1 ROOM # 135 IS ALSO NOT ONLY A LINEN ROOM
 BUT A LAUNDRY CHUTE TERMINATION ROOM WITH THE DOOR
 REQUIRING A 45 MINUTE DOOR SEE 707.13.4.
  
 19) SHEET A2.1 DOOR # 103 AND WINDOW (W):
 19A) THE DOOR SCHEDULE INDICATES DOOR# 103 TO BE A 90
 MINUTE RATED OPENING DOOR TYPE ?B? A ALUMINUM AND
 GLAZED OPENING PLEASE PROVIDE DOCUMENTATION ON THE FIRE
 RATING OF THE ALUMINUM DOOR FRAME AND DOOR ASSEMBLY AS
 WELL AS GLAZING. OPENING PROTECTIVE?S 715.3. THE
 ALLOWABLE OPENINGS IN THIS WALL AREA FOR PROTECTED
 OPENINGS IS 75%. NOTE 704.8.1 DOES ALLOW THESE OPENINGS
 TO BE NOT RATED UP TO 75% OF THE WALL AREA BECAUSE OF
 THE FIRE SPRINKLED BUILDING!
  
 20) SHEET A2.1 DOOR# 103 (SHEET E-9) THIS DOORWAY HAS A
 EXIT SIGN INDICATING THIS IS A EXIST TO A PUBLIC WAY.
 IN A PREVIOUS MEETING DOOR # 21 HAD OPENED ONTO THE
 EASTERN EXPOSURE AND HAD THE SAME TYPE OF PROBLEM THAT
 CONFRONTS THE OCCUPANTS THAT NOW WILL BE EXITING THIS
 DOORWAY TO END UP AT THE PUBLIC WAY. THEY ARE TRAVELING
 WITHIN 5.72 FEET OF THE PROPERTY LINE AND NO PROTECTION
 OF FIRE DANGER FROM ADJOINING PROPERTIES, PLEASE REVIEW
 SECTION 1023.5.2 EGRESS COURTS, CONSTRUCTION AND
 OPENINGS & 1023.6 ACCESS TO THE PUBLIC WAY.
  
  
 21) SHEET A2.1 DOOR# 136B ROLL UP DOOR FOR THE TRASH
 ROOM, LOCATED FROM THE CENTERLINE OF THE ALLEY LESS
 THAN 20?-0? TABLE 602 NON-BEARING EXTERIOR WALLS
 REQUIRES 2HR WALLS AND 90 MINUTE OPENING PROTECTIVE?S
 PLEASE UP DATE THE DOOR SCHEDULE TABLE 715.3. PROVIDE
 MANUFACTURER?S SPECIFICATIONS ON FIRE RATING AND HOW
 THIS DOOR WILL AUTOMATICALLY CLOSE 715.3.7.
  
 22) SHEET A2.2 ASSEMBLY ROOM OR MEETING ROOM 201, LS
 SHEET LS 2 INDICATES 121 OCCUPANTS REQUIRING 2 EXITS AS
 PER TABLE 1014.1 THIS AMOUNT OF OCCUPANTS EXCEED THE
 ALLOWABLE OCCUPANT LOAD FOR ONE EXIT TABLE 1014.1. LS 2
 ONLY INDICATES ONE EXIT AND A NOTE FOR THE MONUMENTAL
 STAIR INDICATING SHAFT NOT REQUIRED AS PER SECTION
 707.2.2. THIS CODE SECTION IS INCORRECT. EITHER YOU ARE
 LOOKING AT:
 707. 2 EXCEPTION 2 WHERE A SHAFT ENCLOSURE IS NOT
 REQUIRED FOR AN ESCALATOR OR STAIR THAT IS NOT PART OF
 MEANS OF EGRESS.
  
 707.2 EXCEPTION 2.2 WHERE THE OPENINGS ARE PROTECTED BY
 A FIRE SHUTTER AT EVERY FLOOR, NOTE IF THE FIRE SHUTTER
 IS CLOSED HOW CAN IT BE PART OF A REQUIRED EGRESS.
  
 707.2 EXCEPTION # 7, (7.2) CAN?T BE USED AGAIN BECAUSE
 IT IS PART OF A REQUIRED MEANS OF EGRESS.
  
 23) SHEET A2.2 DOOR# 201A IS WITHIN A 2HR RATED WALL
 BUT THE DOOR SCHEDULE INDICATES THE DOOR TO BE A 20
 MINUTE DOOR. PLEASES REVIEW TABLE 715.3 OPENING
 PROTECTIVE?S 2HR WALL REQUIRES A 1 ? OPENING
 PROTECTIVE.
  
 24) SHEET A2.2/ LS2, DOOR# 201A WHICH LEADS FORM
 MEETING ROOM 201 OUT INTO THE PARKING GARAGE BEHIND
 PARKED CARS TO REACH THE VERTICAL EXIT ENCLOSURE.
 1013.2 DOES NOT ALLOW TRAVEL EXIT ACCESS THROUGH A
 HIGHER HAZARD OCCUPANCY WITHOUT A RATED CORRIDOR TO
 TRAVEL IN TO REACH THE VERTICAL EXIT. PLEASE SEE
 ATTACHED BOAF INFORMAL INTERPRETATIONS.
  
 25) SHEET A2.2 PLEASE REVIEW THIS LEVEL OF GARAGE AND
 ALL ABOVE FOR CLASSIFICATION AS TO OPEN OR ENCLOSED
 GARAGE. 406.3.3.1. IF CONSIDERED OPEN THE DOOR SCHEDULE
 IS MISSING THE WIND DESIGN PRESSURES, ALL ARE
 +00.0/-00.0. 1609.6.2.2 COMPONENTS AND CLADDING THIS
 COMMENT WILL STAND FOR ALL OPENINGS WITHIN THE OPEN
 PARKING GARAGE FOR ALL FLOORS.
  
 26) SHEET A2.2 THE ELEVATOR MACHINE ROOM DOOR # 205
 DOES NOT INDICATE ANY FIRE RATING IN THE DOOR SCHEDULE
 SHEET A11.01 REVIEW 3006.4 REQUIRING A 2HR RATING.
  
 27) SHEET A2.02 NOTE FOR STRUCTURAL DRAWINGS TO PROVIDE
 DETAIL FOR ALL BLOCK WALLS TO WITHSTAND IMPACT LOADS,
 CRASH WALL STRUCTURAL PLANS HAVE SECTIONS THROUGH FOR 3
 RD AND FOURTH LEVEL BUT NONE FOUND FOR THE SECOND
 LEVEL. 1607.7.3.
  
 28) SHEET A2.02 STAIR# 2 THE EXTERIOR WALL IS MISSING
 THE WALL IDENTIFICATION TYPE AT THE EXTENSION OF
 STAIRWELL. 1019.1.
  
 29) SHEET A2.02 THE EAST SIDE OF THE OPEN PARKING
 GARAGE, THE PLANS DO NOT PROVIDE ANY DIMENSIONS AS TO
 THE DISTANCE THE FACE OF THE BUILDING IS LOCATED TO THE
 PROPERTY LINE. TABLE 704.8.
  
 30) SHEET A2.02 STAIRWELL# 3 WINDOW AA DOES NOT
 INDICATE ANY OPENING PROTECTIVE?S ON SHEET A12.01
 WINDOW SCHEDULE. PLEASE REVIEW 1019.1.4. VERTICAL
 ENCLOSURE EXTERIOR WALLS.
 EXTERIOR WALLS OF A VERTICAL EXIT ENCLOSURE SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 704 FOR
 EXTERIOR WALLS. WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE EXTERIOR OF THE STAIRWAY AND THE
 WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE
 BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES (3.14
 RAD), THE BUILDING EXTERIOR WALLS WITHIN 10 FEET (3048
 MM) HORIZONTALLY OF A NONRATED WALL OR UNPROTECTED
 OPENING SHALL BE CONSTRUCTED AS REQUIRED FOR A MINIMUM
 1-HOUR FIRE-RESISTANCE RATING WITH ?-HOUR OPENING
 PROTECTIVE?S. THIS CONSTRUCTION SHALL EXTEND VERTICALLY
 FROM THE GROUND TO A POINT 10 FEET (3048 MM) ABOVE THE
 TOPMOST LANDING OF THE STAIRWAY OR TO THE ROOF LINE,
 WHICHEVER IS LOWER. THIS NOTE WILL SERVE FOR ALL
 FLOORS.
  
 31) SHEET A2.03 DOOR # 23 & 33 BOTH ARE INDICATED AS
 INTERIOR DOORS ON THE DOOR SCHEDULE BUT THIS LEVEL OF
 THE PARKING GARAGE IS CONSIDERED OPEN? 1609.6.2.2
 PLEASE INDICATE POSITIVE AND NEGATIVE WIND PRESSURES.
 THIS STATEMENT WILL BE COMMON TO ALL FLOORS.
  
 32) SHEET A2.03 ELEVATOR MACHINE ROOM 304 THIS DOOR ON
 THE DOOR SCHEDULE IS INDICATED AS A 20 MINUTE DOOR,
 PLEASE REVIEW 3006.4. NOT LESS THAN THE RATING OF THE
 HOIST WAY ENCLOSURE. 2 HR HOIST WAY ENCLOSURE REQUIRES
 1 ? HOUR OPENING PROTECTIVE.
  
 33) SHEET A2.04 ROOF TOP GARDEN AREA DOES NOT INDICATE
 ANY PITCH AS IN A ROOF TOP OR IN PLANTERS, ROOF DRAINS,
 SCUPPERS AND OR SECONDARY OR OVERFLOW ROOF DRAINS. NOTE
 THE SAME LEVEL AS THE GARAGE FLOOR. PLEASE INDICATE THE
 TYPE OF ROOF COVERING TO BE SUPPLIED.1503.1, 1503.4,
 1503.4.2 & 1503.4.3.
  
 34) SHEET A2.04 DOOR# 400A IS MISSING THE 18? ON THE
 LATCH SIDE OF THE DOOR 11-4.13.6
 MANEUVERING CLEARANCES AT DOORS.
  
 35) A2.05 DOOR# 524 THE ELECTRIC CLOSET THE DOORS SWING
 ACROSS ONE HALF OF THE REQUIRED EGRESS CORRIDOR WIDTH.
 1008.1.8.8 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF
 THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY,
 OR LANDING, NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY OR LANDING, WHEN FULLY OPEN. DOORS SHALL NOT
 OPEN IMMEDIATELY ONTO A STAIR WITHOUT A LANDING. THE
 LANDING SHALL HAVE A WIDTH AT LEAST EQUAL TO THE WIDTH
 OF THE DOOR.
  
 36) A2.05 STAIR TOWER# 2 THE PLANS INDICATE WOVEN WIRE
 SECURITY PARTITION AND DOOR BENEATH SLAB. PLEASE
 EXPLAIN DOES THIS DOOR BLOCK THE VERTICAL EXIT?
 1019.1.1.
 1019.1.1 OPENINGS AND PENETRATIONS.
 EXIT ENCLOSURE OPENING PROTECTIVE?S SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 715.
 EXCEPT AS PERMITTED IN SECTION 402.4.6, OPENINGS IN
 EXIT ENCLOSURES OTHER THAN UNEXPOSED EXTERIOR OPENINGS
 SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO
 THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR
 EGRESS FROM THE ENCLOSURE.
  
 37) 37) A2.05 UNIT M ROOM 525 HAS A VERTICAL CHASE
 BUILT INTO ONE CORNER WITH WALL IDENTIFICATION TAG WALL
 TYPE 6. THIS WALL DOES NOT HAVE A STC RATING. 1207.2.
  
 38) A2.05 THIS FLOOR IS THE FIRST FLOOR ASSEMBLY WHERE
 STRUCTURE BORNE SOUND WILL NEED TO BE ADDRESSED. THIS
 COMMENT WILL ALSO STAND FOR ALL FLOORS ABOVE. 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 39) A2.05 ELEVATOR LOBBY DOOR 514A IS INDICATED AS A 20
 MINUTE DOOR IN THE DOOR SCHEDULE BUT ALSO A TYPE ?K? OR
 ALUMINUM DOOR PLEASE PROVIDE MANUFACTURERS SPEC FOR 20
 MINUTE FIRE RATING USING THIS MATERIAL. TABLE 715.3.
  
 40) A2.05 ELEVATOR LOBBY DOORS ARE TO BE FIRE RATED
 DOORS 707.14.1 ELEVATOR LOBBY .HOW ARE THESE DOORS TO
 CLOSE UPON ACTIVATION OF ALARM SYSTEM 715.3.7.
  
 41) A2.05 THIS COMMENT WILL STAND FOR ALL FLOORS. DOOR
 513 THAT LEADS TO THE MAIDS ROOM IS LISTED WITHIN THE
 DOOR SCHEDULE AS A 20 MINUTE DOOR. THIS WOULD NORMALLY
 BE CORRECT BUT IN THIS CASE THE DOOR ALSO ACTS AS THE
 LAUNDRY CHUTE ACCESS DOOR THAT SEPARATES THE LAUNDRY
 CHUTE ROOM FROM THE CORRIDOR. 707.13.3 REFUSE AND
 LAUNDRY CHUTE ACCESS ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS COMPLETELY ENCLOSED BY
 CONSTRUCTION THAT HAS A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR AND OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVE?S HAVING A
 FIRE PROTECTION RATING OF NOT LESS THAN ? HOUR AND
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE
 DETECTION OF SMOKE.
  
 42) SHEET A2.05 UNIT 501 THERE IS A WINDOW THAT IS NOT
 IDENTIFIED AND EXERCISE ROOM WINDOW DOES NOT HAVE A
 WINDOW IDENTIFICATION TAG. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 43) SHEET A2.05 EXERCISE ROOM WINDOW SINCE THE WINDOW
 SCHEDULE DOES NOT INDICATE ROOM WITH WINDOW TYPE THE
 DESCRIPTION OF THIS WINDOW IS BLOCKED ON THE
 ELEVATIONS, MAY BE A HAZARDOUS LOCATION PROVIDE
 ADDITIONAL INFORMATION. 106.1.2, 2406.3 HAZARDOUS
 LOCATION.
  
  
 44) PLEASE PROVIDE ELEVATIONS FOR THE POOL DECK WITH
 SLOPES, VARIOUS AREAS INDICATE SLOPED DECKS BUT THE
 TRUE ELEVATION ARE NOT PROVIDED SLOPES OF THE WET DECKS
 (424.1.3.1.2) . ALSO NOTE WHAT IS GOING TO BE THE
 COATING ON THE DECK MAKING IT WATERTIGHT. PLANS WILL
 NEED TO INDICATE DECK DRAINS AS WELL AS DRAINS FOR
 PLANTERS, NOTE ? OF THE VERTICAL CONTRIBUTION (WALL
 AREA) WILL NEED TO BE FIGURED INTO THE POOL DECK
 DRAINAGE CALCULATIONS.
  
 45) SHEET A2.05 ALSO INDICATES A SLEEVE FOR A ADA
 COMPLIANT LIFT. IF THE LIFT IS PROVIDED THEN PROVIDE
 MANUFACTURERS SPEC ON LIFT AND SLEEVE. 424.1.2.5.6- NOT
 A REQUIREMENT.
  
 46) SHEET A2.05 GLASS WALL WILL NEED TO BE FIGURED AS A
 GUARD RAIL SYSTEM MEETING THE REQUIREMENTS OF 2407
 .1-3.
  
 47) THIS COMMENT WILL STAND FOR ALL FLOORS. BETWEEN
 UNITS 509 & 510 THERE ARE DOUBLE DOORS PLEASE PROVIDE
 THE STC RATING FOR THESE DOORS .1207.2.
  
 48) SHEET A2.08 THE ROOF TOP DOOR IS MISSING TAG FOR
 IDENTIFICATION, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 49) SHEET A2.08 GRID LINE C AND 11 THERE APPEARS TO BE
 A ROOF TOP HATCH, THE PENTHOUSE FLOOR PLAN DOES NOT
 INDICATE ANY SUCH HATCH?
  
 50) SHEET A2.08 ROOF TOP NOTES INDICATE THE USE OF NOA
 07-0517.02 SYSTEM TYPE ?F?
 FULLY ADHERED MEMBRANE. THIS SUB-SYSTEM AT THE HEADING
 OF THE PAGE INDICATES THIS IS FOR A NON-INSULATED
 LIGHTWEIGHT ROOFING APPLICATION, NOT THE ROOF SYSTEM
 R-VALUE PROVIDED ON THE PLAN OF R-11.37. NOTE THIS R
 VALUE WILL NEED TO MATCH ON THE INPUT DATA SHEET OF THE
 ENERGY CALCULATIONS. CHAPTER 13-404 ROOFS/ CEILINGS.
 PLEASE ALSO PROVIDE A INSULATION LAYOUT SHEET SHOWING
 THE MINIMUM OF R-11.37 AT THE ROOF DRAINS.
 13-404.1ABCD.1, SEE BOAF INFORMAL INTERPRETATIONS.
 SHEET A6.01 DETAIL A14.
  
 51) SHEET A2.08/ M11 BOTH INDICATE THE USE OF A/C
 STANDS, PLEASE SEE TABLE 15.22.3 FOR MINIMUM LEG HEIGHT
 OF STANDS. NOTE TAKE INTO ACCOUNT THE DEPTH OF
 INSULATION REQUIRED IT WILL TAKE TO CREATE THE ROOF
 SLOPE REQUIRED.
  
 52) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
  
 FL BLD CODE 1609.6.2.2/ RULE 9B-72 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 52A) FIXED
 52B) STOREFRONT
 52C) CURTAIN-WALL
 52D) MULLIONS VERTICAL/ HORIZONTAL
 52E) GLAZED EXTERIOR DOORS
 52F) INSULATED EXTERIOR DOORS SWING, SINGLE & PAIRS
 52G) OVERHEAD OR COIL DOORS
 52H) EXTERIOR LOUVER DOORS
 52I WALL LOUVERS
 52J) EFIS SYSTEMS
 52K) ROOFING PRODUCTS, INCLUDING WATERPROOFING
 52L) PRE-ENGINEERED A/C STANDS
  
 53) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 54) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 55) WIND PRESSURES FOUND ON SHEET S8.00 FOR WALL DESIGN
 ARE DESIGNED TO ASCE 7-02 FOR
 BUILDINGS LESS THAN OR EQUAL TO SIXTY FEET, THE TEXT
 SHOULD READ GREATER THAN OR EQUAL TO SIXTY FEET.
 MISPRINT.
  
 56) SHEET A4.01 INDICATES THE FLOOR BETWEEN GARAGE AND
 RESIDENCE TO BE SPRAY ON INSULATION TYPE PLEASE PROVIDE
 MANUFACTURERS SPEC FOR THIS INSULATION OPEN TO THE
 ELEMENT OF WIND. 13-405.1.A.B.1.
  
 57) SHEET A4.07 POOL COLLECTOR TANK PENETRATES THE
 FLOOR SLAB LETTING THE 5TH FLOOR AND FOURTH FLOOR
 COMMUNICATE TOGETHER. HOW IS A FIRE RATING TO BE
 MAINTAINED AT THE 5TH FLOOR ASSEMBLY, THE DOOR LEADING
 TO THE POOL EQUIPMENT (402) ALSO DOES NOT SHOW AS A
 RATED DOOR ON THE DOOR SCHEDULE. PLEASE PROVIDE MORE
 INFORMATION AS WHAT TYPE OF CHEMICALS WILL BE STORED IN
 THE POOL EQUIPMENT ROOM AND QUANTITIES. SECTION 707.2
 EXCEPTIONS,
 715.3 OPENING PROTECTIVE?S & TABLE 307.7(2).
  
 58) SHEET A8.01 INDICATES VARIOUS MASONRY WALLS WITH A
 2 HR FIRE RATING, PLEASE PROVIDE THE MINIMUM EQUIVALENT
 THICKNESS OF THE BLOCK FOR BEARING AND NON BEARING
 WALLS TABLE 721.3.2.THIS REPORT SHOULD BE PREPARED BY
 THE BLOCK MANUFACTURER.
  
 59) PLEASE PROVIDE DETAILS FOR PENETRATIONS OF FIRE
 RATED WALLS (712.3.1) AND PENETRATIONS THROUGH
 HORIZONTAL ASSEMBLIES (712.4.1).
  
 60) SHEET A9.01 PLEASE PROVIDE WHICH OF THE ELEVATORS
 MEETS THE SIZE REQUIREMENTS TO ACCOMMODATE A AMBULANCE
 STRETCHER, SECTION 3002.4. 24?X76? PLEASE PROVIDE A
 DEPICTION WITHIN THE CAB.
  
 61) SECTION 3002.8 EACH ENCLOSED ELEVATOR LOBBY AND
 EACH ELEVATOR MACHINE ROOM SHALL BE PROVIDED WITH AN
 APPROVED SMOKE DETECTOR OR OTHER AUTOMATIC FIRE ALARM
 INITIATING DEVICE WHERE ALLOWED BY NFPA 72 LOCATED IN
 THE LOBBY CEILING IN ACCORDANCE WITH
 NFPA 72. SMOKE DETECTORS SHALL BE INSTALLED IN HOIST
 WAYS WHICH ARE SPRINKLED, AND SHALL NOT BE INSTALLED IN
 UNSPRINKLED ELEVATOR HOIST WAYS UNLESS THEY ARE
 INSTALLED TO ACTIVATE THE HOIST WAY SMOKE RELIEF
 EQUIPMENT. WHEN THE SMOKE DETECTOR IS ACTIVATED, ALL
 AFFECTED ELEVATORS SHALL OPERATE IN CONFORMANCE WITH
 NFPA 72, SECTION 6.15.3. FIRE ALARM INITIATING DEVICES
 ARE NOT REQUIRED FOR ELEVATOR RECALL AT UNENCLOSED
 LOBBIES. E- 10 MISSING SMOKE DETECTOR IN ELEVATOR
 MACHINE ROOM, E-11 MISSING SMOKE DETECTOR IN ELEVATOR
 MACHINE ROOM AND E 13-E15 DO NOT SHOW SMOKE DETECTORS
 IN THE ELEVATOR LOBBY?S.
  
 62) SHEET E13-E15 ALSO DO NOT INDICATE HOW THE ELEVATOR
 LOBBY DOORS WILL AUTOMATICALLY CLOSE UPON THE
 ACTIVATION OF ALARM SYSTEM, NOR DID THE DOOR SCHEDULE
 A11.01. REQUIRED OPENING PROTECTION 707.14.1/ 715.3.
  
 63) A9.02 NOR FP1-FP8 LAUNDRY CHUTE DETAILS DOES NOT
 PROVIDE INFORMATION AS TO THE REQUIRED FIRE SPRINKLER
 REQUIRED WITHIN THE LAUNDRY SHAFT, 707.13.6.
  
 64) PROVISO: PROVIDE SHOP DRAWINGS FOR LAUNDRY CHUTE TO
 BE REVIEWED BY DESIGN TEAM BEFORE SUBMITTAL TO BUILDING
 DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...
  
 65) SHEET A10.01 DETAIL A14 AND A10.02 DETAIL A10,
 INDICATES THE SECURITY GATE WITHIN THE CONFINES OF THE
 VERTICAL STAIR ENCLOSURE, EXIT ENCLOSURES SHALL NOT BE
 USED FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS 1019.1.
 BOTH THE BUILDING AND FIRE REVIEWER WILL NEED TO REVIEW
 IF THIS WILL BE ALLOWED. THE CITIES INTERPRETATION HAS
 BEEN NOT TO ALLOW EVEN SECURITY CAMERAS WITHIN A
 VERTICAL EXIT. SUPPLY INFORMATION ON THE LOCKING
 MECHANISM, AUTOMATIC CLOSING DEVICE AND HOW BOTH WOULD
 BE FAIL SAFE UPON THE ACTIVATION OF THE ALARM SYSTEM.
 WHAT WOULD TRIGGER THE ACTIVATION OF THIS SYSTEM,
 SPRINKLERS, SMOKE ALARM ?
  
 66) BOTH A10.01 AND A10.02 FAIL TO INDICATE COMPLIANCE
 WITH 403.13 STAIRWELL PRESSURIZATION REQUIREMENTS FOR
 HIGH-RISE BUILDINGS EITHER THROUGH PASSIVE OR
 MECHANICAL SYSTEMS, THE MECHANICAL PLANS DO INDICATE
 THE CHASE AND FAN MOTORS FOR MECHANICAL PRESSURIZATION.
 PLEASE MAKE NOTATION WHERE COMPLIANCE CAN BE FOUND.
  
 67) PLEASE PROVIDE ADDITIONAL INFORMATION TO THE DOOR
 SCHEDULE OR DOORS INTO THE ENCLOSURE COMPLYING WITH
 403.12STAIRWAY DOOR OPERATION. SINCE COMMENT 65 ABOUT
 THE SECURITY GATE WITHIN THE STAIRWELL WILL MOST LIKELY
 NOT BE APPROVED. IF THE STAIRWELL DOORS WILL BE LOCKED
 FROM THE STAIRWELL SIDE THEY SHALL BE CAPABLE OF BEING
 UNLOCKED SIMULTANEOUSLY WITHOUT UNLATCHING UPON SIGNAL
 FROM THE FIRE COMMAND CENTER.
  
 68) SHOW COMPLIANCE WITH 403.12.1 STAIRWAY
 COMMUNICATION SYSTEMS 403.12.1FOR BOTH STAIR TOWERS.
  
 69) PLEASE PROVIDE COMPLIANCE WITH 403.15SMOKE CONTROL
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 909 SMOKE
 CONTROL SYSTEMS REQUIREMENTS FOR HIGH RISE BUILDINGS.
 THE MECHANICAL PLANS DO NOT INDICATE HOW THIS WILL BE
 ACCOMPLISHED.
  
 70) SHEET A10.03 GLASS HANDRAILS AND GUARDS, PLEASE
 SHOW COMPLIANCE WITH :
 2407.1 MATERIALS.
 GLASS USED AS STRUCTURAL BALUSTRADE PANELS IN RAILINGS
 SHALL BE CONSTRUCTED OF EITHER SINGLE FULLY TEMPERED
 GLASS, LAMINATED FULLY TEMPERED GLASS OR LAMINATED
 HEAT-STRENGTHENED GLASS. GLAZING IN RAILING IN-FILL
 PANELS SHALL BE OF AN APPROVED SAFETY GLAZING MATERIAL
 THAT CONFORMS TO THE PROVISIONS OF SECTION 2406.1.1.
 FOR ALL GLAZING TYPES, THE MINIMUM NOMINAL THICKNESS
 SHALL BE ? INCH (6.4 MM). FULLY TEMPERED GLASS AND
 LAMINATED GLASS SHALL COMPLY WITH CATEGORY II OF CPSC
 16 CFR 1201, LISTED IN CHAPTER 35.
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7. A
 SAFETY FACTOR OF FOUR SHALL BE USED.
 607.7.1 HANDRAILS AND GUARDS.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE DESIGNED TO
 RESIST A LOAD OF 50 PLF (0.73 KN/M) APPLIED IN ANY
 DIRECTION AT THE TOP AND TO TRANSFER THIS LOAD THROUGH
 THE SUPPORTS TO THE STRUCTURE.
 EXCEPTIONS:
 1. FOR ONE- AND TWO-FAMILY DWELLINGS, ONLY THE SINGLE,
 CONCENTRATED LOAD REQUIRED BY SECTION 1607.7.1.1 SHALL
 BE APPLIED.
 2. IN GROUP I-3, F, H AND S OCCUPANCIES, FOR AREAS THAT
 ARE NOT ACCESSIBLE TO THE GENERAL PUBLIC AND THAT HAVE
 AN OCCUPANT LOAD NO GREATER THAN 50, THE MINIMUM LOAD
 SHALL BE 20 POUNDS PER FOOT (0.29 KN/M).
 1607.7.1.1 CONCENTRATED LOAD.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST
 A SINGLE CONCENTRATED LOAD OF 200 POUNDS (0.89 KN),
 APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP,
 AND HAVE ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO
 TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL
 ELEMENTS OF THE BUILDING. THIS LOAD NEED NOT BE ASSUMED
 TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN THE
 PRECEDING PARAGRAPH.
 1607.7.1.2 COMPONENTS.
 INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL),
 BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO
 WITHSTAND A HORIZONTALLY APPLIED NORMAL LOAD OF 50
 POUNDS (0.22 KN) ON AN AREA EQUAL TO 1 SQUARE FOOT
 (0.093M2), INCLUDING OPENINGS AND SPACE BETWEEN RAILS.
 REACTIONS DUE TO THIS LOADING ARE NOT REQUIRED TO BE
 SUPERIMPOSED WITH THOSE OF SECTION 1607.7.1 OR
 1607.7.1.1.
 1607.7.1.3 STRESS INCREASE.
 WHERE HANDRAILS AND GUARDS ARE DESIGNED IN ACCORDANCE
 WITH THE PROVISIONS FOR ALLOWABLE STRESS DESIGN
 (WORKING STRESS DESIGN) EXCLUSIVELY FOR THE LOADS
 SPECIFIED IN SECTION 1607.7.1, THE ALLOWABLE STRESS FOR
 THE MEMBERS AND THEIR ATTACHMENTS ARE PERMITTED TO BE
 INCREASED BY ONE-THIRD.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A
 MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL
 FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD.
  
 71)SHEET A11.01 DOOR SCHEDULE IS NOT COMPLETE, REMARKS
 ARE FOR THE MOST PART OPEN, NO MENTION OF DOOR
 HARDWARE, LOCKS LEVERS, PANIC HARDWARE, HINGES,
 ELECTRONIC LOCKS AND CLOSERS. SECTION 1008.
  
 72) SHEET A12.01 WINDOW SCHEDULE IS NOT COMPLETE. THE
 WINDOW SCHEDULE NOR PLANS HAVE INDICATED FOR THIS
 PROJECT IF FROM GRADE TO 30?-0? IF LARGE MISSILE WILL
 BE INSTALLED FROM 30?-60? SMALL MISSILE AND ABOVE 60?
 RATED ONLY FOR WIND. IF THE PROJECT DOES ELECT TO
 INSTALL WINDOWS AS SUCH PLEASE PROVIDE A DIAGRAM AND
 ALSO INCLUDE THE INTERIOR ZONE AND END ZONES. THE
 THRESHOLD INSPECTOR WILL NEED SUCH A DOCUMENT TO KEEP
 THE WINDOW PLACEMENT CORRECT, PLEASE ALSO PROVIDE THE
 WINDOW, REPORT NUMBER (FL OR NOA) AND ASSOCIATED
 PRESSURES ON THE SAME DOCUMENT. 1609.6.2.2.
  
  
 73) THIS COMMENT WILL STAND FOR ALL 14.00 SERIES PLANS.
 IN MOST CASES THE SUITE ENTRY DOORS ARE RECESSED IN THE
 CORRIDORS. SINCE THESE DOORS ARE 20 MINUTE RATED THEY
 DO ALSO REQUIRE CLOSERS AND LATCHES. 11-4.13.6 DOES
 REQUIRE A 12 INCH CLEARANCE ON THE CORRIDOR LATCH SIDE
 OF THE DOOR, IN MANY CASES THE PLANS ARE SHORT OF THE
 ONE FOOT REQUIREMENT.
  
 74) A12.01 WINDOW (N) IS A CURTAIN WALL SYSTEM PLEASE
 PROVIDE A LISTED FLOOR ASSEMBLY FOR THIS SYSTEM.
 04.13.1 VOIDS.
 THE VOID CREATED AT THE INTERSECTION OF A FLOOR/CEILING
 ASSEMBLY AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713.4.
  
 713.4 EXTERIOR CURTAIN WALL/FLOOR INTERSECTION.
 WHERE FIRE- RESISTANCE-RATED FLOOR OR FLOOR/CEILING
 ASSEMBLIES ARE REQUIRED, VOIDS CREATED AT THE
 INTERSECTION OF THE EXTERIOR CURTAIN WALL ASSEMBLIES
 AND SUCH FLOOR ASSEMBLIES SHALL BE SEALED WITH AN
 APPROVED MATERIAL OR SYSTEM TO PREVENT THE INTERIOR
 VERTICAL SPREAD OF FIRE. SUCH MATERIAL OR SYSTEMS SHALL
 BE SECURELY INSTALLED AND CAPABLE OF PREVENTING THE
 PASSAGE OF FLAME AND HOT GASES SUFFICIENT TO IGNITE
 COTTON WASTE WHERE SUBJECTED TO ASTM E 119
 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF WATER
 (2.49 PA) FOR THE TIME PERIOD AT LEAST EQUAL TO THE
 FIRE-RESISTANCE RATING OF THE FLOOR ASSEMBLY. HEIGHT
 AND FIRE-RESISTANCE REQUIREMENTS FOR CURTAIN WALL
 SPANDRELS SHALL COMPLY WITH SECTION 704.9.
  
 75) LOUVERS NEW TO THE 2004 FBC- 2007
 SUPPLEMENTS1609.1.4(5) LOUVERS PROTECTING INTAKE AND
 EXHAUST VENTILATION DUCTS NOT ASSUMED TO BE OPEN THAT
 ARE LOCATED WITHIN 30 FEET (9144 MM) OF GRADE SHALL
 MEET REQUIREMENTS OF THE LARGE MISSILE TEST.
 IMPACT-RESISTANT COVERINGS SHALL BE TESTED AT 1.5 TIMES
 THE DESIGN PRESSURE (POSITIVE OR NEGATIVE) EXPRESSED IN
 POUNDS PER SQUARE FEET AS DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING SECTION 1609 FOR WHICH THE
 SPECIMEN IS TO BE TESTED.
  
 76) A12.01 THERE ARE MANY VARIOUS WINDOW WITHIN THE
 WINDOW SCHEDULE THAT QUALIFY AS A
 HAZARDOUS LOCATION 2406.3(7). PLEASE INDICATE AS SUCH
 IN WINDOW SCHEDULE REMARKS.
  
 77) SHEET A14.6 ACCESSIBLE UNIT THE PLAN INDICATES AT
 THE KITCHENETTE ? ON WALL BEYOND-NO BASE CABINET AT
 SINK?, YET THE PLAN CLEARLY INDICATES SWING DOORS ON
 THE SINK BASE UNIT. PLEASE CLARIFY.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK. THIS NOTE WILL STAND FOR ALL ACCESSIBLE UNITS.
  
 78) SHEET A14.01 ENTRY DOOR# 1. ALTHOUGH THIS UNIT IS
 NOT AN ACCESSIBLE UNIT THE CODE DOES NOT DISCERN OR
 MAKE ACCEPTATIONS TO 11-4.13.6 MANEUVERING CLEARANCES
 AT DOORS .
 THIS DOOR REQUIRES A DOOR CLOSURE AND LATCH THUS
 REQUIRING THE 1?-0? CLEAR ON THE CORRIDOR SIDE OF THE
 DOOR. TWO ISSUES, AGAIN THE DOOR SCHEDULE DOES NOT
 INDICATE THE HARDWARE REQUIRED FOR THIS DOOR.
  
 THE SECOND ISSUE IS ONE THAT CAN BE ARGUED, WE HAVE
 ACCESSIBLE ROOM MAKING AN EXEMPTION TO THE OTHER GUEST
 ROOMS. NO WHERE IN 11-4.13.6 DOES IT INDICATE
 EXCEPTIONS. IF A DISABLED PERSON RENTS TWO ROOM NOT
 ADJOINING AND WANTS TO CHECK ON THEIR CHILDREN IN
 ANOTHER ROOM THAT IS NOT ACCESSIBLE THEY WOULD BE
 UNABLE TO DO SUCH BECAUSE OF THE LIMITATION. NEIL
 MELICK OUR FORMER BUILDING OFFICIAL HAS SAT ON THE
 GOVERNORS? TAC BOARD FOR THE DISABLED AND NOW SITS ON
 THE FED BOARD, HE WILL BE CHECKING IN ON THIS SITUATION
 AND PROVIDE FURTHER INSIGHT. THIS COMMENT WILL STAND
 FOR ALL FLOORS.
  
 79) SHEET A2.01. ANOTHER ACCESSIBLE ISSUE WILL BE THE
 SERVING AND DINING AREA FIRST FLOOR THE BUFFET AND
 BREAKFAST AREAS, PLEASE SHOW COMPLIANCE WITH: SECTIONS
 11-5.1. 5% OF DINING AREAS, INCLUDING THE OUTSIDE
 DINING AREA AND 11-5.2 COUNTERS AND BARS (BUFFET AREA).
  
 80) SHEET A2.01. THE PASSENGER LOADING ZONE, PLEASE
 PROVIDE THE VERTICAL CLEARANCE IN THIS AREA AS WELL AS
 THE HEIGHT ALONG THE VEHICLE ROUTE. 11-4.6.5 VERTICAL
 CLEARANCE. PROVIDE MINIMUM VERTICAL CLEARANCE OF 114
 INCHES (2895 MM) AT ACCESSIBLE PASSENGER LOADING ZONES
 AND ALONG AT LEAST ONE VEHICLE ACCESS ROUTE TO SUCH
 AREAS FROM SITE ENTRANCE(S) AND EXIT(S). AT PARKING
 SPACES COMPLYING WITH SECTION 11-4.1.2(5)(B), PROVIDE
 MINIMUM VERTICAL CLEARANCE OF 98 INCHES (2490 MM) AT
 THE PARKING SPACE AND ALONG AT LEAST ONE VEHICLE ACCESS
 ROUTE TO SUCH SPACES FROM SITE ENTRANCE(S) AND EXIT(S).
  
 81) SHEET A15.01 THE REFLECTED CEILING PLAN INDICATES
 DROP CEILINGS IN THE COMPUTER ALCOVE AND LOBBY AREA BUT
 THE SECTION ON A4.03 DOES NOT PROVIDE DETAIL AS TO HOW
 THE GYPSUM WALL BOARD IS TO BE INSTALLED AT THE VARIOUS
 HEIGHTS, 106.1.2 ADDITIONAL INFORMATION REQUIRED, AND
 SECTION 2508.1 & TABLE 2508.1/ GYPSUM WALLBOARD.
  
 82) A15.01 LIGHTING NICHE THAT LEADS TO THE ELEVATORS
 SHEET A4.02 INDICATES VARIOUS CEILING HEIGHTS, SOFFITS,
 ETC BUT AGAIN THERE IS NO SECTION OR DETAIL MARKERS
 PROVIDING HOW THE FINISH GYPSUM WALL BOARD CEILINGS ARE
 TO BE INSTALLED THERE ARE NO DETAILS FOR THIS TYPE OF
 APPLICATIONS, SECTION 2508.1 & TABLE 2508.1 / GYPSUM
 WALLBOARD. THIS COMMENT WILL STAND FOR ALL FLOORS.
  
 83) A15.01 NOTE# 8 INDICATES FOR FINISH INFORMATION WE
 ARE TO REFER TO THE I. D. SET, NO FINISHES HAVE BEEN
 PROVIDED FOR THIS PLAN REVIEW.
  
 83A) PLEASE PROVIDE COMPLIANCE WITH 803.1AND TABLE
 803.5.
  
 83B) SINCE THERE ARE NO DETAILS OF SOFFITS NOR WALL
 FINISH DETAILS PLEASE REVIEW THE NEW DETAILS FOR
 803.4.2 SET OUT CONSTRUCTION.
  
 83C) IF THERE IS TO BE TEXTILE WALL COVERINGS COMPLY
 WITH 803.6.1.
  
 84) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  